Plan Review Details - Permit 00081286
Plan Review Stops For Permit 00081286
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-10-24 Cont ID  
Sent By drunnels Date 2000-10-24 Time 14:00 Rev Time 1.00
Received By drunnels Date 2000-10-24 Time 13:59 Sent To  
Notes
2001-01-08 00:00:00FS PERMIT #00100934

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-10-02 Cont ID  
Sent By drunnels Date 2000-10-02 Time 12:31 Rev Time 1.00
Received By drunnels Date 2000-10-02 Time 12:31 Sent To  
Notes
2001-01-08 00:00:00PRIOR COMMENTS NOT ADDRESSED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-06 Cont ID  
Sent By drunnels Date 2000-09-06 Time 15:43 Rev Time 1.00
Received By drunnels Date 2000-09-06 Time 15:43 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT FLORIDA ENERGY SHEETS SIGNED &
 SEALED BY ENG. AND SIGNED BY OWNER/AGENT
 2.SUBMIT PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING AND DOORS FOR STORE-
 FRONTS. METRO DADE OR SBCCI
 3.SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-28 Cont ID  
Sent By dpalmer Date 2000-09-28 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2000-09-28 Time 18:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-11 Cont ID  
Sent By dpalmer Date 2000-09-11 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2000-09-11 Time 13:03 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% (LIGHTING ETC)
  
 2)NOTE: PLEASE SHOW LOAD FOR SHOW WINDOW
 RECEPTS PER 220-3-7 A OR B.
  
 3)NOTE: PLEASE SHOW TRACK LIGHTING
 LOAD CALCULATIONS PER 220-12-B
  
 4)NOTE: PLEASE SEE E-4 AND SEE LOCAL
 AMENDMENTS FOR COLOR CODING FOR 480/277V
 SYSTEMS.
  
 5)NOTE: PLEASE PROVIDE ALL MIN AIC RAT-
 -INGS FOR ALL EQUIPMENT,MAINS/PANELS.
 PER 110-9/215-5.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-28 Cont ID  
Sent By mcarsill Date 2000-09-28 Time 08:26 Rev Time 0.00
Received By mcarsill Date 2000-09-28 Time 08:26 Sent To  
Notes
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH SPRINKLER DRAWINGS INCLUDED IN
 PLANS.
 2) FIRE SPRINKLER INSTALLATION TO BE
 DONE UNDER SEPARATE PLAN AND PERMIT.
 3) MONITORS TO NOT BLOCK REQUIRED
 FIRE SPRINKLER FLOOR COVERAGE.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-06 Cont ID  
Sent By mcarsill Date 2000-09-06 Time 11:32 Rev Time 0.00
Received By mcarsill Date 2000-09-06 Time 11:31 Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ NFPA 101, 1985 LIFE SAFETY
 CODE INSTEAD OF NFPA 101, 1991 LIFE
 SAFETY CODE.
 2) PROVIDE FIRE ALARM DRAWINGS FOR FIRE
 ALARM EQUIPMENT SHOWN ON PLANS. A
 SEPARATE PLAN AND PERMIT REQUIRED. CUT
 SHEETS REQUIRED ON ALL DEVICES PLANNED
 FOR USE.
 3) FINISH SCHEDULE DOES NOT INDICATE
 FLAME SPREAD RATING FOR WALLS AND
 CEILINGS. INTERIOR FINISH IN MERCANTILE
 OCCUPANCIES SHALL BE CLASS A OR B.
 4) PROVIDE FIRE SPRINKLER SHOP DRAWINGS
 WITH PERMIT FOR FIRE SPRINKLER SYSTEM
 INSTALLATION.
 5) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST:
 STOCKROOM DOOR FROM SALES AREA CANNOT
 BE SUBJECT TO LOCKING, NOT MORE THAN
 50 PERCENT OF EXIT ACCESS CAN BE THROUGH
 STOCKROOM, A 44" AISLE IS TO BE PROVIDED
 AND MAINTAINED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-27 Cont ID  
Sent By ndenmark Date 2000-09-27 Time 15:54 Rev Time 0.33
Received By ndenmark Date 2000-09-27 Time 15:54 Sent To  
Notes
2001-01-08 00:00:00PRIOR COMMENTS ADDRESSED BY REVISION
 DATED 9/26/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-09-07 Cont ID  
Sent By ndenmark Date 2000-09-07 Time 09:42 Rev Time 0.50
Received By ndenmark Date 2000-09-07 Time 09:48 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1. PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3. SECONDARY DRAIN LINE SHALL NOT TIE
 INTO PRIMARY DRAIN LINE. RUN SEPARATELY
 AND TERMINATE IN A CONSPICOUS LOCATION
 OR USE FLOAT SWITCH PER 1997 SMC 304.8
 4. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED/TIED TO BUILDING FIRE ALARM
 PER NFPA 90A 4-4.4

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-28 Cont ID  
Sent By tlarge Date 2000-09-28 Time 11:29 Rev Time 0.65
Received By tlarge Date 2000-09-28 Time 11:29 Sent To  
Notes
2001-01-08 00:00:00INSTANTANEOUS HEATER SHALL NOT INFRINGE
 ON THE CLEAR FLOOR SPACE FOR THE LAV.
 PER FIG.31 FACBC.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-09-06 Cont ID  
Sent By tlarge Date 2000-09-06 Time 19:00 Rev Time 0.65
Received By tlarge Date 2000-09-06 Time 18:52 Sent To  
Notes
2001-01-08 00:00:001)ACCESSIBLE TOILET ROOMS LOCATED IN
 STORAGE AREAS SHALL BE INDELIBLY POSTED
 FOR THE INTENDED USE,BE ON AN ACCESSIBLE
 ROUTE AND AVAILABLE TO PATRONS WITHOUT
 RESTRTICTION DURING NORMAL OPERATING
 HOURS.THE ACCESSIBLE ROUTE SHALL BE
 CLEARLY DEFINED ON THE PLANS.
 FLA.ACCESSIBILITY CODE SECS.4.1,4.2,4.3.
 STANDARD PLUMBING CODE SEC.407.2.2.
  
 2)INDICATE COMPLIANCE W/COMMENT #1 ON
 THE PLANS.
  
 3)INSTANT WATER HEATERS SHALL NOT
 INFRINGE UPON THE REQUIRED CLEARANCES
 PER FACBC SEC.4.19,FIGS.31 & 32.
 PLUMBING PLANS EXAMINER.
  
 4)ONLY 2 FIXTURES PERMITTED ON 1/2"C.W.
 COUNTYWIDE AMENDMENTS TO SPC SEC.607.7
  
 5)LAVS SHALL CONNECT TO THE STACK W/O
 OFFSETS.SPC SEC.1001.5,1001.9.
  
 6)FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 7)FLOORS AND WALLS SHALL BE NONABSORBENT
 TO A HEIGHT OF 4'PER SBC SEC.1204.2.
  
 8)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 4.1.3(10)(A)PROVISIONS SHALL BE MADE FOR
 PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.