Plan Review Details - Permit 00081607
Plan Review Stops For Permit 00081607
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-10-04 Cont ID  
Sent By mcarsill Date 2000-10-04 Time 15:27 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO CUT SHEETS PROVIDED FOR FIRE
 SPRINKLER HEADS PLANNED FOR USE.
 PLEASE PROVIDE CUT SHEETS FOR FIRE
 SPRINKLER HEADS THAT WILL BE USED
 INSIDE THE BUILDING.
 2) ENTIRE FIRE SPRINKLER AND STANDPIPE
 SYSTEM IS SUBJECT TO FIRE RESCUE
 APPROVAL.
 3) SOFFITS ARE NOT TO INTERFERE WITH
 ANY FIRE SPRINKLER HEAD DISCHARGE
 PATTERNS.
 4) FIRE DEPARTMENT CONNECTION TO BE
 NO MORE THAN 150 FEET TO A FIRE
 HYDRANT.
 APPROVED PROVISO:

Review Stop FS  
Rev No 2 Status P Date 2000-10-04 Cont ID  
Sent By lsmith Date 2000-10-04 Time 16:02 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER MEC 10/04/00

Review Stop FS  
Rev No 1 Status F Date 2000-08-31 Cont ID  
Sent By mcarsill Date 2000-08-31 Time 15:55 Rev Time 0.00
Received By mcarsill Date 2000-08-31 Time 15:55 Sent To  
Notes
2001-01-08 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL AND MECHANICAL ROOMS. ALL
 VERTICAL SHAFTS ARE ALSO TO BE
 PROTECTED BY FIRE SPRINKLER HEADS.
 2) STANDPIPE SYSTEM TO COMPLY WITH
 NFPA 14.
 3) THE RETAIL AREA IS TO BE SPRINKLER
 PROTECTED PRIOR TO THE BUILDING
 RECEIVING A CERTIFICATE OF OCCUPANCY.
 4) THE OUTSIDE HOSE VALVE STANDPIPE
 NOT SHOWN ON PLANS.
 5) NO CUT SHEETS PROVIDED FOR FIRE
 SPRINKLER HEADS PLANNED FOR USE.
 6) PLEASE PROVIDE FIRE SPRINKLER
 PROTECTION IN KITCHENS OF UNITS D1,
 F, A, AND D2.
 7) ON AUGUST 31, 2000, WRITER SPOKE TO
 DAVID THOMAS OF WIGINTON FIRE SPRINKLER
 COMPANY. HE ADVISED HE WOULD FAX
 THIS OFFICE A DIAGRAM INDICATING THE
 LOCATION OF THE OUTSIDE HOSE VALVE.