Plan Review Details - Permit 00091111
Plan Review Stops For Permit 00091111
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-04-10 Cont ID  
Sent By bstaples Date 2001-04-10 Time 09:45 Rev Time 1.00
Received By bstaples Date 2001-04-10 Time 09:44 Sent To  
Notes
2001-04-10 00:00:00REVISIOR ISSUED WRS 4/10/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-11-22 Cont ID  
Sent By drunnels Date 2000-11-22 Time 15:50 Rev Time 1.00
Received By drunnels Date 2000-11-22 Time 15:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-24 Cont ID  
Sent By drunnels Date 2000-10-24 Time 15:02 Rev Time 2.00
Received By drunnels Date 2000-10-24 Time 12:49 Sent To  
Notes
2001-01-08 00:00:001. DEAD END CORRIDORS OVER 20 FEET IN
 LENGTH ARE NOT ALLOWED/SECTION 1005.2
 1997 EDITION SBC
 2. TENNANT SPACES ARE REQUIRED TO HAVE 2
 MEANS OF EGRESS/ SECTION 1004.1.2 1997
 EDITION SBC
 3. ALL COMBUSTIBLES IN CONCEALED SPACES
 SHALL COMPLY WITH SECTION 707
 1997 EDITION SBC

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-09-17 Cont ID  
Sent By dpalmer Date 2001-09-17 Time 22:24 Rev Time 0.00
Received By dpalmer Date 2001-09-17 Time 22:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-13 Cont ID  
Sent By dpalmer Date 2001-03-13 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2001-03-13 Time 12:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-24 Cont ID  
Sent By dpalmer Date 2000-10-24 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2000-10-24 Time 12:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-09-27 Cont ID  
Sent By mcarsill Date 2001-09-27 Time 15:11 Rev Time 0.00
Received By mcarsill Date 2001-09-27 Time 15:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-04-06 Cont ID  
Sent By mcarsill Date 2001-04-06 Time 14:30 Rev Time 0.00
Received By mcarsill Date 2001-04-06 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-11-03 Cont ID  
Sent By mcarsill Date 2000-11-03 Time 11:15 Rev Time 0.00
Received By mcarsill Date 2000-11-03 Time 11:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-10-24 Cont ID  
Sent By mcarsill Date 2000-10-24 Time 13:08 Rev Time 0.00
Received By mcarsill Date 2000-10-24 Time 13:08 Sent To  
Notes
2001-01-08 00:00:001) PROVIDE A SECOND MEANS OF EGRESS FROM
 TENANT SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-10-06 Cont ID  
Sent By mcarsill Date 2000-10-06 Time 09:32 Rev Time 0.00
Received By mcarsill Date 2000-10-06 Time 09:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-26 Cont ID  
Sent By pkrauss Date 2001-03-26 Time 12:26 Rev Time 0.30
Received By pkrauss Date 2001-03-26 Time 12:10 Sent To  
Notes
2001-03-26 00:00:00REVISION -
  
 CHANGED CONFERENCE RM., CORRIDOR AND
 RECEPTION AREA TO HARD CEILINGS.NOTE
 15 ON DRAWING AC-1 INDICATES ACCESS
 PANELS TO BE INSTALLED WHERE NEEDED.
 CHANGED DROPS IN THESE AREAS TO LINEAR
 DIFFUSERS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 08:00 Rev Time 0.25
Received By ndenmark Date 2000-10-21 Time 08:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-26 Cont ID  
Sent By tlarge Date 2000-09-26 Time 11:53 Rev Time 1.25
Received By tlarge Date 2000-09-26 Time 10:46 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO**************
 SINK IN COFFEE ROOM #102 SHALL COMPLY
 W/FACBC SEC.4.24.1-4.24.7.
  
 CALL 561659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.