Plan Review Details - Permit 00090162
Plan Review Stops For Permit 00090162
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-07 Cont ID  
Sent By tlarge Date 2000-09-07 Time 06:21 Rev Time 0.30
Received By tlarge Date 2000-09-07 Time 06:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-09-06 Cont ID  
Sent By tlarge Date 2000-09-06 Time 11:10 Rev Time 0.33
Received By tlarge Date 2000-09-06 Time 11:10 Sent To  
Notes
2001-01-08 00:00:001)APPLICATION NOTES"REPLACE FUEL LINE TO
 RANGE ONLY"BUT PLANSSHOW PIPING TO
 WATER AND GAS DRYER.CLARIFY.SGC SEC.301.
  
 2)CLEARLY NOTE ON PLAN IF GAS IS LP OR
 NATURAL.THE SUBMITTED TABLE IS FOR LP
 GAS.SUBMIT CORRECT TABLE.SGC 301,305.4.
  
 3)SUBMIT GAS ISOMETRIC SHOWING ROUTING
 OF GAS LINE.SGC SEC.301.
  
 4)COMPLY W/ATTACHED REQS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.