Plan Review Details - Permit 00090135
Plan Review Stops For Permit 00090135
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-09-06 Cont ID  
Sent By lmartine Date 2000-09-06 Time 11:26 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-09-06 Cont ID  
Sent By mcarsill Date 2000-09-06 Time 10:22 Rev Time 0.00
Received By mcarsill Date 2000-09-06 Time 10:22 Sent To  
Notes
2001-01-08 00:00:001) ON SEPTEMBER 6, 2000, THIS WRITER
 CONTACTED MR. NORDINE BY TELEPHONE. MR.
 NORDINE ADVISED THAT 8 TO 9 DOORS
 THROUGHOUT THE BUILDING WILL BE REPLACED
 TO 1 1/2 RATED FIRE DOORS. ALSO MR.
 NORDINE ADVISED THAT 5/8 TYPE X SHEET
 ROCK WILL BE USED.
 2) FIRE DOORS TO BE USED ARE TO BE
 PROPERLY LABELED IN ACCORDANCE WITH
 NFPA 80, FIRE DOORS AND WINDOWS, SECTION
 1-6.1. FIRE DOORS THAT ARE INSTALLED TO
 EQUIPPED WITH SELF-CLOSING DEVICES PER
 NFPA 80, FIRE DOORS AND WINDOW, SECTION
 2-4.1.2. METAL DOOR FRAMES ARE TO
 BE LABELED PER NFPA 80, FIRE DOORS AND
 WINDOWS, SECTION 2-3.1.1
 APPROVED PROVISO: