Plan Review Details - Permit 00081558
Plan Review Stops For Permit 00081558
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-28 Cont ID  
Sent By drunnels Date 2000-09-28 Time 13:07 Rev Time 1.00
Received By drunnels Date 2000-09-28 Time 13:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-25 Cont ID  
Sent By drunnels Date 2000-09-25 Time 07:45 Rev Time 1.00
Received By lmartine Date 2000-09-25 Time 07:45 Sent To  
Notes
2001-01-08 00:00:001.PROVIDE LIFE SAFETY PLAN
 2.EXIT DOOR MUST COMPLY WITH FLORIDA
 HANDICAP CODE.
 3.PROVIDE UL# FOR DEMIZING WALLS.
 4.EXPLAIN EXISTING STAIRS LEADING UP?
 5.SHOW HOWREMOVING EXISTING CEILING
 WILL AFFECT THE ENERGY ENVELOPE OF
 THE BUILDING. FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING CONST.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 11:20 Sent To  
Notes
2001-01-08 00:00:00***************** PROVISO ************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH ALL
 NEW BRACNH CIRCUIT #`S ON PLANS.
 PLEASE CORRELATE WITH PANEL SCHEDULE
 THAT ALSO NEEDS TO BE SUBMITTED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-09-28 Cont ID  
Sent By mcarsill Date 2000-09-28 Time 13:12 Rev Time 0.00
Received By mcarsill Date 2000-09-28 Time 13:12 Sent To  
Notes
***NONE***