Plan Review Details - Permit 00090101
| Plan Review Stops For Permit 00090101 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-11-03 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-03 |
Time |
11:20 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-11-03 |
Time |
11:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-20 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | SECTION 4.12.6,'97 SBC REQUIRES | | | ELEVATOR LOBBIES,PROVIDE COMPLETE 9TH FL | | | LAYOUT TO CLERIFY LOBBY SITUATION AND | | | SHOW EXIT AT DOOR "C" DOES NOT EXIT THRU | | | ADJACENT TENANT SPACE. | | | | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 561-659-8096 | | | EXT;8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-31 |
Time |
19:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-31 |
Time |
19:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-09-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-21 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-21 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE COMPLETE ADDED LOADS FOR | | | PANEL "HA". PANELS "LA" AND "LB " WERE | | | OK. | | | | | | PLANS WOULD HAVE PASSED WITH PROVISO BUT | | | WERE COMING BACK FOR BLDG. COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-16 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-16 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-06 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-06 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH ON WALLS AND CEILINGS | | | IN EXITS TO BE CLASS A OR B. INTERIOR | | | FINISH IN OFFICES ON WALLS AND CEILINGS | | | TO BE CLASS A,B, OR C. | | | 2) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. PLEASE PROVIDE FIRE SPRINKLER | | | DRAWINGS WITH PLANS. | | | 3) PLEASE PROVIDE COMPLETE FIRE ALARM | | | SYSTEM SHOP DRAWINGS FOR FIRE ALARM | | | EQUIPMENT SHOWN ON PLANS. FIRE ALARM | | | EQUIPMENT TO BE CLASS A, STYLE D NOT | | | CLASS B, STYLE C AS SHOWN IN FIRE ALARM | | | NOTES. |
|
|
| Review Stop |
FS |
|
| Rev No |
1 |
Status |
P |
Date |
2000-09-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-07 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-07 |
Time |
16:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-10-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-30 |
Time |
17:20 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-10-30 |
Time |
17:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-09-11 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-11 |
Time |
16:25 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-09-11 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-09-10 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-10 |
Time |
10:12 |
Rev Time |
0.33 |
| Received By |
pschmitz |
Date |
2000-09-10 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
|