Plan Review Details - Permit 00090978
Plan Review Stops For Permit 00090978
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-12-06 Cont ID  
Sent By rbrown Date 2001-12-06 Time 17:53 Rev Time 0.00
Received By rbrown Date 2001-12-06 Time 17:52 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-03-30 Cont ID  
Sent By jwitmer Date 2001-03-30 Time 15:29 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-30 00:00:00BUILDING PLAN REVIEW
 PROVISO: 1)- PAY COUNTY IMPACT FEES
 2)- OWNER / CONTRACTOR TO SIGN
 ENEREGY CALS
 3)- PROVIDE RECORDED NOTICE OF
 COMMENCEMENT
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659- 8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-31 Cont ID  
Sent By drunnels Date 2000-10-31 Time 07:43 Rev Time 2.50
Received By drunnels Date 2000-10-31 Time 07:42 Sent To  
Notes
2001-01-08 00:00:001. ENERGY EFFICIENCY SHEETS MUST BE SIGN
 -ED BY THE OWNER/AGENT
 2. SUBMIT PRODUCT APPROVALS FOR WINDIWS,
 DOORS AND ROOF COVERINGS
 3. SUBMIT DETAILS SHOWING CASHIER
 COUNTER COMPLIES WITH SECTION 7.2 OF THE
 FLORIDA ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 19:36 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 19:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-29 Cont ID  
Sent By dpalmer Date 2001-03-29 Time 22:26 Rev Time 0.00
Received By dpalmer Date 2001-03-29 Time 22:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-16 Cont ID  
Sent By dpalmer Date 2000-10-16 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2000-10-16 Time 19:47 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SEE 210-63 FOR REQ`MENT
 OF GFI ON ROOF.
  
 2)NOTE: PLEASE SEE 210-62 FOR SHOW
 WINDOW RECEPTS. 220-12A
  
  
 3)NOTE: PLEASE SEE 220-12B FOR TRACK
 LIGHTING LOAD CALCULATIONS. PLEASE SHOW
  
 4)NOTE: PLEASE SEE 250-50. WHERE AVAIL-
 -ABLE BLDG. STEEL ALSO FOR GROUNDING
 ELECTRODE CONDUCTOR. NEW CONTRUCTION.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-03-13 Cont ID  
Sent By mamini Date 2001-03-13 Time 15:14 Rev Time 4.00
Received By mamini Date 2001-03-13 Time 11:24 Sent To  
Notes
2001-03-13 00:00:00PASSED:
 RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 10-27-00 SATISFACTORY, CHANGES ARE
 IMPLEMENTED.
 ANY QUESTION PLEASE CONTACT 561-659-8096
 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-10-27 Cont ID  
Sent By mgonzale Date 2000-10-27 Time 11:35 Rev Time 3.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00COMMENTS
 SHEET 5
 PARKING SPACES REQUIRE CAR TOPS OR
 SIDEWALK. CLARIFY IF WICH OPTION AND
 ALSO SHOW HD RAMP IF APPLICABLE.
 SHEET 5
 DRIVEWAY ENTRANCES MUST BE PER CITY OF
 WEST PALM BEACH SPECIFICATIONS. SEE
 DWG ATTACHED.
 ALL SHEETS
 THE SCALE BAR SHOWS 10' WHEN IT IS REALL
 Y 20'(1"=20')PLEASE CHANGE IN ALL
 APPLICABLE DRAWINGS.
 SHEET 5
 PLEASE UPDATEPUBLIC UTILITIES CONTACT
 INFORMATION
 SHEET 6
 PLEASE PROVIDE 2 SETS OF THIS SHEET TO
 OUR STORM WATER ENGINEER FOR APPROVAL.
 JOSE DEL RIOS
 PUBLIC UTILITIES ENGINEERING
 1000 45TH ST SUITE 15
 WEST PALM BEACH, FL 33407
 (561) 659 8040
 ALSO PROVIDE ALL STORM CALCULATIONS
 SEE REQUIREMENTS ATTACHED.
 SHEET 7
 PLEASE MAKE CORRECTIONS AND SUBMIT TWO
 SETS FOR REVIEW TO
 MANNY GONZALEZ
 AT THE SAME ADDRESS AS ABOVE. FOR PUBLIC
 UTILITIES APPROVAL.
 SHEET 7
 PROVIDE NOTE STATING 18" MIN CLEARANCE
 BETWEEN WATER AND SEWER CROSSINGS.
 SHEET 7
 FOR THE DIRECT TAP PLEASE USE EITHER A
 1" OR 2" COPPER SERVICE LINE. REQUIRED
 BY CITY OF WEST PALM BEACH PUBLIC UTIL.
 SHEET 7
 METERS MUSDT BE LOCATED ON THE SIDEWALK
 THEY MUST HAVE LOCKING LIDS AND TOUCH
 READ MOUNTING OPTION.
 SHEET 7
 PLEASE PROVIDE SUNSHINE LOCATING SERVICE
 NOTE AND THEIR 1-800 NUMBER.
 SHEET 7
 A CLEAN OUT IS REQUIRED JUST INSIDE OF
 PROPERTY LINE AS SHOWN ON THE PLAN.
 SHEET 7
 ANY OLD METER BOXES IN THE VICINITY OF
 SITE NOT IN USE MUST BE FILLED WITH
 CONCRETE OR LOCKED WITH A LOCKING LID.
 SHEET 12
 PLEASE PROVIDE CITY STANDARD DETAILS
 PLEASE EMAIL [email protected]
 .FL.US TO REQUEST IN ELECTRONIC FORMAT.
 SHEET 14
 FYI THE DUMPSTER MUST PROVIDE A 12'-6"
 MINIMUM OPENING. SEE MINIMUM REQUIREMENT
 S ATTACHED.
 HAVE A GREAT DAY !

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-12-11 Cont ID  
Sent By mcarsill Date 2001-12-11 Time 13:01 Rev Time 0.00
Received By mcarsill Date 2001-12-11 Time 13:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-15 Cont ID  
Sent By rbrown Date 2001-12-06 Time 17:53 Rev Time 0.00
Received By mcarsill Date 2001-03-15 Time 09:22 Sent To  
Notes
2001-03-15 00:00:001) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE UNDERGROUND
 FUEL TANKS AND ABOVE GROUND DISPENSING
 PUMPS. UNDERGROUND FUEL TANKS ARE TO BE
 A MINIMUM OF THREE FEET FROM PROPERTY
 LINES.
 2) PROVIDE FLAME SPREAD INFORMATION ON
 CANOPY.
 3) PROVIDE INFORMATION FOR PROPANE
 STORAGE AREA.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-20 Cont ID  
Sent By mcarsill Date 2000-09-20 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2000-09-20 Time 14:44 Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED ON
 PLANS. SHOULD READ NFPA 101-LIFE SAFETY
 CODE, 1985 INSTEAD OF 1994.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 3) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 4) SERVICE STATION TO COMPLY WITH THE
 REQUIREMENTS OF NFPA 30A, THE STANDARD
 FOR AUTOMOTIVE AND MARINE SERVICE
 STATION CODE, AND UNIFORM FIRE SAFETY
 RULES AND STANDARDS, CHAPTER 4A-49.
 5)THE UNDERGROUND FUEL TANKS ARE TO
 COMPLY WITH NFPA 30, THE STANDARD FOR
 THE STORAGE AND HANDLING OF COMBUSTIBLE
 LIQUIDS.
 6) PLEASE INDICATE ON THE PLANS, THE
 LENGTHS OF FUEL HOSES PLANNED FOR USE.
 7) PLEASE IDENTIFY TYPE SIGNAGE FOR
 EMERGENCY SHUT OFFS FOR FUEL DISPENSING
 EQUIPMENT.
 8) PLEASE IDENTIFY THE LOCATIONS FOR
 WARNING SIGNS AT THE FUEL DISPENSING
 AREA. WHAT WORDING IS PLANNED FOR THESE
 SIGNS.
 9) PLEASE INDICATE BREAKAWAY DEVICE
 LOCATIONS.
 10) PLEASE INDICATE TYPES AND LOCATIONS
 OF FIRE EXTINGUISHERS.
 11) PLEASE PROVIDE LISTING INFORMATION
 ON DEVICES PLANNED FOR USE AT FUEL
 DISPENSING AREA.
 12) PLEASE PROVIDE INFORMATION ON
 PROPANE STORAGE AREA.
 13) PLEASE PROVIDE FLAME SPREAD
 CHARACTERISTICS ON CANOPY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-27 Cont ID  
Sent By pkrauss Date 2001-03-27 Time 16:22 Rev Time 0.45
Received By pkrauss Date 2001-03-27 Time 15:38 Sent To  
Notes
2001-03-27 00:00:00ADDITIONAL PERMIT REQUIRED FOR WALK-IN
 COOLER/FREEZER, SUBMIT PLANS WITH
 PERMIT APPLICATION.
  
 ADDITIONAL PERMIT REQUIRED FOR FUEL,
 SUBMIT PLANS WITH PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-28 Cont ID  
Sent By ndenmark Date 2000-10-28 Time 13:37 Rev Time 0.50
Received By ndenmark Date 2000-10-28 Time 13:37 Sent To  
Notes
2001-01-08 00:00:00NOTE:
 ADDITIONAL MECHANICAL PERMITS REQUIRED
 FOR FUEL SYSTEM AND WALK IN COOLER AND
 FREEZER BOXES.
 FUEL PLANS ARE TO BE STAMPED WITH PALM
 BEACH COUNTY DEPT. OF ENVIRONMENTAL
 REGULATORY MANAGEMENT APPROVAL PRIOR TO
 SUBMITTAL TO THIS DEPT. FOR APPROVAL
 PROVIDE DETAIL PLANS AND CUT SHEETS AT
 TIME OF PERMIT APPLICATION FOR THESE
 ADDITIONAL MECHANICAL PERMITS. PERMITS
 REQUIRED TO ISSUED AND POSTED ON JOBSITE
 PRIOR TO COMMENCEMENT OF RELATED WORK.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-03-25 Cont ID  
Sent By kstevens Date 2002-03-25 Time 16:55 Rev Time 0.00
Received By kstevens Date 2002-03-25 Time 16:55 Sent To  
Notes
2002-03-25 00:00:00REVISION OK - VENT OUTSIDE BLDG - NEW
 SEWER LINE - STRUCTION AT PROPERTY LINE
 GREASE TRAP LOCATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-31 Cont ID  
Sent By pschmitz Date 2001-03-31 Time 15:37 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-09-23 Cont ID  
Sent By tlarge Date 2000-09-23 Time 10:34 Rev Time 2.00
Received By pschmitz Date 2000-09-23 Time 09:00 Sent To  
Notes
2001-01-08 00:00:001)SHT.12-REVISE REFERENCE TO "A"COPPER.
 THERE IS NO SUCH CLASSIFICATION.
  
 2)CONTACT ROD COMPO AT 561-835-7423 FOR
 REQS.FOR THE GREASY WASTE SYSTEM.SUBMIT
 A COPY OF APPROVAL FORM FROM WPB
 UTILITIES.MIN.SIZE GREASE TRAP TO BE 750
 GALS.COUNTYWIDE AMEND.101.4.7.
  
 3)SUBMIT PIPING DIAGRAMS FOR AIR AND
 WATER LINES.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 4) MIN.SIZE OF BUILDING SEWER SHALL BE
 4"PER SPC SEC.714.1 FOOTNOTE #2.(SHT.P-1
  
 5)ALL PLUMBING WORK NOT INSTALLED BY THE
 BUILING SUPPLIER SHALL BE DONE BY THE
 LICENSED PLUMBING CONTRACTOR.F.S.CHAPT.
 468.SEE SHTS.SC-1,P-1,P-3,AND NOTES.
 PLANS NOTE WORK TO BE DONE BY GC
  
 6)DRAINS FOR INDIRECT WASTES INSTALLED
 IN FIELD SHALL BE FLOOR SINKS NOT FLOOR
 DRAINS OR FUNNEL DRAINS.SPC SEC.804.1.
  
 7)SUBMIT ADDITIONAL INFORMATION ON LP
 TANK STORAGE.SHOW TOTAL AGGREGATE
 CAPACITY,LOCATION OF ANY SOURCES OF
 IGNITION,LOCATION OF TANKS IN PROXIMITY
 TO BUILDING OPENINGS,ETC.COMPLY W/NFPA
 58 SEC.3-2.2.2.AND TABLE 3-2.2.2.
  
 8)COMPLY W/ATTACHED LIST OF REQS.FOR GAS
 DRAWINGS.
  
 9)HEAT TRAPS ARE REQD.ON THE WATER
 HEATERS PER F.E.C.SEC.412.1.ABCD.2.1.3.
  
 10)WATER HEATER SHALL BE READILY
 ACCESSIBLE PER SPC SEC.501.7.SUPPLY
 SHIP'S LADDER AND PLATFORM OR RELOCATE
 TO FLOOR.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 07:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-05 Cont ID  
Sent By sgraham Date 2001-04-05 Time 11:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***