Plan Review Details - Permit 00091180
Plan Review Stops For Permit 00091180
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-11-15 Cont ID  
Sent By dpalmer Date 2000-11-15 Time 09:32 Rev Time 0.00
Received By dpalmer Date 2000-11-15 Time 09:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-11-13 Cont ID  
Sent By dpalmer Date 2000-11-13 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2000-11-13 Time 10:07 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE RISER, FEEDERS ARE
 SHOWN AT 400 MCM 320A . NOT RATED FOR
 400A SERVICE.
  
 2)NOTE: RISER AND PANEL SCHEDULE DO NOT
 CORRELATE. ONE SHOWS MCB AND THE OTHER
 MLO. PLEASE CLARIFY.
  
 3)NOTE:PLEASE CLARIFY THE 220V OUTLET
 IN GARAGE. PLEASE SHOW ON PANEL SCHEDULE
  
 4)NOTE: PLEASE SHOWON PANEL THE REQ`D
 BATH(S) CIRCUIT(S) PER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-11 Cont ID  
Sent By dpalmer Date 2000-10-11 Time 19:39 Rev Time 0.00
Received By dpalmer Date 2000-10-11 Time 19:39 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE ELECTRICAL RISER
 DIAGRAM,,, ONLY 1-SET OF 3/0 CONDUCTORS
 SHOWN. PLEASE SEE AMPACITIES OF 310-15
 AND 310-16 75 DEGREE COLUMN. TOTAL LOAD
 SHOWN AT 311AMPS?? PLEASE ADJUST
 CONDUCTORS.
  
 2)NOTE: ALSO, PLEASE SEE THE FOLLOWING
 ARTS:373-7/373-8/380-3 FOR EQUIPMENT ETC
 BEING USED AS RACEWAYS TO OTHER DISC`S
 PANELS ETC. IF THE MAIN DISC IS BEING
 USED AS RACEWAY? THEN IT MUST MEET ALL
 CODES REFERENCED IN NEC. ALSO PLEASE
 PLACE NOTE ON PLAN FOR THOSE REQ`MENTS
 TO BE MET.IF NOT SHOW SECOND CONDUIT
 FROM METERCAN TO 2ND MAIN DISC.
  
 3)NOTE: PLEASE NOTE MISSING OUTLET PER
 210-52 AND PLEASE SHOW PANEL "C" ON
 ELECTRICAL PLANS PER 215-5. NOTE 110-26
 FOR CLEARENCES ABOUT POOL EQUIPMENT.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-07 Cont ID  
Sent By jleech Date 2000-10-07 Time 14:03 Rev Time 0.50
Received By jleech Date 2000-10-07 Time 14:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-27 Cont ID  
Sent By tlarge Date 2000-10-27 Time 09:58 Rev Time 0.30
Received By tlarge Date 2000-10-27 Time 09:58 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-11-02 Cont ID  
Sent By fknapp Date 2000-11-02 Time 15:25 Rev Time 4.00
Received By fknapp Date 2000-11-02 Time 09:33 Sent To  
Notes
2001-01-08 00:00:00 
  
 ************BUILDING PROVISO************
  
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR ALL EXTERIOR SWING ENTRY DOORS.
  
 2)PROVIDE RAISE SEAL AND ORIGINAL DATE
 AND SIGNATURE OF ARCHITECT AND ENGINEER
 ON NORANDEX PRODUCT APPROVAL FORM FOR
 WINDOWS, MULLIONS, AND SLIDING GLASS
 DOORS WITH JOB SITE LOCATION.
  
 3)PROVIDE BUTT GLASS ENGINEERING.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.
  
 4)PROVIDE STORM PANEL INFORMATION UNDER
 SEPARATE PERMIT.
  
 5)PROVIDE NOC BEFORE A PERMIT CAN BE
 ISSUED.
  
 6)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-27 Cont ID  
Sent By gjoyce Date 2000-09-27 Time 17:45 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***