Plan Review Details - Permit 00081234
Plan Review Stops For Permit 00081234
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-11 Cont ID  
Sent By dpalmer Date 2000-10-11 Time 18:02 Rev Time 0.00
Received By dpalmer Date 2000-10-11 Time 18:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-14 Cont ID  
Sent By dpalmer Date 2000-09-14 Time 18:24 Rev Time 0.00
Received By dpalmer Date 2000-09-14 Time 18:24 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT COMPLETED PLANS.
 NO RISER DIAGRAM/LOAD CALCULATIONS/
 PANEL SCHEDULES?????????
  
 2)NOTE: MISSING SMOKE DETECTORS FOR
 MEDIA/PLAY ROOM.ROOMS WITH BATHS AND OR
 CLOSETS ARE ADAPTABLE TO SLEEPING ROOMS
 AND THEREFORE REQ` SMOKE DETECTORS PER
 NFPA-72.
  
 3)NOTE; MISSING WP GFI FOR A/C CU ON
 MASTER BATH SIDE OF HOUSE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372
  
 **PLEASE SEE MISSING OUTLETS PER 210-52
 BEDROOM #4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-06 Cont ID  
Sent By jleech Date 2000-09-06 Time 18:49 Rev Time 0.33
Received By jleech Date 2000-09-06 Time 18:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 06:44 Rev Time 0.30
Received By tlarge Date 2000-08-29 Time 06:40 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 1)VEG.SINK NOT SHOWN ON SANITARY RISER.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 2)MAX.OF 4 FIXTURE UNITS PERMITTED ON 2"
 WET VENT.SEE M.B.STACK.
  
 3)SHOWER IN M.B.SHALL CONNECT TO HORIZ.
 DRAIN DOWNSTREAM OF W.C.PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.
  
 4)SUBMIT REVISED SIGNED,DATED AND SEALED
 SANITARY RISER PRIOR TO PLUMBING INSP.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-10-18 Cont ID  
Sent By rmcdouga Date 2000-10-18 Time 15:28 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)PROVIDE ENGINEERING FOR BUTT GLASS
 WINDOW IN BREAKFAST ROOM PER SECTION
 2406.2 1997 SBC. ENGINEER'S ORIGINAL
 SIGNATURE,DATE AND RAISED SEAL IS
 REQUIRED AS WELL AS DESIGNER OF RECORD'S
 ON LETTER STATING THAT HE HAS REVIEWED
 AND APPROVED THE APPLICATION.
  
 2)PROVIDE PRODUCT APPROVALS FOR (2)
 LARGE FIXED GLASS WINDOWS IN LIVING ROOM
 THE PRODUCT APPROVALS SUBMITTED FOR
 FIXED GLASS WINDOWS ARE FOR WINDOWS WITH
 MAXIMUM DIMENSIONS OF 120"W X 60"H.
  
 3)PROVIDE PRODUCT APPROVALS FOR ROOFING
 MATERIALS UNDER A SEPARATE PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-27 Cont ID  
Sent By lsmith Date 2000-09-27 Time 13:22 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TM SEE NOTES ON PLANS

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By gjoyce Date 2000-08-24 Time 17:19 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***