Plan Review Details - Permit 00090804
Plan Review Stops For Permit 00090804
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-10-11 Cont ID  
Sent By hpiskura Date 2000-10-11 Time 14:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-10-04 Cont ID  
Sent By mgonzale Date 2000-10-04 Time 13:54 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISOS
  
 PLEASE REVISED PLANS SHOWING CORRECT
 LOCATION OF 6" FIRE SPRINKLER LINE IN
 RELATION TO THE PROPOSED INLET.
  
 NEW FIRE HYDRANT LOCATION SHOULD BE 2'
 MIN INSIDE OF CURB.
  
 PROVIDE DRAINAGE FLOW ARROWS AS SHOWN.
  
 A MINIMUM OF TWO SETS OF PLANS MUST
 SUBMITTED FOR APPROVAL AND UTILITY
 INSPECTOR.
 ATTENTION MANNY GONZALEZ
 ENGINEERING SERVICES
 1000 45TH ST SUITE 15
 WEST PALM BEACH, FL 33407
 561 659 8040 EXT .2306
  
 ALSO A MINIMUM OF 2 SHOP DRAWINGS
 SUBMITTALS MUST ALSO BE SUBMITTED.
  
 SHOW EXISTING FIRE HYDRANT (TO REMAIN)
  
 YOU MAY SAVE A VALVE SINCE THE TAP
 REQUIRES A TAP AND FIRE HYDRANT IS NOT
 FAR FROM TAP LOCATION.
  
 NEW PIPE SHALL BE CLASS52, CEMENT LINE
 D, DIP (FIRE HYDRANT LINE)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-09-28 Cont ID  
Sent By mcarsill Date 2000-09-28 Time 11:00 Rev Time 0.00
Received By mcarsill Date 2000-09-28 Time 11:00 Sent To  
Notes
2001-01-08 00:00:001) PLEASE INDICATE HOW FIRE AND
 PARAMEDICAL UNITS USE THE PROPOSED GATE
 ASSEMBLY.
 2) CLEAR WIDTH MUST BE AT LEAST 15 FEET
 BUT 20 FEET IN CLEAR WIDTH IS PREFERRED.
 APPROVED PROVISO:

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-20 Cont ID  
Sent By gjoyce Date 2000-09-20 Time 16:45 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***