| Plan Review Stops For Permit 00090510 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-01-11 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-11 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-01-11 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2001-01-11 00:00:00 | THE STAIRS AS SHOWN ON SHEET A-1A DO NOT | | | MEET THE RISER TO TREAD RATIO OF SBC | | | 1007.3.PLEASE REVISE AS NECESSARY. | | 2001-01-10 00:00:00 | DOES NOT MEET EGRESS FOR SECOND TENANT A | | | S SHOWN.CONTRACTOR WILL CALL BACK W/AR | | | CHITECT. 1/10/01 HHP REV 3 12/22/00 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2000-12-12 |
Time |
15:19 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2000-12-12 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-12-06 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-12-06 |
Time |
09:41 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-12-06 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1]SUBMIT 2 SETS OF REVISIONS FOR REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-10 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-10 |
Time |
15:19 |
Rev Time |
2.00 |
| Received By |
drunnels |
Date |
2000-10-10 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.PROVIDE SQUARE FOOTAGE OF AREA UNDER | | | CONTRACT IN ORDER TO CACULATE OCCUPANT | | | LOAD.TABLE 1003.1 | | | 2.PROVIDE PLANS AND DETAILS FOR 4TH | | | FLOOR ROOM. | | | 3. PROVIDE DETAILS FOR STAIRS TO 4TH | | | FLOOR ROOM " TREADS AND RISERS" | | | 4.SHEET A-1A DETAILS 8&9 REFRENCES EXIST | | | -ING RATED WALLS SUBMIT DETAIL SHOWING | | | UL RATING. | | | 5.SHEET A-1A DETAIL 10 REFERENCES GYPSUM | | | BOARD AND METAL STUD WALL SUBMIT SHOWING | | | UL# FOR TENANT SEPARATION. | | | 6.EXIT DOOR # 308 SWINGS WRONG DIRECTION | | | SECTION 1012.1.2 SBC 1997 EDITION | | | 7.EXIT DOOR LOCATION MUST COMPLY WITH | | | SECTION 1004.1.4 SBC 1997 EDITION | | | 8.SUBMIT RATING ON DOORS PER SECTION | | | 705.1.2 SBC 1997 EDITION. | | | 9.DEAD END CORRIDORS OVER 20 FEET ARE | | | NOT ALLOWED "CORRIDOR 306" SECTION | | | 1005.2 AND TABLE 1004 | | | 10. BUILDING IS CONSTRUCTION TYPE 2 ALL | | | LUMBER USED MUST COMPLY TO SECTION 6&7 | | | SBC 1997 EDITION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-20 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-20 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2001-08-20 00:00:00 | ***** NOTE********* | | | | | | 1)NOTE: REVIEW FOR SERVICE RISER DIAGRAM | | | ONLY. | | | | | | DV PALMER |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-30 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-30 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2001-07-30 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM JAN 17TH, | | | 2001 AND COMMENTS FROM JULY 21ST,2001. | | | | | | JAN`S COMMENTS ASKED FOR ALL REVISIONS | | | TO BE CLOUDED. PLANS CAME BACK IN FOR | | | A RE-STAMP?? NOT REVISION. | | | JULY`S COMMENTS STILL NOTED THAT BOTH | | | SETS WERE NOT THE SAME SHOWING CLOUDS | | | AND ALSO COMMENTS FOR TAPPED CONDUCTORS | | | PER 240-21. ALSO NEEDED TO BE SIGNED | | | AND SEALED PER FS/FAC. | | | NOW PLANS ARE SUBMITTED AGAIN AS | | | REVISIONS?? AND COMMENTSARE STILL NOT | | | ADDRESSED FROM EITHER REVIEW??? | | | | | | | | | PLEASE ADDRESS NOTES AND SUBMIT REVISION | | | -S FOR REVIEW. FEES WILL BE OWED FOR | | | ALL REVISIONS. IF THERE ARE ANY QUESTION | | | -S PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-07-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-21 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-21 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2001-07-21 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ELECTRICAL | | | RISER DIAGRAM SHOWS TAPS FROM THE TRANS- | | | -FORMER BEING TAPPED? PLEASE NOTE THAT | | | THESE TWO PANELS MAY BE FED WITH TWO | | | SEPARATE RUNS FROM THE TRANSFORMER BUT | | | NOT INTO A GUTTER AND THEN TAPPED AGAIN. | | | 240-21 | | | *TRANSFORMER CAN HAVE LUGS RATED FOR | | | MORETHAN ONE WIRE* | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | SIGNED, DATED OR SEALED BY THE ENGINEER | | | OF RECORD PER FS,FAC 471.025. | | | PLEASE ALSO NOTE THAT TWO DIFFERENT | | | SETS OF PLANS WERE SUBMITTED?? | | | PLEASE CORRELATE AND SUBMIT. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-17 |
Time |
20:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-17 |
Time |
20:27 |
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLANS INDICATE REVISIONS BEING | | | DONE ON 12/29/00 BUT NO CHANGES ARE | | | IDENTIFIED ON PLANS BY CLOUDS OR | | | TRIANGLES???PLEASE DO SO AND SUBMIT FOR | | | REVIEW. | | | | | | ALSO, MORETHAN 4 SHEETS SHOW REVISION | | | DATES PAST THE ISSUE DATE OF PERMIT. | | | FEES ARE OWED. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-11 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-11 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-20 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-20 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2001-08-20 00:00:00 | ACCORDING TO RICK LEE, THE STAIR IS | | | ONLY FOR CONVENIENCE. SINCE IT WILL | | | NOT BE USED FOR EXITING, THE STAIR | | | DETAILS WILL BE APPROVED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-01-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-09 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-09 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-11-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-29 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-29 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ON NOVEMBER 29,2000, THE DRAWINGS | | | WERE RED-LINED BY THE ARCHITECT WHICH | | | WERE FOLDED AND PLACED ON TOP OF THE | | | PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-21 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-21 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OLD PAGES NEED TO BE REPLACED WITH NEW | | | ONES. PLANS ARE DIFFICULT TO FOLLOW | | | WITH NEW ADDITIONS AND DELETIONS | | | TOGETHER. PLEASE CORRELATE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-09-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-21 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-21 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED ON | | | T-1. SHOULD READ NFPA 101, LIFE SAFETY | | | CODE, 1985 EDITION. | | | 2) INTERIOR FINISHES NEED TO BE NOTED | | | ON PLANS. | | | 3) NO HYDRAULIC CALCULATIONS PROVIDED | | | FOR FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. | | | 4) DRAFT STOP IS TO BE 18" NON | | | COMBUSTIBLE WITH FIRE SPRINKLER HEADS NO | | | FARTHER APART THAN 6' FEET. | | | 5) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101 REQUIREMENTS FOR SAME. | | | 6) HEADROOM IN MEANS OF EGRESS TO BE | | | 7'-6" OR 6'-8 WITH PROJECTIONS FROM | | | CEILING. | | | 7) PROVIDE SEPARATE PLANS AND PERMIT | | | FOR FIRE ALARM EQUIPMENT SHOWN ON PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-29 00:00:00 | REVISION DATED 12/29/00 - CHANGED | | | LOCATION OF VAV'S AND VARIOUS | | | DROPS...NO IMPACT. | | | PHK. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-12-07 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-07 |
Time |
15:33 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-12-07 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO CHANGES TO PREVIOUSLY REVIEWED PLANS | | | ACCEPTED AS SUBMITTED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-06 |
Time |
06:41 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-10-06 |
Time |
06:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-01-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-01-21 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2001-01-21 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2001-01-21 00:00:00 | REVISION ON BREAK RM SINK OK. PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-09-17 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-17 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2001-01-21 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | LOUNGE CABINET SHALL BE A MAX.OF 34"AFF | | | PER FACBC SECX.4.24.1-4.24.7. | | | | | | THE 30"X48"CLEAR FLOOR SPACE REQUIRED BY | | | THE ABOVE CODE SECS.SHALL BE CENTERED ON | | | THE FIXTURE. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|