Plan Review Details - Permit 00090058
Plan Review Stops For Permit 00090058
Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-11-05 Cont ID  
Sent By pkrauss Date 2001-11-05 Time 08:50 Rev Time 0.45
Received By pkrauss Date 2001-11-05 Time 08:01 Sent To  
Notes
2001-11-05 00:00:00*******************DENIED***************
  
  
 PLAN SHEETS M2.00, M2.01 & M2.03
 INDICATE HEAT WHEEL ON ROOF.PLAN
 SHEET M2.03 DOES NOT SHOW A DETAIL OF
 THE HEAT WHEEL AS THE ORIGINAL
 SUBMITTAL DID.
  
 PROVISO ON THE ORIGINAL PLAN WAS NOT
 ADDRESSED.MINIMUM OF 10' SEPARATION
 BETWEEN O.A. AND EXHAUST.
  
 PLEASE PROVIDE DETAIL OF HEAT WHEEL
 WITH SEQUENCE OF OPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-23 Cont ID  
Sent By pkrauss Date 2001-02-23 Time 08:25 Rev Time 0.33
Received By pkrauss Date 2001-02-23 Time 08:25 Sent To  
Notes
2001-02-23 00:00:00PER APPROVED REVISIONS W/ MAIN PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-09-06 Cont ID  
Sent By ndenmark Date 2000-09-06 Time 09:34 Rev Time 0.25
Received By ndenmark Date 2000-09-06 Time 09:34 Sent To  
Notes
2001-01-08 00:00:00PLAN REVIEW FOR MECH FAILED ON BLDG
 PERMIT NUMBER 00081069