| Plan Review Stops For Permit 00081203 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-04 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-04 |
Time |
14:29 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-04 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-06 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-27 |
Time |
19:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-27 |
Time |
19:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************UNSAT **************** | | | | | | | | | 1)NOTE: PLEASE SEE FIRST REVIEW NOTES. | | | NOT ALL NOTES WERE ADDRESSED. | | | 110-9/215-5 | | | | | | | | | PLEASE SUBMIT FOR REVIEW.ONCE AGAIN IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-29 |
Time |
21:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-29 |
Time |
21:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS SHOWING | | | ALL BRANCH CIRCUIT #`S ON PLANS. | | | PLEASE CORRELATE #`S WITH PANEL SCHEDULE | | | TO BE SUBMITTED WITH PLANS. 215-5 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL MAINS AND PANELS. EQUIPMENT MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9 | | | | | | 3)NOTE : PLEASE SHOW GROUNDING ELECTRODE | | | ATTACHMENTS PER 250 OF THE NEC. | | | | | | 4)NOTE :PLEASE SHOW ALL CONTINUOUS | | | LOADS AT 125%. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-25 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-25 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-10-03 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-03 |
Time |
13:38 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-10-03 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-30 |
Time |
14:54 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-09-01 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | INSUFFICIENT MECHANICAL INFORMATION FOR | | | REVIEW. PROVIDE INFORMATION ON DIFFUSERS | | | OUTSIDE AIR PER ASHRAE 62-89, AIR | | | BALANCE SHOWING COMPLIANCE W/ SMC 501.2, | | | VENTILATION AND BATH EXHAUST REQUIRED TO | | | COMPLY WITH ASHRAE 62-89 AND STANDARD | | | CODES | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR W/ | | | NOTIFICATION BY BLDG FIRE ALARM OR HORN | | | AND STROBE REQUIRED PER NFPA 90A 4-4.4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-30 |
Time |
09:09 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2000-11-30 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-26 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-26 |
Time |
15:04 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-09-26 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3(10)(A). | | | CALL 561 -659-8096 EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-27 |
Time |
08:42 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-27 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)A DRINKING FOUNTAIN IS REQD. PER SPC | | | TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | 2)SUBMIT A WATER ISOMETRIC FOR REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 3)CLEANOUTS ARE REQD.AND SHALL COMPLY W/ | | | SPC SEC.710.2. | | | | | | 4)A MAIN VENT IS REQD.PER SPC SEC.904.3. | | | | | | 5)CLARIFY FLOOR DRAIN.IF IT'S FOR THE | | | TOILET ROOM,INSTALL ONE IN EACH TOILET | | | ROOM.SPC 409.4.1.1. | | | | | | 6)SHOW WHEELCHAIR TURNING SPACE IN | | | TOILET ROOMS.FACBC SEC.4.2.3. | | | | | | 7)SHOW LOCATION OF FUTURE SINK ON PLANS. | | | IF LOCATED IN A BREAK/LOUNGE AREA THE | | | SINK SHALL COMPLY W/FACBC SEC.4.24.1- | | | 4.24.7. | | | | | | 8)WALLS IN TOILET ROOMS SHALL BE | | | NONABSORBENT TO A HEIGHT OF 4' PER SBC | | | SEC.1204.2(PLANS NOTE PAINT-WHAT TYPE?) | | | | | | 9)WATER CLOSETS NOT PERMITTED ON WET | | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.911.1.1. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|