Plan Review Details - Permit 00081600
Plan Review Stops For Permit 00081600
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-09-27 Cont ID  
Sent By lmartine Date 2000-09-27 Time 16:16 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-09-01 Cont ID  
Sent By mcarsill Date 2000-09-01 Time 15:28 Rev Time 0.00
Received By mcarsill Date 2000-09-01 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-09-11 Cont ID  
Sent By ndenmark Date 2000-09-11 Time 16:33 Rev Time 0.25
Received By ndenmark Date 2000-09-11 Time 16:33 Sent To  
Notes
2001-01-08 00:00:00NO MECH PLANS TO REVIEW SUBMIT PLANS
 AT TIME OF MECH PERMIT APPLICATION
 PRIOR TO ANY MECHANICAL WORK BEING DONE

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-10 Cont ID  
Sent By tlarge Date 2000-10-10 Time 12:37 Rev Time 0.65
Received By tlarge Date 2000-10-10 Time 12:37 Sent To  
Notes
2001-01-08 00:00:00REPLACE PLUMBING FIXTURES ONLY.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-09-03 Cont ID  
Sent By tlarge Date 2000-09-03 Time 07:25 Rev Time 0.75
Received By tlarge Date 2000-09-03 Time 07:02 Sent To  
Notes
2001-01-08 00:00:001)CLEARLY SHOW DIMENSIONS(LXW) OF ALL
 H.C.STALLS.COMPLY WFACBC FIG.30(B).
  
  
 2)SHT.A-2-HANDICAP STALLS SHOWN AS 32"
 WIDE.COMPLY W/FACBC FIG.30.(SEE ROOMS
 227/230 & 132/133.
  
 3)SHOW CLEAR FLOOR SPACE FOR HANDICAP
 URINAL.COMPLY W/FACBC SEC.4.18.3.
  
 4)SUBMIT SANITARY AND WATER RISER
 DIAGRAMS FOR ANY CHANGES TO THE PIPING
 SYSTEM.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.