| Plan Review Stops For Permit 00081286 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-10-24 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-24 |
Time |
14:00 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-24 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FS PERMIT #00100934 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-10-02 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-02 |
Time |
12:31 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-02 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PRIOR COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-06 |
Time |
15:43 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-06 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.SUBMIT FLORIDA ENERGY SHEETS SIGNED & | | | SEALED BY ENG. AND SIGNED BY OWNER/AGENT | | | 2.SUBMIT PRODUCT APPROVAL FOR IMPACT | | | RESISTANT GLAZING AND DOORS FOR STORE- | | | FRONTS. METRO DADE OR SBCCI | | | 3.SUBMIT FIRE SPRINKLER PLANS AND PERMIT | | | APPLICATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-28 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-28 |
Time |
18:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-09-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-11 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-11 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% (LIGHTING ETC) | | | | | | 2)NOTE: PLEASE SHOW LOAD FOR SHOW WINDOW | | | RECEPTS PER 220-3-7 A OR B. | | | | | | 3)NOTE: PLEASE SHOW TRACK LIGHTING | | | LOAD CALCULATIONS PER 220-12-B | | | | | | 4)NOTE: PLEASE SEE E-4 AND SEE LOCAL | | | AMENDMENTS FOR COLOR CODING FOR 480/277V | | | SYSTEMS. | | | | | | 5)NOTE: PLEASE PROVIDE ALL MIN AIC RAT- | | | -INGS FOR ALL EQUIPMENT,MAINS/PANELS. | | | PER 110-9/215-5. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-28 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-28 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH SPRINKLER DRAWINGS INCLUDED IN | | | PLANS. | | | 2) FIRE SPRINKLER INSTALLATION TO BE | | | DONE UNDER SEPARATE PLAN AND PERMIT. | | | 3) MONITORS TO NOT BLOCK REQUIRED | | | FIRE SPRINKLER FLOOR COVERAGE. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-06 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-06 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. | | | SHOULD READ NFPA 101, 1985 LIFE SAFETY | | | CODE INSTEAD OF NFPA 101, 1991 LIFE | | | SAFETY CODE. | | | 2) PROVIDE FIRE ALARM DRAWINGS FOR FIRE | | | ALARM EQUIPMENT SHOWN ON PLANS. A | | | SEPARATE PLAN AND PERMIT REQUIRED. CUT | | | SHEETS REQUIRED ON ALL DEVICES PLANNED | | | FOR USE. | | | 3) FINISH SCHEDULE DOES NOT INDICATE | | | FLAME SPREAD RATING FOR WALLS AND | | | CEILINGS. INTERIOR FINISH IN MERCANTILE | | | OCCUPANCIES SHALL BE CLASS A OR B. | | | 4) PROVIDE FIRE SPRINKLER SHOP DRAWINGS | | | WITH PERMIT FOR FIRE SPRINKLER SYSTEM | | | INSTALLATION. | | | 5) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS EXIST: | | | STOCKROOM DOOR FROM SALES AREA CANNOT | | | BE SUBJECT TO LOCKING, NOT MORE THAN | | | 50 PERCENT OF EXIT ACCESS CAN BE THROUGH | | | STOCKROOM, A 44" AISLE IS TO BE PROVIDED | | | AND MAINTAINED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-27 |
Time |
15:54 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-09-27 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PRIOR COMMENTS ADDRESSED BY REVISION | | | DATED 9/26/00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-07 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-07 |
Time |
09:42 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-09-07 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89 | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3. SECONDARY DRAIN LINE SHALL NOT TIE | | | INTO PRIMARY DRAIN LINE. RUN SEPARATELY | | | AND TERMINATE IN A CONSPICOUS LOCATION | | | OR USE FLOAT SWITCH PER 1997 SMC 304.8 | | | 4. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED/TIED TO BUILDING FIRE ALARM | | | PER NFPA 90A 4-4.4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-28 |
Time |
11:29 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-09-28 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | INSTANTANEOUS HEATER SHALL NOT INFRINGE | | | ON THE CLEAR FLOOR SPACE FOR THE LAV. | | | PER FIG.31 FACBC. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-06 |
Time |
19:00 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-09-06 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)ACCESSIBLE TOILET ROOMS LOCATED IN | | | STORAGE AREAS SHALL BE INDELIBLY POSTED | | | FOR THE INTENDED USE,BE ON AN ACCESSIBLE | | | ROUTE AND AVAILABLE TO PATRONS WITHOUT | | | RESTRTICTION DURING NORMAL OPERATING | | | HOURS.THE ACCESSIBLE ROUTE SHALL BE | | | CLEARLY DEFINED ON THE PLANS. | | | FLA.ACCESSIBILITY CODE SECS.4.1,4.2,4.3. | | | STANDARD PLUMBING CODE SEC.407.2.2. | | | | | | 2)INDICATE COMPLIANCE W/COMMENT #1 ON | | | THE PLANS. | | | | | | 3)INSTANT WATER HEATERS SHALL NOT | | | INFRINGE UPON THE REQUIRED CLEARANCES | | | PER FACBC SEC.4.19,FIGS.31 & 32. | | | PLUMBING PLANS EXAMINER. | | | | | | 4)ONLY 2 FIXTURES PERMITTED ON 1/2"C.W. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.607.7 | | | | | | 5)LAVS SHALL CONNECT TO THE STACK W/O | | | OFFSETS.SPC SEC.1001.5,1001.9. | | | | | | 6)FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC SEC.409.4.1.1. | | | | | | 7)FLOORS AND WALLS SHALL BE NONABSORBENT | | | TO A HEIGHT OF 4'PER SBC SEC.1204.2. | | | | | | 8)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | 4.1.3(10)(A)PROVISIONS SHALL BE MADE FOR | | | PEOPLE WHO HAVE TROUBLE BENDING OR | | | STOOPING. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|