| Plan Review Stops For Permit 00090869 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-11-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-11-09 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-23 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-10-23 |
Time |
08:16 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER ATTACHED TO APPLICATION |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-21 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-21 |
Time |
12:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-11 |
Time |
21:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-11 |
Time |
21:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE CALL FOR CORRECT LIST OF | | | CURRENT CODES WE ARE UNDER. NOT ALL ON | | | COVER SHEET ARE CORRECT. | | | | | | THE "99" NEC APPLIES FOR ELECTRICAL. | | | | | | 2)NOTE: PLEASE CLARIFY ALL ELECTRICAL | | | WORK ONLY BEING DONE FOR SHELL??? | | | SHOW ALL MIN EGRESS LIGHTING FOR ALL | | | FLOORS AND EMERGENCY/EXIT LIGHTING | | | REQ`D BY NFPA./LIFE SAFETY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-28 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-28 |
Time |
10:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-11-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-15 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-15 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ON NOVEMBER 17,2000, WRITER SPOKE TO | | | RICK RICKER OF SLATER PAUL AND | | | ASSOCIATES. THE FOLLOWING ITEMS WERE | | | DISCUSSED WITH MR. RICKER. | | | 1) VERIFICATION OF OCCUPANT LOAD FOR THE | | | ENTIRE BUILDING TO BE LESS THAN 50 | | | PERSONS. | | | 2) CODE ANALYSIS TABLE DOES NOT MATCH. | | | 3) FIRE CODE TRAVEL DISTANCE IS 150 | | | FEET WHICH IS MORE STRINGENT THAN THE | | | BUILDING CODES. | | | 4) FIRE HYDRANTS NOT SHONW ON PLANS. | | | 5) EXITING AND STAIRS WERE EXPLAINED | | | TO WRITER BY MR. RICKER. | | | 6) GENERATOR INSTALLATION TO POSSIBLY | | | OCCUR LATER. | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM INSTALLATION. | | | A LETTER IS TO BE PROVIDED BY MR. RICKER | | | TO THIS WRITER. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-10-06 |
Time |
10:32 |
Rev Time |
1.30 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.FIRE ALARM SYSTEM SHALL BE CLASS A OR | | | ADDRESSABLE. | | | 2.INDICATE LOCATION OF PROTECTED MEANS | | | OF EGRESS FROM 2ND AND 3RD FLOORS. | | | 3.PROVIDE EXIT LIGHT AND EMERGENCY LIGHT | | | LOCATIONS THROUGHOUT. | | | 4.PROVIDE DETAILS OF RATED STAIR ENCLOSU | | | RE. (WALLS AND SELF CLOSING DOORS) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-06 |
Time |
15:47 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-10-06 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LIMITED TO SCOPE OF WORK ON APPROVED | | | DRAWINGS AS SHOWN. ADDITIONAL WORK TO | | | BE SUBMITTED FOR APPROVAL PRIOR TO BEGIN | | | NING |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-11-03 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-11-03 |
Time |
10:35 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-11-03 |
Time |
10:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-09-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-23 |
Time |
08:52 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-09-23 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT COMPLETE PLUMBING PLANS THAT | | | REFLECT THE ENTIRE SCOPE OF PLUMBING | | | WORK TO BE PERFORMED.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|