Plan Review Details - Permit 00091125
Plan Review Stops For Permit 00091125
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-12-11 Cont ID  
Sent By dpalmer Date 2001-12-11 Time 20:34 Rev Time 0.00
Received By dpalmer Date 2001-12-11 Time 20:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 20:44 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 20:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-05 Cont ID  
Sent By dpalmer Date 2000-10-05 Time 07:42 Rev Time 0.00
Received By dpalmer Date 2000-10-05 Time 07:42 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW CLARIFICATION OF NEW
 PANEL BEING INSTALLED. YOU SHOW MLO AND
 60A ? IS THIS GOING TO HAVE A 60 AMP
 BRKER FOR THE MAIN? IF NOT THEN A MAIN
 IS REQ`D AT DETACHED STRUCTURE.
  
 2)NOTE: PLEASE SHOW GROUNDING ATTACHMENT
 AT THE DETACHED STRUCTURE. BLDG/SLAB
 STEEL AND COLD WATER BOND. PER 250-50
  
 3)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN
 AS EXISTING FOR 200AMP SERVICE??? #1 IS
 NOT LARGE ENOUGH FOR 200A SERVICE.
 PLEASE SUBMIT CLARIFICATION. IF #1 THEN
 MAIN SERVICE CONDUCTORS WILL BE REQ`D TO
 BE BROUGHT UP TO CODE.
  
 4)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ASLL SLEEPING ROOMS.THIS INCLUDE
 -S CABANA, AS IT HAS A CLOSET AND BATH
 FOR SLEEPING ROOM CONVERSION.
 ALL MUST BE WIRED INLINE.
  
 5)NOTE; PLEASE PROVIDE PANEL SCHEDULES
 FOR EXISTING AND NEW PANEL. PLEASE LIST
 THE REQ`D BATH(S) CIRCUIT(S) PER 210-52D
 AND 210-11-C-3. MUST BE #12 AWG AND 20A.
  
 6)NOTE: PLEASE NOET MISSING OUTLET FOR
 NEW SECOUND FLOOR BATH REQ`D BY 210-52D
  
 7)(NOTE: PLEASE NOTE MISSING EGRESS
 LIGHT REQ`D FOR CABANA PER 210-70.
  
 8)NOTE: PLEASE NOTE ELECTRICAL PANEL
 SHOWN IN CABANA CLOSET. THIS IS NOT
 PERMITTED IN CLOSET SPACE PER 110-26F
 AND 384-7 FOR ELECTRICAL EQUIPMENT BEING
 INSTALLED AROUND IGNITABLE MATERIALS.
  
 9)NOTE: PLEASE CLARIFY 240/1%%C SHOWN ON
 BOTTOM OF LOAD CALCULATIONS. (TYPE-O)???
  
 10)NOTE: SPACE HEATER SHOWN ON LOAD
 CALCULATIONS FOR CABANA? NOT SHOWN ON
 ELECTRICAL FLOOR PLAN???? PLEASE CALRIFY
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THEREARE ANY QUESITONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-10-07 Cont ID  
Sent By jleech Date 2000-10-07 Time 07:03 Rev Time 0.25
Received By jleech Date 2000-10-07 Time 07:02 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN
 A/C CONTRACTOR MUST SUBMIT PLANS WITH
 APPLICATION.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-12-17 Cont ID  
Sent By kstevens Date 2001-12-17 Time 13:01 Rev Time 1.00
Received By kstevens Date 2001-12-17 Time 13:01 Sent To  
Notes
2001-12-17 00:00:00NO GAS WATER HEATER AT THIS HOUSE

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-12-15 Cont ID  
Sent By pschmitz Date 2001-12-15 Time 16:53 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-15 00:00:00PLUMBING PLAN REVIEW,DENIED
 SEE ATTACHED GAS PERMIT REQUIRMENTS,
 ADDRESS EA CIRCLED COMMENT,1,2,3,4,5,6,
 7,8,9,SEPERATEGAS PERMITREQUIRED.
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-20 Cont ID  
Sent By dpalmer Date 2001-12-11 Time 20:34 Rev Time 0.25
Received By jleech Date 2001-01-20 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-10 Cont ID  
Sent By tlarge Date 2000-10-10 Time 17:17 Rev Time 0.50
Received By tlarge Date 2000-10-10 Time 17:10 Sent To  
Notes
2001-01-08 00:00:001)FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 2)FIXTURE BRANCHES NOT PERMITTED ON WET
 VENT PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.(RISER FOR 2ND.FLR.BATH TO
 CONNECT TO HORIZONTAL DRAIN DOWN-
 STREAM OF EXISTING WATER CLOSET.)
  
 3)A MAX.OF 2 WATER CLOSETS ARE PERMITTED
 ON A 3" BUILDING DRAIN.SPC TABLE 714.1,
 FOOTNOTE #3
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-01-25 Cont ID  
Sent By jgomez Date 2001-01-25 Time 15:56 Rev Time 3.00
Received By jgomez Date 2001-01-25 Time 15:56 Sent To  
Notes
2001-01-25 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE ENERGY CALCULATIONS.
 2-PROVIDE PRODUCT APPROVAL FOR:
 -METAL ROOF (MISSING PAGE 3 OF 5 AND
 DRAWINGS ARE NOT LEGIBLE).
 -WINDOW MULLIONS.
 -CURRENT PRODUCT APPROVAL FOR DOUBLE
 HUNG WINDOWS. ALONG WITH DRAWINGS.
 3-UNVENTED ATTIC AS ALTERNATE MATERIALS
 AND METHODS, SECTION 103.7 OF CITY
 AMENDMENTS TO SBC 1997.
 -PROVIDE COMPLETE SET OF DETAILS AND
 SPECIFICATIONS SHOWING SYSTEM/ASSEMBLY
 OF UNVENTED ATTIC. SIGNED,SEALED AND
 DATED.
 4-MECHANICAL, ELECTRICAL, PLUMBING AND
 ROOFING CONTRACTORS TO PULL OUT THEIR
 OWN PERMITS.
  
  
  
  
  
  
 NOTES:
 -PROVIDE ALL INFORMATION REQUESTED ON
 THIS PROVISO PRIOR TO CONSTRUCTION OR
 INSTALLATION IN ORDER TO AVOID DELAYS
 OR CONFLICTS.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-10-20 Cont ID  
Sent By jgomez Date 2000-10-20 Time 14:26 Rev Time 2.50
Received By jgomez Date 2000-10-20 Time 14:26 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS. SECTION 2405.2 SBC 1997.
 3-PROVIDE ATTIC ACCESS AT SECOND FLOOR
 ROOF. SECTION 2309.6 SBC 1997.
 4-PROVIDE CURRENT SURVEY WITH NEW BLDG
 LAYOUT. SIGNED AND SEALED.
 5-PROVIDE PRODUCT APPROVAL FOR:
 -FLAT ROOF SYSTEM.
 -METAL ROOF (MISSING SHEET 3 OF 5 AND
 APPROVED DRAWINGS AREN'T LEGIBLE).
 -DOUBLE FRENCH DOORS.
 -OUTSWING & INSWING SINGLE FRENCH DOORS
 -WINDOW MULLIONS.
 -DOUBLE HUNG WINDOWS (PRODUCT APPROVAL
 EXPIRED AND NEED COPIES OF APP'D DWGS)
 -PROVIDE EXTRA COPY OF CASEMENT WINDOWS
 6-EGRESS WINDOWS AT SECOND FLOOR BEDRMS
 DON'T COMPLY WITH SECTION 1005.4.4 OF
 SBC 1997.
 7-SPECIFY ATTIC VENTILATION AS PER SEC.
 2309.7 SBC 1997.
 8-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AS PER CITY SAMPLE ATTACHED AND A KEY
 PLAN.
 -CIRCLE/HIGHLIGHT SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED ACCORDING TO THE MEAN ROOF
 HEIGHT, DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE AND CONNECTION TYPE.
 9-PROVIDE FRAMING DETAILS AT NEW DOORS
 AND WINDOWS AND SPECIFY HOW OPENINGS
 ARE REINFORCED TO RECEIVE THE STORM
 PANELS.
 10-SEE PLANS FOR ADDITIONAL COMMENTS,
 INCLUDING THOSE BY THE OTHER TRADES.
  
  
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER THE
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ (BUILDING PLAN REVIEWER) AT
 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-27 Cont ID  
Sent By gjoyce Date 2000-09-27 Time 16:57 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***