Plan Review Details - Permit 00090202
Plan Review Stops For Permit 00090202
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-10-25 Cont ID  
Sent By drunnels Date 2000-10-25 Time 08:49 Rev Time 2.00
Received By drunnels Date 2000-10-25 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-05 Cont ID  
Sent By drunnels Date 2000-10-05 Time 08:24 Rev Time 2.00
Received By drunnels Date 2000-10-05 Time 08:24 Sent To  
Notes
2001-01-08 00:00:001. PLANS ARE INCOMPLETE PLEASE SUBMIT
 SUFFICIENT PLANS FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-02-21 Cont ID  
Sent By dpalmer Date 2001-02-21 Time 08:20 Rev Time 0.00
Received By dpalmer Date 2001-02-21 Time 08:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-12-29 Cont ID  
Sent By dpalmer Date 2000-12-29 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2000-12-29 Time 15:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-31 Cont ID  
Sent By dpalmer Date 2000-10-31 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2000-10-31 Time 16:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-27 Cont ID  
Sent By dpalmer Date 2000-09-27 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2000-09-27 Time 19:10 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE COMPLETE AND SHOW LOAD
 CALCULATIONS. LOADS SHOWN AS ??? THIS IS
 NOT ACCEPTABLE. ALL LOADS MUST BE SHOWN
 215-5. PER ART;220 OF THE NEC.
  
 2)NOTE: PLEASE SHOW NEW PANEL "SP" ON
 PANEL SCHEDULE. NOT AS SUB PANEL??
  
 3)NOTE: PLEASE SHOW LOAD CALCS AND WHAT
 DERATING FACTORS YOU ARE USING.
 PLEASE NOTE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%. (LIGHTING, HEAT LAMPS
 ETC)
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-10-20 Cont ID  
Sent By mcarsill Date 2000-10-20 Time 11:26 Rev Time 0.00
Received By mcarsill Date 2000-10-20 Time 11:25 Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH INFORMATION WAS
 LOCATED ON PAGE I1.0, NOT PAGE I1.1
 FLAME CERTIFICATES ARE ATTACHED TO
 PERMIT APPLICATION AND ASSOCIATED
 PAPERWORK.
 2) PRE-EXISTING STEPS HAVE BEEN
 APPROVED BY THE BUILDING DEPARTMENT
 PER DEAN RUNNELS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-18 Cont ID  
Sent By mcarsill Date 2000-09-18 Time 10:30 Rev Time 0.00
Received By mcarsill Date 2000-09-18 Time 10:30 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE PROVISIONS FOR AT
 LEAST TWO HANDICAPPED PERSONS WITH
 REGARDS TO SEATING WITHIN RESTAURANT.
 2) PLEASE PROVIDE MORE DETAILS ON
 INTERIOR FINISHES. INTERIOR FINISHES
 SHALL BE CLASS A,B, OR C.
 3) ANY CHANGES IN ELEVATIONS LESS THAN
 21" SHALL BE BY RAMPS. NO LESS THAN
 THREE STAIRS AT 7" EACH SHALL BE
 PROVIDED WHEN STAIRS ARE NEEDED.
 4) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 1985 LIFE SAFETY CODE NOT
 1997 LIFE SAFETY CODE.
 5) ANY DOOR IN A REQUIRED MEANS OF
 EGRESS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS SHALL HAVE PANIC
 HARDWARE ON IT.
 6) NEW FABRIC CANOPY NOTED ON PAGE A3.1
 IS TO BE FIRE RETARDANT. FLAME
 CERTIFCATIONS ARE TO BE SUBMITTED.
 7) PLEASE INDICATE WHERE THE FIRE ALARM
 AUDIO-VISUAL DEVICES ARE LOCATED. THE
 SMOKE DETECTORS AND MANUAL PULL
 STATIONS WERE LOCATED ON PAGE E-2.
 8) COMPLETE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE HOOD,DUCT
 AND EXTINGUISHING SYSTEM.
 9) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ndenmark Date 2000-12-28 Time 15:13 Sent To  
Notes
2001-01-08 00:00:00CAN NOT LOCATE ORIGINAL TO REVIEW
 REVISION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-28 Cont ID  
Sent By ndenmark Date 2000-10-28 Time 14:04 Rev Time 0.25
Received By ndenmark Date 2000-10-28 Time 14:03 Sent To  
Notes
2001-01-08 00:00:00NO CHANGES FROM LAST APPROVED PLAN
 SAME PROVISO COMMENTS APPLY RE: SEPARATE
 PERMITS REQUIRED FOR HOODS AND SUPPRES-I
 SION SYSTEMS AND WALK IN BOXES AS NOTED
 BEFORE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-11 Cont ID  
Sent By ndenmark Date 2000-09-11 Time 16:25 Rev Time 0.33
Received By ndenmark Date 2000-09-11 Time 16:25 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 SEPARATE PERMITS REQUIRED FOR HOODS AND
 SUPPRESSION SYSTEM TESTS ON THESE ARE
 REQUIRED
 SUBMIT PLANS AT TIME OF MECH PERMIT APPL
 ICATION FOR THESE SYSTEMS

Review Stop P PLUMBING
Rev No 9 Status P Date 2001-03-08 Cont ID  
Sent By pschmitz Date 2001-03-08 Time 09:20 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 8 Status P Date 2001-02-23 Cont ID  
Sent By pschmitz Date 2001-02-23 Time 15:43 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status P Date 2001-01-31 Cont ID  
Sent By pschmitz Date 2001-01-31 Time 07:26 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status F Date 2001-01-28 Cont ID  
Sent By pschmitz Date 2001-01-28 Time 10:21 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-28 00:00:00PLUMBING PLAN REVIEW 6TH TIME
 (1)SHT.P-2 GREASE TRAP,MAKE,MOD;SIZE.
 (2) SHT'S P-1,FS-1 QUESTION ON LOCATION
 OF F/S,F/D THAT WILL SERVE,INDIRECT
 WASTE ANDSTAY 6" OFF FLR,ALSO F/D AT
 COOLER DOOR.
 (3) SHT P-2 DISHWASHER, ONLY 1 F/S SHOWN
 ALL INDIRECT WASTE TO BE 6" OFF FLR.
 (4) SHT P-5 GAS PIPE SUPPORT 6" OFF FLR.
 2-1/2" RUN DIRECTLY TO 2" HEADER.
 (4) PUBLIC REST RM'S PLANS NEED TO BE
 INCLUDED IN THIS PLAN REVIEW.
 END OF COMMENTS,QUESTIONS CONTACT
 PAUL SCHMITZ 561-6549-8096 X 8233

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-01-02 Cont ID  
Sent By pschmitz Date 2001-01-02 Time 14:04 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW5TH TIME
 SEE PREVIOUS NOTES ON ATTACHED.
 QUESTIONS CONTACT PAUL SCHMITZ
 5671 659 8096 X 8233

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-12-31 Cont ID  
Sent By pschmitz Date 2000-12-31 Time 11:08 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW CODE REFERENCES
 SPC 94SGC 97FACBC 97
 (1) SHTS P-1,P-2 SHOW OCCUPANCY LOAD AS
 REQUIRED,TAB 407 MIN. NUMBER FACILITIES.
 SHOW REST RM LAY OUT W/ DEMINSIONS AND
 ELEVATIONS TO COMPLY W/FACBC SEC 4.22
 (2)PROVIDE KITCHEN EQUIPMENT DRWGS.
 (3) CONTACT WPB REGIONAL SEWER PLANT
 RODNEY COMPO 561-835-7423 FOR APPROVAL,
 GREASE TANK,SIZE,LOCATION AND CUT SHTS.
 (4) REST RM'S (S-1) W/C P-1 NOT VENTED,
 SHOW DWV PIPE SIZES FOR THIS BRANCH.
 TRAP PRIMER WATER SUPPLY TO A PLUMBING
 FIXTURE IN THE SAME ROOM.SEC 409.4
 (5)LOCATION AND SIZE OF WTR HTR,ENERGY
 TYPE.SEC 104.2
 (6) THIS IS THE THIRD TIME IN FOR PLAN
 REVIEW,PLEASE COMPLY WITH PREVIOUS
 COMMENTS AND ABOVE COMMENTS,ATTACHED.
 QUESTIONS CONTACT PAUL SCHMITZ
 561-659 8096 X 8233
 SEE ATTACHED GAS PIPING REQUIRMENTS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-01-02 Cont ID  
Sent By drunnels Date 2000-11-02 Time 10:04 Rev Time 1.00
Received By pschmitz Date 2000-11-02 Time 10:03 Sent To  
Notes
2001-01-08 00:00:00NO PLUMBING/ PLUMBING TO BE UNDER
 SEPERATE PERMIT

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-21 Cont ID  
Sent By pschmitz Date 2000-10-21 Time 12:43 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW RESUBMIT DENIED
 PLEASE ADDRESS PREVIOUS COMMENTS BY
 TIM LARGE DATED09-12-00
 (5)LOCATION & SIZE OF EX GREASE TRAP.
 CONTACT RODNEY COMPO 561-835-7423
 WPB.REG.SEWER PLANT FOR APPROVAL,WITH
 COPIES TO THIS OFFICE.
 (10) SPC SEC 914 DESIGN OF CIRCUIT/LOOP,
 W/C IN WOMENS LOUNGE, NOT VENTED,
 CONNECT STACK S-2 TO HORZ 3" W/C WASTE.
 (12) SUBMIT ISOMETRIC OF GREASE WASTE,
 ALL INDIRECT WASTE TO F/S.
 (13) GAS ISOMETRIC SEC 104.2 GAS PSI,
 TYPE OF MATERIAL,TOT. DEVELOPED LENGTH,
 TOT. BTU'S,LOCATION OF EMERGENCY SHUT
 OFF VALVE,W/MANUAL SHUT OFF UP STREAM,
 UNION DOWN STREAM, ALL BELOW CEILING.
 (16) HORIZONTAL WASTE & VENT SYSTEM,
 SEC 921.4.1,921.4.2 DESIGN 2 PIPE SIZES
 LARGER,MIN SIZE MAIN 4",BRANCHES3"
 HAND SINKS MAY BE 2".
 (17) ALL INDIRECT WASTE TO F/S
 (1) ADDED NOTE, DISHWASHER WASTE TO
 TO SANITARY SEWER,LOCAL ORDINANCE2425-90
 END OF COMMENTS PAUL SCHMITZ

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-09-12 Cont ID  
Sent By tlarge Date 2000-09-12 Time 20:35 Rev Time 2.50
Received By pschmitz Date 2000-09-12 Time 19:37 Sent To  
Notes
2001-01-08 00:00:001)INDICATE OCCUPANT LOAD OF RESTAURANT
 BASED ON SPC TABLE 407.SEE SPC SEC.
 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS.
  
 2)SUBMIT DAY,MONTH AND YEAR BUILDING WAS
 PERMITTED FOR CONSTRUCTION.COMPLIANCE
 W/FLA.STATUTE 553.141 MAY BE REQD.
  
 3)SUBMIT OCCUPANT LOAD OF BANQUET ROOM
 FOR POSSIBLE COMPLIANCE W/F.S.553.141.
  
 4)PLANS SHALL BE ROUTED TO DEPT.OF BUS.
 REGULATION FOR REVIEW AND APPROVAL PRIOR
 TO REVIEW BY THIS DEPT.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.101.4.7.
  
 5)SUBMIT VERIFICATION OF EXISTING GREASE
 INTERCEPTOR.NOTE SIZE AND LOCATION ON
 PLAN.CONTACT R.COMPO AT 561-835-7423 FOR
 APPROVAL.SUBMIT COPY OF APPROVAL TO THIS
 OFFICE.SPC SEC.101.4.7.
  
 6)PER SPC TABLE 407-THE MINIMUM NUMBER
 OF REQUIRED SANITARY FACILITIES IS AS
 FOLLOWS:MALES-4 WATER CLOSETS
 2 LAVATORIES
 FEMALES -4 WATER CLOSETS
 2 LAVATORIES
 THIS DOESN'T INCLUDE COMPLIANCE W/F.S.
 553.141.
  
 7)SHT.A2.4-"TYP.MOUNTING HEIGHT"-REVISE
 GRAB BAR MEASUREMENTS.(LENGTH AND MOUNT-
 ING HEIGHTS)THEY DO NOT COMPLY W/FACBC.
 AND DIMENSIONS SHALL BE LEGIBLE.
  
 8)SHT.A2.4-CENTERLINE OF ACCESSIBLE
 WATER CLOSET FROM WALL SHALL COMPLY W/
 FACBC SEC.4.16 AND FIG.#30.
  
 9)SHT.A2.4-IDENTIFY ACCESSIBLE URINAL
 ON PLANS AND SHOW CLEAR FLOOR SPACE FOR
 URINAL.FACBC SEC.4.18.
  
 10)DESIGN OF PLUMBING SYSTEM SHALL
 COMPLY W/SPC SEC.914 FOR CIRCUIT AND
 LOOP SYSTEM IF THAT IS THE INTENT.
  
 11)SHT.P-1-LAYOUT OF PLUMBING SYSTEM
 ON FLOOR PLAN DOESN'T CORRELATE W/
 SANITARY RISER ON P-2.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 12)SUBMIT AN ISOMETRIC DRAWING FOR ALL
 NEW PLUMBING WORK TO BE INSTALLED.COUNTY
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 13)SUBMIT A GAS ISOMETRIC FOR ANY NEW
 GAS WORK.SHOW DISTANCE FROM POINT OF
 DELIVERY TO MOST REMOTE OUTLET,TYPE OF
 PIPING,TYPE OF GAS,DELIVERY PSI ETC.IN
 ORDER TO VERIFY EXISTING SYSTEM COMPLIES
 W/CODE.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.3.1
  
 14)DRY VENTS NOT PERMITTED.BASE OF STACK
 SHALL BE WASHED.SPC SEC.906.2.1.
  
 15)SHOW SIZE OF EXIST.STACK S/1.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 16)HORIZ.COMBINATION WASTE AND VENT
 SYSTEM SHALL COMPLY W/SPC SEC.921.
  
 17)ALL INDIRECT WASTES SHALL DISCHARGE
 TO FLOOR SINKS,NOT FLOOR DRAINS.SPC SEC.
 804.1,807.1.3.
  
 18)SIZE OF PIPE INSULATION SHALL COMPLY
 W/F.E.C.TABLE 411.
  
 19)SIZE EXISTING RISER S/1 AND VENT
 STACK.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 20)ALL SHEETS SHALL BE SIGNED AND SEALED
 PER F.A.C.61G15-23.002.(SEE P-1).
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.