Plan Review Details - Permit 00081302
Plan Review Stops For Permit 00081302
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-11 Cont ID  
Sent By dpalmer Date 2000-10-11 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2000-10-11 Time 09:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 19:10 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL
 EQUIPMENT BEING INSTALLED. MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER
 110-9. 215-5 THIS IS REQ`D ON ALL PLANS.
  
 2)NOTE: PLEASE SHOW EQUIPMENT GRND REQ`D
 BETWEEN MAIN DISC AND PANEL. 250-122
  
 3)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3ON PANEL
 SCHEDULE. 215-5
  
 4)NOTE: PLEASE SHOW MAIN DISCONNECT ON
 HOUSE PLANS WITH METER.NOTE. 110-26
  
 5)NOTE: MISSING GFI/REC PER 210-52E
  
 6)NOTE: PLEASE SEE 210-70 FOR EGRESS
 LIGHTING FROM GARAGE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW. ALSO PLEASE PLACE ELECTRICAL
 RISER/CALCULATIONS/PANEL SCHEDULE ON
 E-SHEET WITH ELECTRICAL FLOOR PLANS.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-01 Cont ID  
Sent By pkrauss Date 2001-03-01 Time 11:03 Rev Time 0.30
Received By pkrauss Date 2001-03-01 Time 10:58 Sent To  
Notes
2001-03-01 00:00:00REVISION - ADD ONE R/A DROP.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-26 Cont ID  
Sent By jleech Date 2000-08-26 Time 13:43 Rev Time 0.50
Received By jleech Date 2000-08-26 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-17 Cont ID  
Sent By jleech Date 2000-11-17 Time 11:00 Rev Time 0.25
Received By jleech Date 2000-11-17 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-26 Cont ID  
Sent By jleech Date 2000-08-26 Time 13:44 Rev Time 0.50
Received By jleech Date 2000-08-26 Time 13:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-10-17 Cont ID  
Sent By rmcdouga Date 2000-10-17 Time 13:46 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 1)PROVIDE PRODUCT APPROVAL FORM FOR
 GARAGE SIDE ENTRY DOOR WITH ORIGINAL
 SIGNATURE,DATE AND EMBOSSED SEAL OF
 ENGINEER CERTIFYING PRODUCT AND DESIGN
 PROFESSIONAL OF RECORD. ALSO,PROVIDE
 JOB SITE LOCATION ON FORM.
  
 2)THE LETTER FROM THE ENGINEER CERTIFY-
 ING THE ENTRY DOOR FOR CODE COMPLIANCE
 MUST BE ACCOMPANIED BY A WET SIGNED,
 DATED AND SEALED LETTER FROM THE DESIGN
 PROFESSIONAL OF RECORD STATING THAT HE
 HAS REVIEWED AND APPROVED THE ENGINEER'S
 REPORT.
  
 3)THE ENGINEERING REPORT FOR THE BUTT
 GLASS ASSEMBLIES INCORRECTLY SITES ASCE
 7-93 AS THE DESIGN CRITERIA USED TO
 DETERMINE THE WIND LOADS. THE ACCEPTED
 DESIGN STANDARDS FOR THE CITY OF WPB ARE
 THE 1997 SBC SEC.1606 OR ASCE 7-95.
 PLEASE CORRECT. ALSO, THE REPORT MUST BE
 WET SIGNED, DATED AND SEALED BY THE
 DESIGNER OF RECORD UPON HIS REVIEW AND
 ACCEPTANCE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-25 Cont ID  
Sent By rmcdouga Date 2000-09-25 Time 08:37 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED PER TONY MARCELLO 9-25-00 RLM
  
 DENIED
  
  
 1)DESIGN CERTIFICATE SHEET INDICATES A
 M.R.H. OF 15',THE ACTUAL M.R.H.IS 18'.
 THE BASIC V.P. IS DIFFERENT (T16062A)
 PLEASE RECHECK.
  
 2)PLEASE SUPPLY AN EXTRA ENERGY FACE
 PAGE.
  
 3)THE BUTT GLASS IN THE LIVING ROOM MUST
 COMPLY WITH SEC.2406.2.
  
 4)PRODUCT APPROVAL IS REQUIRED FOR THE
 ENTRY DOOR.
  
 5)PRODUCT APPROVAL IS REQUIRED FOR THE
 GARAGE DOOR, THE GARAGE SIDE ENTRY AND
 THE FOYER ENTRY.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By gjoyce Date 2000-08-24 Time 17:26 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***