Plan Review Details - Permit 00091034
Plan Review Stops For Permit 00091034
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-10-16 Cont ID  
Sent By hpiskura Date 2000-10-16 Time 13:26 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-30 Cont ID  
Sent By dpalmer Date 2000-10-30 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2000-10-30 Time 12:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-11 Cont ID  
Sent By dpalmer Date 2000-10-11 Time 22:06 Rev Time 0.00
Received By dpalmer Date 2000-10-11 Time 22:06 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: COMPLETED LOAD CALCULATIONS
 NEED TO BE SUBMITTED. PLEASE SHOW CLACS.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%
 (LIGHTING ETC).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-10-25 Cont ID  
Sent By rturnque Date 2000-10-25 Time 14:12 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-29 Cont ID  
Sent By mcarsill Date 2000-09-29 Time 08:40 Rev Time 0.00
Received By mcarsill Date 2000-09-29 Time 08:40 Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISHES IN EXITS TO BE
 CLASS A OR B. INTERIOR FINISHES IN
 OFFICE AREAS TO BE CLASS A, B OR C.
 2) DEMOLITION PLAN SHOWS EXISTING
 BATTERY PACK EMERGENCY LIGHT FIXTURES.
 CLEARLY INDICATE ON PLANS WHERE THE
 EMERGENCY LIGHT FIXTURES ARE LOCATED
 SINCE THE BATTERY PACK LIGHTS ARE NOT
 SHOWN ON PAGE E-2.
 3) ADDITIONAL EXIT SIGNS MAY BE NEEDED
 IF THE DIRECTIONAL SIGN CANNOT BE
 SEEN FROM THE HALLWAY NEAR THE ENDS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-06 Cont ID  
Sent By ndenmark Date 2000-10-06 Time 13:55 Rev Time 0.25
Received By ndenmark Date 2000-10-06 Time 13:55 Sent To  
Notes
***NONE***