Plan Review Details - Permit 00091048
Plan Review Stops For Permit 00091048
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-10-17 Cont ID  
Sent By hpiskura Date 2000-10-17 Time 10:00 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-11-14 Cont ID  
Sent By dpalmer Date 2000-11-14 Time 22:15 Rev Time 0.00
Received By dpalmer Date 2000-11-14 Time 22:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-11 Cont ID  
Sent By dpalmer Date 2000-10-11 Time 20:22 Rev Time 0.00
Received By dpalmer Date 2000-10-11 Time 20:22 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION ON
 GENERATOR.MORETHAN SIX THROWS ON THE
 MDP? PLEASE SHOW MORE DETAIL ON FEEDERS
 GOING TO EACH BLDG. PER LOCAL AMENDMENTS
 NO MORE THAN 8` OF UNPROTECTED CONDUCTOR
 -S PERMITTED INSIDE BLDG.?? NEED TO
 SHOW.
 PLEASE SEE REQ`MENTS FOR LABELING OF
 ALL BLDG. DISCONNECTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS/INSIGHT
 ON THIS INSTALLATION PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-11-14 Cont ID  
Sent By mcarsill Date 2000-11-14 Time 13:09 Rev Time 0.00
Received By mcarsill Date 2000-11-14 Time 13:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-16 Cont ID  
Sent By mcarsill Date 2000-10-13 Time 16:41 Rev Time 0.00
Received By mcarsill Date 2000-10-13 Time 16:41 Sent To  
Notes
2001-01-08 00:00:001) ENTIRE GENERATOR ROOM IS TO BE
 CONSTRUCTED WITH AT LEAST A TWO HOUR
 FIRE RATING. OPENINGS IN WALLS TO BE
 AT LEAST 1 1/2 FIRE RATED. PLEASE
 PROVIDE TESTED TWO HOUR RATED ASSEMBLY
 2) A RAISED SILL OF AT LEAST 4" HIGH
 SHALL BE PROVIDED AT DOOR OPENINGS.
 3) ALL FLOORS AND WALLS SHALL BE
 LIQUIDTIGHT.
 4) IF THE EXISTING MAINTENANCE BUILDING
 IS FIRE SPRINKLER PROTECTED, FIRE
 SPRINKLER COVERAGE IS TO BE EXTENDED
 INTO THE GENERATOR ROOM.
 5) PROVIDE MORE DETAILS ON EMERGENCY
 GENERATOR.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-20 Cont ID  
Sent By jleech Date 2000-11-20 Time 07:41 Rev Time 0.50
Received By jleech Date 2000-11-20 Time 07:41 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 ROOF DRAINS SHALL DISCHARGE TO AN
 APPROVED LOCATION AND SHALL NOT
 CREATE A NUISANCE.
 SUBMIT RISER DIAGRAM BEFORE PLUMBING
 INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-30 Cont ID  
Sent By tlarge Date 2000-09-30 Time 05:36 Rev Time 0.50
Received By tlarge Date 2000-09-30 Time 05:15 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 ROOF DRAINS SHALL DISCHARGE TO AN
 APPROVED LOCATION AND NOT CREATE A
 NUISANCE.SUBMIT RISER DIAGRAM PRIOR TO
 INSPECTION.SPC 301.11.1,COUNTYWIDE AMEND
 MENTS TO SPC 104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-27 Cont ID  
Sent By gjoyce Date 2000-09-27 Time 11:43 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***