| Plan Review Stops For Permit 00090978 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-06 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2001-12-06 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2001-12-06 |
Time |
17:52 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-30 |
Time |
15:29 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-30 00:00:00 | BUILDING PLAN REVIEW | | | PROVISO: 1)- PAY COUNTY IMPACT FEES | | | 2)- OWNER / CONTRACTOR TO SIGN | | | ENEREGY CALS | | | 3)- PROVIDE RECORDED NOTICE OF | | | COMMENCEMENT | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659- 8096 EX 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-31 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-31 |
Time |
07:43 |
Rev Time |
2.50 |
| Received By |
drunnels |
Date |
2000-10-31 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. ENERGY EFFICIENCY SHEETS MUST BE SIGN | | | -ED BY THE OWNER/AGENT | | | 2. SUBMIT PRODUCT APPROVALS FOR WINDIWS, | | | DOORS AND ROOF COVERINGS | | | 3. SUBMIT DETAILS SHOWING CASHIER | | | COUNTER COMPLIES WITH SECTION 7.2 OF THE | | | FLORIDA ACCESSIBILITY CODE FOR BUILDING | | | CONSTRUCTION |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-11-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-20 |
Time |
19:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-20 |
Time |
19:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-29 |
Time |
22:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-29 |
Time |
22:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-16 |
Time |
19:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-16 |
Time |
19:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE 210-63 FOR REQ`MENT | | | OF GFI ON ROOF. | | | | | | 2)NOTE: PLEASE SEE 210-62 FOR SHOW | | | WINDOW RECEPTS. 220-12A | | | | | | | | | 3)NOTE: PLEASE SEE 220-12B FOR TRACK | | | LIGHTING LOAD CALCULATIONS. PLEASE SHOW | | | | | | 4)NOTE: PLEASE SEE 250-50. WHERE AVAIL- | | | -ABLE BLDG. STEEL ALSO FOR GROUNDING | | | ELECTRODE CONDUCTOR. NEW CONTRUCTION. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-03-13 |
Time |
15:14 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-03-13 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2001-03-13 00:00:00 | PASSED: | | | RESPONSES TO PREVIOUS REVIEW COMMENTS | | | DATED 10-27-00 SATISFACTORY, CHANGES ARE | | | IMPLEMENTED. | | | ANY QUESTION PLEASE CONTACT 561-659-8096 | | | EXT. 8492 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2000-10-27 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-10-27 |
Time |
11:35 |
Rev Time |
3.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | COMMENTS | | | SHEET 5 | | | PARKING SPACES REQUIRE CAR TOPS OR | | | SIDEWALK. CLARIFY IF WICH OPTION AND | | | ALSO SHOW HD RAMP IF APPLICABLE. | | | SHEET 5 | | | DRIVEWAY ENTRANCES MUST BE PER CITY OF | | | WEST PALM BEACH SPECIFICATIONS. SEE | | | DWG ATTACHED. | | | ALL SHEETS | | | THE SCALE BAR SHOWS 10' WHEN IT IS REALL | | | Y 20'(1"=20')PLEASE CHANGE IN ALL | | | APPLICABLE DRAWINGS. | | | SHEET 5 | | | PLEASE UPDATEPUBLIC UTILITIES CONTACT | | | INFORMATION | | | SHEET 6 | | | PLEASE PROVIDE 2 SETS OF THIS SHEET TO | | | OUR STORM WATER ENGINEER FOR APPROVAL. | | | JOSE DEL RIOS | | | PUBLIC UTILITIES ENGINEERING | | | 1000 45TH ST SUITE 15 | | | WEST PALM BEACH, FL 33407 | | | (561) 659 8040 | | | ALSO PROVIDE ALL STORM CALCULATIONS | | | SEE REQUIREMENTS ATTACHED. | | | SHEET 7 | | | PLEASE MAKE CORRECTIONS AND SUBMIT TWO | | | SETS FOR REVIEW TO | | | MANNY GONZALEZ | | | AT THE SAME ADDRESS AS ABOVE. FOR PUBLIC | | | UTILITIES APPROVAL. | | | SHEET 7 | | | PROVIDE NOTE STATING 18" MIN CLEARANCE | | | BETWEEN WATER AND SEWER CROSSINGS. | | | SHEET 7 | | | FOR THE DIRECT TAP PLEASE USE EITHER A | | | 1" OR 2" COPPER SERVICE LINE. REQUIRED | | | BY CITY OF WEST PALM BEACH PUBLIC UTIL. | | | SHEET 7 | | | METERS MUSDT BE LOCATED ON THE SIDEWALK | | | THEY MUST HAVE LOCKING LIDS AND TOUCH | | | READ MOUNTING OPTION. | | | SHEET 7 | | | PLEASE PROVIDE SUNSHINE LOCATING SERVICE | | | NOTE AND THEIR 1-800 NUMBER. | | | SHEET 7 | | | A CLEAN OUT IS REQUIRED JUST INSIDE OF | | | PROPERTY LINE AS SHOWN ON THE PLAN. | | | SHEET 7 | | | ANY OLD METER BOXES IN THE VICINITY OF | | | SITE NOT IN USE MUST BE FILLED WITH | | | CONCRETE OR LOCKED WITH A LOCKING LID. | | | SHEET 12 | | | PLEASE PROVIDE CITY STANDARD DETAILS | | | PLEASE EMAIL [email protected] | | | .FL.US TO REQUEST IN ELECTRONIC FORMAT. | | | SHEET 14 | | | FYI THE DUMPSTER MUST PROVIDE A 12'-6" | | | MINIMUM OPENING. SEE MINIMUM REQUIREMENT | | | S ATTACHED. | | | HAVE A GREAT DAY ! |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-11 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-11 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-03-15 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2001-12-06 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-15 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2001-03-15 00:00:00 | 1) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATION OF THE UNDERGROUND | | | FUEL TANKS AND ABOVE GROUND DISPENSING | | | PUMPS. UNDERGROUND FUEL TANKS ARE TO BE | | | A MINIMUM OF THREE FEET FROM PROPERTY | | | LINES. | | | 2) PROVIDE FLAME SPREAD INFORMATION ON | | | CANOPY. | | | 3) PROVIDE INFORMATION FOR PROPANE | | | STORAGE AREA. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-09-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-20 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-20 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED ON | | | PLANS. SHOULD READ NFPA 101-LIFE SAFETY | | | CODE, 1985 INSTEAD OF 1994. | | | 2) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. | | | 3) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 4) SERVICE STATION TO COMPLY WITH THE | | | REQUIREMENTS OF NFPA 30A, THE STANDARD | | | FOR AUTOMOTIVE AND MARINE SERVICE | | | STATION CODE, AND UNIFORM FIRE SAFETY | | | RULES AND STANDARDS, CHAPTER 4A-49. | | | 5)THE UNDERGROUND FUEL TANKS ARE TO | | | COMPLY WITH NFPA 30, THE STANDARD FOR | | | THE STORAGE AND HANDLING OF COMBUSTIBLE | | | LIQUIDS. | | | 6) PLEASE INDICATE ON THE PLANS, THE | | | LENGTHS OF FUEL HOSES PLANNED FOR USE. | | | 7) PLEASE IDENTIFY TYPE SIGNAGE FOR | | | EMERGENCY SHUT OFFS FOR FUEL DISPENSING | | | EQUIPMENT. | | | 8) PLEASE IDENTIFY THE LOCATIONS FOR | | | WARNING SIGNS AT THE FUEL DISPENSING | | | AREA. WHAT WORDING IS PLANNED FOR THESE | | | SIGNS. | | | 9) PLEASE INDICATE BREAKAWAY DEVICE | | | LOCATIONS. | | | 10) PLEASE INDICATE TYPES AND LOCATIONS | | | OF FIRE EXTINGUISHERS. | | | 11) PLEASE PROVIDE LISTING INFORMATION | | | ON DEVICES PLANNED FOR USE AT FUEL | | | DISPENSING AREA. | | | 12) PLEASE PROVIDE INFORMATION ON | | | PROPANE STORAGE AREA. | | | 13) PLEASE PROVIDE FLAME SPREAD | | | CHARACTERISTICS ON CANOPY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-27 |
Time |
16:22 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-03-27 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2001-03-27 00:00:00 | ADDITIONAL PERMIT REQUIRED FOR WALK-IN | | | COOLER/FREEZER, SUBMIT PLANS WITH | | | PERMIT APPLICATION. | | | | | | ADDITIONAL PERMIT REQUIRED FOR FUEL, | | | SUBMIT PLANS WITH PERMIT APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-28 |
Time |
13:37 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-10-28 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTE: | | | ADDITIONAL MECHANICAL PERMITS REQUIRED | | | FOR FUEL SYSTEM AND WALK IN COOLER AND | | | FREEZER BOXES. | | | FUEL PLANS ARE TO BE STAMPED WITH PALM | | | BEACH COUNTY DEPT. OF ENVIRONMENTAL | | | REGULATORY MANAGEMENT APPROVAL PRIOR TO | | | SUBMITTAL TO THIS DEPT. FOR APPROVAL | | | PROVIDE DETAIL PLANS AND CUT SHEETS AT | | | TIME OF PERMIT APPLICATION FOR THESE | | | ADDITIONAL MECHANICAL PERMITS. PERMITS | | | REQUIRED TO ISSUED AND POSTED ON JOBSITE | | | PRIOR TO COMMENCEMENT OF RELATED WORK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-25 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-03-25 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2002-03-25 00:00:00 | REVISION OK - VENT OUTSIDE BLDG - NEW | | | SEWER LINE - STRUCTION AT PROPERTY LINE | | | GREASE TRAP LOCATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-03-31 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-03-31 |
Time |
15:37 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-09-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-23 |
Time |
10:34 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
2000-09-23 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SHT.12-REVISE REFERENCE TO "A"COPPER. | | | THERE IS NO SUCH CLASSIFICATION. | | | | | | 2)CONTACT ROD COMPO AT 561-835-7423 FOR | | | REQS.FOR THE GREASY WASTE SYSTEM.SUBMIT | | | A COPY OF APPROVAL FORM FROM WPB | | | UTILITIES.MIN.SIZE GREASE TRAP TO BE 750 | | | GALS.COUNTYWIDE AMEND.101.4.7. | | | | | | 3)SUBMIT PIPING DIAGRAMS FOR AIR AND | | | WATER LINES.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | 4) MIN.SIZE OF BUILDING SEWER SHALL BE | | | 4"PER SPC SEC.714.1 FOOTNOTE #2.(SHT.P-1 | | | | | | 5)ALL PLUMBING WORK NOT INSTALLED BY THE | | | BUILING SUPPLIER SHALL BE DONE BY THE | | | LICENSED PLUMBING CONTRACTOR.F.S.CHAPT. | | | 468.SEE SHTS.SC-1,P-1,P-3,AND NOTES. | | | PLANS NOTE WORK TO BE DONE BY GC | | | | | | 6)DRAINS FOR INDIRECT WASTES INSTALLED | | | IN FIELD SHALL BE FLOOR SINKS NOT FLOOR | | | DRAINS OR FUNNEL DRAINS.SPC SEC.804.1. | | | | | | 7)SUBMIT ADDITIONAL INFORMATION ON LP | | | TANK STORAGE.SHOW TOTAL AGGREGATE | | | CAPACITY,LOCATION OF ANY SOURCES OF | | | IGNITION,LOCATION OF TANKS IN PROXIMITY | | | TO BUILDING OPENINGS,ETC.COMPLY W/NFPA | | | 58 SEC.3-2.2.2.AND TABLE 3-2.2.2. | | | | | | 8)COMPLY W/ATTACHED LIST OF REQS.FOR GAS | | | DRAWINGS. | | | | | | 9)HEAT TRAPS ARE REQD.ON THE WATER | | | HEATERS PER F.E.C.SEC.412.1.ABCD.2.1.3. | | | | | | 10)WATER HEATER SHALL BE READILY | | | ACCESSIBLE PER SPC SEC.501.7.SUPPLY | | | SHIP'S LADDER AND PLATFORM OR RELOCATE | | | TO FLOOR. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-11-19 |
Time |
07:50 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-04-05 |
Time |
11:11 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|