Plan Review Details - Permit 00090101
Plan Review Stops For Permit 00090101
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-11-03 Cont ID  
Sent By drunnels Date 2000-11-03 Time 11:20 Rev Time 1.00
Received By drunnels Date 2000-11-03 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-20 Cont ID  
Sent By lmartine Date 2000-09-20 Time 12:15 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 SECTION 4.12.6,'97 SBC REQUIRES
 ELEVATOR LOBBIES,PROVIDE COMPLETE 9TH FL
 LAYOUT TO CLERIFY LOBBY SITUATION AND
 SHOW EXIT AT DOOR "C" DOES NOT EXIT THRU
 ADJACENT TENANT SPACE.
  
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096
 EXT;8456

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-31 Cont ID  
Sent By dpalmer Date 2000-10-31 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2000-10-31 Time 19:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-21 Cont ID  
Sent By dpalmer Date 2000-09-21 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2000-09-21 Time 10:39 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE COMPLETE ADDED LOADS FOR
 PANEL "HA". PANELS "LA" AND "LB " WERE
 OK.
  
 PLANS WOULD HAVE PASSED WITH PROVISO BUT
 WERE COMING BACK FOR BLDG. COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-10-16 Cont ID  
Sent By mcarsill Date 2000-10-16 Time 13:59 Rev Time 0.00
Received By mcarsill Date 2000-10-16 Time 13:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-06 Cont ID  
Sent By mcarsill Date 2000-09-06 Time 12:41 Rev Time 0.00
Received By mcarsill Date 2000-09-06 Time 12:40 Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH ON WALLS AND CEILINGS
 IN EXITS TO BE CLASS A OR B. INTERIOR
 FINISH IN OFFICES ON WALLS AND CEILINGS
 TO BE CLASS A,B, OR C.
 2) NO FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS. PLEASE PROVIDE FIRE SPRINKLER
 DRAWINGS WITH PLANS.
 3) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM SHOP DRAWINGS FOR FIRE ALARM
 EQUIPMENT SHOWN ON PLANS. FIRE ALARM
 EQUIPMENT TO BE CLASS A, STYLE D NOT
 CLASS B, STYLE C AS SHOWN IN FIRE ALARM
 NOTES.

Review Stop FS  
Rev No 1 Status P Date 2000-09-07 Cont ID  
Sent By mcarsill Date 2000-09-07 Time 16:15 Rev Time 0.00
Received By mcarsill Date 2000-09-07 Time 16:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-30 Cont ID  
Sent By ndenmark Date 2000-10-30 Time 17:20 Rev Time 0.33
Received By ndenmark Date 2000-10-30 Time 17:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-11 Cont ID  
Sent By ndenmark Date 2000-09-11 Time 16:25 Rev Time 0.25
Received By ndenmark Date 2000-09-11 Time 16:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-10 Cont ID  
Sent By tlarge Date 2000-09-10 Time 10:12 Rev Time 0.33
Received By pschmitz Date 2000-09-10 Time 10:12 Sent To  
Notes
***NONE***