| Plan Review Stops For Permit 00081547 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-01 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-01 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) FIRE ALARM SYSTEM IS TO FUNCTION | | | CLASS WHEN A DEVICE IS REMOVED FROM | | | SERVICE. | | | 2) SYSTEM TO BE MONITORED BY A LICENSED | | | UL LISTED CENTRAL STATION APPROVED BY | | | FIRE RESCUE. | | | 3) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | | TO BE AUDIBLE THROUGHOUT. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-29 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-29 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO CUT SHEETS ON FIRE ALARM DEVICES | | | PLANNED FOR USE. | | | 2) FIRE PUMP RUN AND FIRE PUMP FAIL IS | | | TO BE MONITORED BY FIRE ALARM SYSTEM. | | | 3) REMOTE ANNUNCIATOR IS NEEDED FOR | | | GARAGE. |
|
|
|