Plan Review Details - Permit 00081675
Plan Review Stops For Permit 00081675
Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-08-16 Cont ID  
Sent By dpalmer Date 2001-08-16 Time 12:58 Rev Time 0.00
Received By dpalmer Date 2001-08-16 Time 12:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-08-14 Cont ID  
Sent By dpalmer Date 2001-08-14 Time 10:43 Rev Time 0.00
Received By dpalmer Date 2001-08-14 Time 10:43 Sent To  
Notes
2001-08-14 00:00:00PROVISO FROM PREVIOUS REVIEW STILL
 STANDS. 11/27/00

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-11-27 Cont ID  
Sent By dpalmer Date 2000-11-27 Time 17:57 Rev Time 0.00
Received By dpalmer Date 2000-11-27 Time 17:57 Sent To  
Notes
2001-01-08 00:00:00************* REVISION REQ'STED ********
  
 1)NOTE: PLEASE SHOW BLDG. STEEL AS PART
 OF THE GROUNDING ELECTRODE SYSTEM PER
 250-50 ON RISER DIAGRAM.
  
 2)NOTE: PLEASE SHOW AIC RATINGS OF MAINS
 AND PANEL. PER 110-9 AND 215-5
  
 PLEASE SUBMIT AND SHOW ALL THE ABOVE
 INFORMATION ON PLAN BEFORE ROUGH ELECTR-
 -ICAL INSPECTION IS CALLED IN. IF THERE
 ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-11-16 Cont ID  
Sent By dpalmer Date 2000-11-16 Time 17:41 Rev Time 0.00
Received By dpalmer Date 2000-11-16 Time 17:41 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES FROM PRIOR
 REVIEWS. NOT ALL NOTES WERE ADDRESSED???
  
 2)NOTE: PLEASE SEE RISER, PANEL SHOWS
 IT AS MCB? AND PANEL SCHEDULE SHOWS MLO?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE THAT NO AIC RATINGS
 FOR MAIN DISCONNECT OR PANEL WERE SHOWN?
 MAINS AND PANELS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. PER 110-9.
  
 4)NOTE: AS ON PRIOR REVIEW PLEASE SHOW
 NEW BLDG STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. PER 250-50 FOR
 NEW BLDG FOOTERS.!!
  
 5)NOTE: PLEASE SEE NOTES FROM BLDG AND
 MY REVIEW. SEE F.A.C 61G16 AND 481.221
 PLANS ARE SIGNED,SEALED AND DATED.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-10-24 Cont ID  
Sent By dpalmer Date 2000-10-24 Time 17:19 Rev Time 0.00
Received By dpalmer Date 2000-10-24 Time 17:19 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE 680-6-A-2 FOR NOTE
 SHOWN FOR POOL AREA. PLEASE ADJUST PLAN
 NOTE.
  
 2)NOTE: NOW THAT YOU HAVE SUBMITTED A
 RISER DIAGRAM SHOWING ALL NEW SERVICE
 BEING INSTALLED, PLEASE SUBMIT AIC
 RATINGS FOR ALL EQUIPMENT BEING INSTALL-
 -ED. MIAN DISC/ AND PANEL MUST BE RATED
 FOR THE AVAIABLE FAULT CURRENT PER 110-9
 AND 215-5.
  
 3)NOTE: PLEASE SEE ART 384-7 AND 110-26
 OF THE NEC. NEW PANEL SHOWN IN BATHROOM
 CLOSET MAY NOT BE INSTALLED IN THAT
 LOCATION. PLEASE ADJUST LOCATION AND
 MAKE CHANGES TO PLAN.
  
 4)NOTE: PER 250-50 NEW BLDG STEEL MUST
 BE BONDED TO GROUNDING ELECTRODE CONDUC-
 -TOR.PLEASE SHOW ON RISER DIAGRAM 215-5
  
  
 5)NOTE: PLEASE SEE THE REQ`MENTS PER FL
 ADMINISTATIVE CODE FOR PLANS TO CONTAIN
 INFORMATION ON ARCH OF RECORD. PLEASE
 CLARIFY FRANCIS DIGIOVANI? IS THIS THE
 FIRM UNDER WHICH PATRICK SEAGRAVES WORKS
 ?? PLEASEDATE THE SIGNED AND SEALED
 PLAN. ALL PER 61G16 AND 471.221.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-14 Cont ID  
Sent By dpalmer Date 2000-09-14 Time 20:42 Rev Time 0.00
Received By dpalmer Date 2000-09-14 Time 20:42 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION ON
 SERVICE CONDUCTOR SIZE. YOU SHOW #1.
 PLEASE SEE 310-15 AND 310-16
  
 2)NOTE: MISSING A/C DISC`S PER 440-11
  
 3)NOTE:PLEASE LIST REQ`D BATH(S) CIRCUIT
 (S) PER 210-11-C-3 ON PANEL SCHEDULE..
  
 4)NOTE: PLEASE SEE LOAD CALCUALTIONS.
 CALCS DO NOT CORRELATE WITH MECHANICAL
 PLANS OR ELECTRICAL A/C PLAN LAYOUT.
 215-5.
  
 5)NOTE: PLEASE SEE SQ FT BEING ADDED ON
 BLDG PLANS. THIS ALSO DOES NOT CORRELATE
 WITH LOAD CALCULATIONS FOR SQ FT/GEN LT.
 PER 220
  
 6)NOTE: PLEASE SEE SMALL APPLIANCE
 CALCSSHOWN. YOU SHOW 4.5 KW AND ONLY
 TWO CIRCUITS. PLEASE CLARIFY.
  
 7)NOTE: PLEASE SEE RISER DIAGRAM AND
 CORRELATE WITH ELECTRICAL PLAN. WHERE
 IS THE SECOND PANEL GOING? PLEASE
 SUBMIT CLARIFICATION ON SERVICE.
 NOTE ON ELECTRICAL PLAN SAYS CIRCUITS
 ARE BEING FED TO EXISTING 200 AMP
 FUSE PANEL.? RISER DIAGRAM DOES NOT
 SHOW THIS.
  
 8)NOTE: MISSING WP GFI REC FOR A/C CU`S.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-16 Cont ID  
Sent By jleech Date 2000-09-16 Time 07:43 Rev Time 0.33
Received By jleech Date 2000-09-16 Time 07:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-13 Cont ID  
Sent By tlarge Date 2000-09-13 Time 20:03 Rev Time 0.30
Received By tlarge Date 2000-09-13 Time 19:56 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 SUBMIT REVISED SANITARY RISER PRIOR TO
 PLBG.INSPECTION.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-11-17 Cont ID  
Sent By rmcdouga Date 2000-11-17 Time 15:53 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO
  
 1)PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE WITH SPECIFIC ANCHORS BEING
 USED FOR STORM PANELS PRIOR TO
 INSTALLATION.
  
 2)DOUBLE OUTSWING GLAZED METAL DOORS ARE
 TO BE INSTALLED WITHOUT SIDELITES AS PER
 PRODUCT APPROVALS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-10-27 Cont ID  
Sent By rmcdouga Date 2000-10-27 Time 10:35 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM BEACH
 CO.,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITTED TO CITY OF WPB BUILDING DEPT.
 BEFORE A PERMIT CAN BE ISSUED.
  
 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR EXTERIOR
 FRENCH DOORS W/SIDELITES AS SHOWN ON
 PLANS.
  
 3)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN INDICATING WINDOWS AND DOORS THAT
 WILL RECEIVE STORM PANELS.
  
 4)ARCHITECT TO DATE AND PROVIDE LEGIBLE
 NAME AND REGISTRATION NUMBER.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-28 Cont ID  
Sent By rmcdouga Date 2000-09-28 Time 08:07 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITTED TO CITY OF WPB BLDG. DEPT.
  
 2)PROVIDE ATTIC ACCESS PER 97 SBC 2309.6
  
 3)BATHROOM WINDOWS MUST COMPLY WITH
 SAFETY GLAZING REQUIREMENTS PER 97 SBC
 2405.2.
  
 4)PLEASE SPECIFY TRUSS ANCHORS FOR TRUSS
 -ES AT REAR WITH 705# UPLIFT.
  
 5)NOTE 5 ON SHEET S-1 IS INCORRECT. THE
 WINDLOAD FOR PALM BEACH CO. IN ASCE7-95
 IS 140 MPH,NOT 110 MPH. PLEASE RECHECK
 YOUR CALCULATIONS.
  
 6)IF STRUCTURE IS NOT DESIGNED BY AN
 ARCHITECT OR ENGINEER,THE DESIGN MUST
 CONFORM TO SSTD 10-97,WHICH IS THE
 PRESCRIPTIVE STANDARD ADOPTED BY THE
 CITY OF WPB. CITY AMENDMENTS TO 97 SBC.
 SEC.104.2.3. PLEASE REVIEW PLANS FOR
 COMPLIANCE WITH SSTD 10-97 AND DO NOT
 SITE OTHER DESIGN CRITERIA ON PLANS.
 IF DESIGNED BY ARCHITECT OR ENGINEER
 PLANS MUST BE SIGNED,SEALED AND DATED.
  
 7)PROVIDE EAST AND WEST ELEVATIONS
 SHOWING ALL OPENINGS IN NEW AND EXISTING
 STRUCTURE,SO THAT THE PERCENTAGE OF
 ALLOWABLE OPENINGS CAN BE DETERMINED PER
 97 SBC TABLE 600.
  
 8)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR FRENCH
 DOORS WITH SIDELITES AS SHOWN ON REAR
 ELEVATION ON PLANS. IMPACT GLASS OR
 OTHER IMPACT PROTECTION WILL BE REQUIRED
  
 9)PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE,WITH SPECIFIC ANCHORS TO BE
 USED,FOR STORM PANELS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-09 Cont ID  
Sent By gjoyce Date 2000-09-09 Time 07:50 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***