Plan Review Details - Permit 00091113
Plan Review Stops For Permit 00091113
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-12-21 Cont ID  
Sent By mcarsill Date 2000-12-21 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2000-12-21 Time 10:37 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE MORE DETAILS ON
 CERAMIC DUCT WRAP THAT IS IDENTIFIED
 ON THE PLANS. IF DRYWALL IS USED THEN
 IT MUST BE 5/8 TYPE X FIRE RATED
 DRYWALL.
 2) SEPARATE PLANS AND PERMIT REQUIRED
 FOR FIRE SUPPRESSION SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-09-29 Cont ID  
Sent By mcarsill Date 2000-09-29 Time 11:09 Rev Time 0.00
Received By mcarsill Date 2000-09-29 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-12-18 Cont ID  
Sent By ndenmark Date 2000-12-18 Time 11:48 Rev Time 0.50
Received By ndenmark Date 2000-12-18 Time 11:48 Sent To  
Notes
2001-01-08 00:00:00DENIED
 1. PROVIDE PRODUCT APPROVAL INFORMATION
 ON PYROSCAT INSULATION. INCLUDE INSTALL-
 ATION DETAILS.
 2. ENTIRE DUCT LENGTH TO BE PROTECTED
 PER 1997 SMC 505.9.1 "ALL VERTICAL AND
 HORIZONTAL DUCTS LOCATED WITHINN A BUILD
 ING OF TWO STORIES OR MORE SHALL BE
 ENCLOSED IN A CONTINUOUS ENCLOSURE
 \\EXTENDING FROM THE CEILING ABOVE THE
 HOOD TO OR THROUGH THE ROOF." PROVIDE
 DETAILS ON METHOD OF COMPLIANCE TO BE
 USED.
 PROVIDE INFORMATION ON HOW RESIDUE TRAP
 WILL EXTEND THROUGH ABOVE ENCLOSURE AND
 HOW MAINTAINANCE WILL OCCUR TO PREVENT
 BUILDUP AT THIS LOCATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-27 Cont ID  
Sent By ndenmark Date 2000-09-27 Time 13:13 Rev Time 0.25
Received By ndenmark Date 2000-09-27 Time 13:13 Sent To  
Notes
2001-01-08 00:00:00HANGING DETAIL ON APPROVED PLAN 00061244