Plan Review Details - Permit 00091204
Plan Review Stops For Permit 00091204
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-11-07 Cont ID  
Sent By dpalmer Date 2000-11-07 Time 15:14 Rev Time 0.00
Received By dpalmer Date 2000-11-07 Time 15:14 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS AND PANELS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. PER 110-9.
 THIS IS REQ`D ON PLANS PER 215-5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-19 Cont ID  
Sent By dpalmer Date 2000-10-19 Time 22:26 Rev Time 0.00
Received By dpalmer Date 2000-10-19 Time 22:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 06:45 Rev Time 0.25
Received By ndenmark Date 2000-10-21 Time 06:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-23 Cont ID  
Sent By lmartine Date 2000-10-23 Time 13:13 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLAN APPROVED BY TIM L. ON 10/20/00,
 SEE BACK OF APPLICATION FOR SIGN OFF
 L.M.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-11-07 Cont ID  
Sent By rmcdouga Date 2000-11-07 Time 15:45 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR AWNING WINDOWS. ONES THAT
 WERE SUBMITTED HAD EXPIRED.
  
 2)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN FOR STORM PANELS PRIOR TO INSTALL-
 ATION.
  
 3)PROVIDE SOIL COMPACTION TEST AT 1ST
 INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-10-24 Cont ID  
Sent By rmcdouga Date 2000-10-24 Time 14:50 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM BEACH
 CO.,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITTED TO CITY OF WPB BUILDING DEPT.
 BEFORE PERMIT TO CONSTRUCT WILL BE
 ISSUED.
  
 2)PROVIDE SOIL TEST PER 1804.2.7 CITY
 AMENDMENTS TO 97 SBC
  
 3)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR FIXED
 GLASS,ARCHED FIXED GLASS AND AWNING
 WINDOWS.
  
 4)PROVIDE PRODUCT APPROVALS FOR ROOF
 COVERING MATERIALS.
  
 5)PROVIDE ENERGY CODE CALCULATIONS
 INCLUDING MANUAL "J" CALCS. PER 1997 FL
 ENERGY EFFICIENCY CODE.
  
 6)PROVIDE 2 COMPLETED CITY OF WPB DESIGN
 COMPLIANCE FORMS.
  
 7)PROVIDE PRODUCT APPROVALS FOR STORM
 PANELS,INSTALLATION SCHEDULE AND KEY
 PLAN FOR ALL GLAZING IN NEW WINDOWS AND
 DOORS THAT DO NOT HAVE IMPACT GLASS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-27 Cont ID  
Sent By gjoyce Date 2000-09-27 Time 18:28 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***