| Plan Review Stops For Permit 00081560 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-29 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-29 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) SMOKE DETECTORS TO BE INSTALLED A | | | MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 2) WHEN ACTIVATED, THE FIRE ALARM SYSTEM | | | IS TO BE AUDIBLE THROUGHOUT. | | | 3) IF BUILDING IS FIRE SPRINKLER | | | PROTECTED, THEN FLOW AND TAMPER | | | SWITCHES ARE TO BE SUPERVISED AND BE | | | MONITORED. |
|
|
|