Plan Review Details - Permit 00081726
Plan Review Stops For Permit 00081726
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-12-05 Cont ID  
Sent By drunnels Date 2000-12-05 Time 12:39 Rev Time 1.00
Received By drunnels Date 2000-12-05 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-10-11 Cont ID  
Sent By drunnels Date 2000-10-11 Time 13:31 Rev Time 1.00
Received By drunnels Date 2000-10-11 Time 13:31 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT PRODUCT APPROVALS FOR WINDOW &
 DOOR GLAZING FOR STOREFRONT/ METRO DADE
 COUNTRY OR SBCCI SSTD12-97
 2. SUBMIT PLANS AND APPLICATION FOR
 PERMIT FOR FIRE SPRINKLER
  
 PROVISO
 1.ALL WOOD TO BE FRT PER CHAPTER 6 SBC
 2.SIGNS TO BE UNDER SEPARATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-13 Cont ID  
Sent By drunnels Date 2000-09-13 Time 14:53 Rev Time 1.00
Received By drunnels Date 2000-09-13 Time 14:53 Sent To  
Notes
2001-01-08 00:00:001.SHEET A0.1
 CHANGE CODE REFRENCE TO SBC 1997
 EDITION.
 BUILDING CONST.IS TYPE 2 NOT TYPE 4
 2.SHEET A5.2 SECTION 13 NOTE AT TOP
 SHOWS 5/8 INCH PLYWOOD & NOTE AT
 BOTTOM SHOWS 1/2 PLYWOOD PLEASE
 CLARIFY?
 3.SUBMIT WALL SECTION SHOWING TENANT
 DENIZING WALLS FIRE RATING AND UL #
  
 4.SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION FROM SPRINKLER CONTRACTOR.
 5.SUBMIT PRODUCT APPROVAL FOR WINDOW &
 DOOR GLAZING FOR STOREFRONT/ MTERO
 DADE COUNTY OR SBCCI SSTD12-97.
  
 PROVISO
 1) ALL WOOD TO BE FRT PER SP.3 SECTION
 06100.
 2) SIGNS TO BE UNDER SEPERATE PERMIT

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-21 Cont ID  
Sent By dpalmer Date 2001-03-21 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2001-03-21 Time 18:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-11 Cont ID  
Sent By dpalmer Date 2000-10-11 Time 10:52 Rev Time 0.00
Received By dpalmer Date 2000-10-11 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 17:32 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 17:32 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE PROVIDE INFORMATION FOR
 ENGINEER OF RECORD PER FL ADMINISTRATIVE
 CODE.61G15-23.002
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION
 ON WIRE SIZE FEEDING PANEL "DP".
 PANEL IS SHOWN TO BE 225A MAX.?
  
 3)NOTE: PLEASE SHOW ALL RECEPTS UNDER
 210-8 AS BEING GFI/GFI PROTECTED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-10-11 Cont ID  
Sent By mcarsill Date 2000-10-11 Time 11:33 Rev Time 0.00
Received By mcarsill Date 2000-10-11 Time 11:33 Sent To  
Notes
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.
 2) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON DRAWINGS.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-12 Cont ID  
Sent By mcarsill Date 2000-09-12 Time 10:19 Rev Time 0.00
Received By mcarsill Date 2000-09-12 Time 10:19 Sent To  
Notes
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 FOR FIRE SPRINKLER PLAN.
 2) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. HOW IS BASE BUILDING FIRE ALARM
 SYSTEM HEARD WITHIN TENANT SPACE.
 3) PROVIDE EMERGENCY LIGHTING IN
 STOCKROOM.
 4) EXITING PERMITTED IN STOCKROOM IF THE
 FOLLOWING CONDITIONS EXIT, DOOR LEADING
 TO STOCKROOM CANNOT BE LOCKED, AN AISLE
 OF AT LEAST 44" WIDE IS TO BE PROVIDED
 AND MAINTAINED, AND NOT MORE THAN 50
 PERCENT OF THE EXIT ACCESS IS TO BE
 PROVIDED THROUGH STOCKROOM.
 5) FIRE EXTINGUISHERS ARE TO BE PROVIDED

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-03-30 Cont ID  
Sent By pkrauss Date 2001-03-28 Time 13:25 Rev Time 0.25
Received By pkrauss Date 2001-03-28 Time 13:10 Sent To  
Notes
2001-03-28 00:00:00ONLY PROVIDED 1 SET OF PLANS
 AS BUILTS - KEEP PLANS SUBMITTED, RED
 LINED IN FIELD, OKAY PER LOU HATTON.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-12-19 Cont ID  
Sent By ndenmark Date 2000-12-19 Time 08:56 Rev Time 0.33
Received By ndenmark Date 2000-12-19 Time 08:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-04 Cont ID  
Sent By ndenmark Date 2000-12-04 Time 14:33 Rev Time 0.50
Received By ndenmark Date 2000-12-04 Time 14:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-10-17 Cont ID  
Sent By ndenmark Date 2000-10-17 Time 17:33 Rev Time 0.50
Received By ndenmark Date 2000-10-17 Time 17:33 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1. THE USE OF CO2 SENSORS TO REDUCE THE
 AMOUNT OF OUTSIDE AIR REQUIRED BY ASHRAE
 62-89 IS NOT SPECIFIED AS AN ALTERNATIVE
 METHOD. ACCEPTABLE REDUCTION METHODS ARE
 GIVEN IN 6.1.3.4 INTERMITTENT OR
 VARIABLE OCCUPANCY. "PEAK OCCUPANCIES OF
 LESS THAN THREE HOURS DURATION" AND WHEN
 "PROVIDED THE AVERAGE OCCUPANCY USED IS
 NOT LESS THAN ONE-HALF THE MAXIMUM.
 THE USE OF CO2 SENSORS TO REDUCE REQUIRE
 AMOUNTS OF OUTSIDE AIR DOES NOT TAKE INT
 CONSIDERATION THE EFFECTS OF POSSIBLE
 ELEVATION OF OTHER CONTAMINANTS.
 2. DRAWING M 2.1 SHOWS AUX. PAN DRAIN
 CONNECTED TO PRIMARY CONDENSATE DRAIN
 LINE. DETAIL IN CIRCLE DOES NOT SHOW
 THIS. NOTE THAT AUX DRAIN LINE SHALL NOT
 BE CONNECTED TO PRIMARY DRAIN LINE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-09-13 Cont ID  
Sent By ndenmark Date 2000-09-13 Time 12:34 Rev Time 0.50
Received By ndenmark Date 2000-09-13 Time 12:33 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.PROVIDE INFORMATION ON O/A DAMPER
 CAPACITIES (MAX AND MIN)
 DO NOT REDUCE OUTSIDE AIR BELOW
 VALUES SHOWN ON M2.0 ( 1940 CFM) BY CO2
 SENSOR. 1940 CFM IS MINIMUM REQUIRED
 VOLUME PER ASHRAE 62-89 TABLE 2.
 2 PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3.CONDENSATE DRAIN LINE AND EMERGENCY
 OVERFLOW DRAIN LINE SHALL NOT CONNECT
 TOGETHER. OVERFLOW DRAIN LINE SHALL
 TERMINATE IN A CONSPICOUS LOCATION. 1997
 SMC 304.8.6.1
 4. NOTE: RETURN AIR PLENUM AREA ABOVE
 CEILING TO BE CONSTRUCTED ENTIRELY OF
 NONCOMBUSTIBLE MATERIALS. PER 1997 SMC
 609.1.1

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-07 Cont ID  
Sent By tlarge Date 2000-10-07 Time 09:30 Rev Time 1.25
Received By tlarge Date 2000-10-07 Time 08:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-09-12 Cont ID  
Sent By tlarge Date 2000-09-12 Time 18:20 Rev Time 1.00
Received By tlarge Date 2000-09-12 Time 17:21 Sent To  
Notes
2001-01-08 00:00:001)TITLE SHEET-CODE INFORMATION-NOTE
 STANDARD PLUMBING CODE W/1999 COUNTYWIDE
 AMENDMENTS.
  
 2)SUBMIT SQUARE FOOTAGE OF HABITABLE
 FLOOR SPACE TO SHOW COMPLIANCE W/SPC
 TABLE 407.SEE SPC SEC.407.1.3. FOR
 ALLOWED DEUCTIBLE AREAS.ADDITIONAL
 PLUMBING FIXTURES MAY BE REQD.
  
 3)DOOR CANNOT SWING INTO CLEAR FLOOR
 SPACE FOR LAV.IN MEN'S TOILET ROOM PER
 FACBC SEC.4.22.2.
  
 4)MAX.HT.OF LAVATORY TO RIM SHALL BE 34"
 PER FACBC SEC.4.19.2.
  
 5)FLOOR DRAINS IN TOILET ROOM SHALL BE A
 MIN.OF 3" PER SPC SEC.409.4.1.1.
  
 6)TERMINATION PT.OF T & P LINE SHALL
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.507.8.4.THE LINE SHALL NOT DISCHARGE
 TO CD.
  
 7)WATER CLOSETS AND FLOOR DRAINS ARE NOT
 PROPERLY VENTED.COMPLY W/SPC SEC.
 906.2.1.
  
 8)CLEANOUTS SHALL BE INSTALLED PER SPC
 SEC.710.2.1.
  
 9)SHT.M3.0 REFERS TO GAS SYSTEM.IF NOT
 APPLICABLE REMOVE FROM PLANS.
  
 10)EACH SHEET WHICH MUST BE SEALED BY
 THE PROFESSIONAL ENGINEER SHALL LEGIBLY
 INDICATE THEIR NAME,ADDRESS AND NUMBER
 ON EACH SHEET PER FLA.ADMIN.CODE
 61G15-23.002.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.