Plan Review Details - Permit 00090361
Plan Review Stops For Permit 00090361
Review Stop P PLUMBING
Rev No 4 Status P Date 2000-10-13 Cont ID  
Sent By tlarge Date 2000-10-13 Time 11:15 Rev Time 1.25
Received By tlarge Date 2000-10-13 Time 11:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-10-05 Cont ID  
Sent By tlarge Date 2000-10-05 Time 17:50 Rev Time 0.65
Received By tlarge Date 2000-10-05 Time 17:50 Sent To  
Notes
2001-01-08 00:00:00SUBMIT PROPER SIZING TABLES FOR ALL PIPE
 MATERIAL BEING USED.SGC SEC.302.
  
 2)PLANS SHALL BE COMPILED INTO 2 SETS.
 DELETE ALL UNNECESSARY SHEETS.COUNTYWIDE
 AMENDMENTS 104.2.1.
  
 3)SUBMIT SIZING TABLE FOR 2 PSI SYSTEM.
 SGC SEC.302,COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-16 Cont ID  
Sent By pschmitz Date 2000-09-16 Time 09:04 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:002ND PLAN REVIEW DENIED
 (1) SEE ATTACHED COMMENTS, ADDRESS NOTES
 2,3,4,8, & ADDITONAL NOTES.
 (2) RETURN COMMENTS SHTS AND INFO ON
 PLEXCO PIPE,WITH TAB I PROVIDED.
 END OF COMMENTS PAUL SCHMITZ

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-09-10 Cont ID  
Sent By pschmitz Date 2000-09-10 Time 10:42 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SEPERATE PERMIT FOR PLUMBING.
 (2) TOTAL DEV. LGTH, TOT BTU'S.
 93) CUT SHT FOR MED PSI REGULATOR.
 (4) TYPE OF MATERIAL ABOVE GRADE & TAB
 USED. SGC 97
 (5) INFO ON PIPING TO ISLAND GRILL.
 END COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233