Plan Review Details - Permit 00081302
| Plan Review Stops For Permit 00081302 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-11 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-11 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-12 |
Time |
19:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-12 |
Time |
19:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL | | | EQUIPMENT BEING INSTALLED. MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER | | | 110-9. 215-5 THIS IS REQ`D ON ALL PLANS. | | | | | | 2)NOTE: PLEASE SHOW EQUIPMENT GRND REQ`D | | | BETWEEN MAIN DISC AND PANEL. 250-122 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3ON PANEL | | | SCHEDULE. 215-5 | | | | | | 4)NOTE: PLEASE SHOW MAIN DISCONNECT ON | | | HOUSE PLANS WITH METER.NOTE. 110-26 | | | | | | 5)NOTE: MISSING GFI/REC PER 210-52E | | | | | | 6)NOTE: PLEASE SEE 210-70 FOR EGRESS | | | LIGHTING FROM GARAGE. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMAITON | | | FOR REVIEW. ALSO PLEASE PLACE ELECTRICAL | | | RISER/CALCULATIONS/PANEL SCHEDULE ON | | | E-SHEET WITH ELECTRICAL FLOOR PLANS. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-01 |
Time |
11:03 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-03-01 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2001-03-01 00:00:00 | REVISION - ADD ONE R/A DROP. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-08-26 |
Time |
13:43 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-08-26 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-11-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-17 |
Time |
11:00 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2000-11-17 |
Time |
10:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-08-26 |
Time |
13:44 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-08-26 |
Time |
13:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-10-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-10-17 |
Time |
13:46 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | 1)PROVIDE PRODUCT APPROVAL FORM FOR | | | GARAGE SIDE ENTRY DOOR WITH ORIGINAL | | | SIGNATURE,DATE AND EMBOSSED SEAL OF | | | ENGINEER CERTIFYING PRODUCT AND DESIGN | | | PROFESSIONAL OF RECORD. ALSO,PROVIDE | | | JOB SITE LOCATION ON FORM. | | | | | | 2)THE LETTER FROM THE ENGINEER CERTIFY- | | | ING THE ENTRY DOOR FOR CODE COMPLIANCE | | | MUST BE ACCOMPANIED BY A WET SIGNED, | | | DATED AND SEALED LETTER FROM THE DESIGN | | | PROFESSIONAL OF RECORD STATING THAT HE | | | HAS REVIEWED AND APPROVED THE ENGINEER'S | | | REPORT. | | | | | | 3)THE ENGINEERING REPORT FOR THE BUTT | | | GLASS ASSEMBLIES INCORRECTLY SITES ASCE | | | 7-93 AS THE DESIGN CRITERIA USED TO | | | DETERMINE THE WIND LOADS. THE ACCEPTED | | | DESIGN STANDARDS FOR THE CITY OF WPB ARE | | | THE 1997 SBC SEC.1606 OR ASCE 7-95. | | | PLEASE CORRECT. ALSO, THE REPORT MUST BE | | | WET SIGNED, DATED AND SEALED BY THE | | | DESIGNER OF RECORD UPON HIS REVIEW AND | | | ACCEPTANCE. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-09-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-09-25 |
Time |
08:37 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED PER TONY MARCELLO 9-25-00 RLM | | | | | | DENIED | | | | | | | | | 1)DESIGN CERTIFICATE SHEET INDICATES A | | | M.R.H. OF 15',THE ACTUAL M.R.H.IS 18'. | | | THE BASIC V.P. IS DIFFERENT (T16062A) | | | PLEASE RECHECK. | | | | | | 2)PLEASE SUPPLY AN EXTRA ENERGY FACE | | | PAGE. | | | | | | 3)THE BUTT GLASS IN THE LIVING ROOM MUST | | | COMPLY WITH SEC.2406.2. | | | | | | 4)PRODUCT APPROVAL IS REQUIRED FOR THE | | | ENTRY DOOR. | | | | | | 5)PRODUCT APPROVAL IS REQUIRED FOR THE | | | GARAGE DOOR, THE GARAGE SIDE ENTRY AND | | | THE FOYER ENTRY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-08-24 |
Time |
17:26 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|