Plan Review Details - Permit 00081203
Plan Review Stops For Permit 00081203
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-10-04 Cont ID  
Sent By drunnels Date 2000-10-04 Time 14:29 Rev Time 1.00
Received By drunnels Date 2000-10-04 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-06 Cont ID  
Sent By dpalmer Date 2000-10-06 Time 10:56 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-27 Cont ID  
Sent By dpalmer Date 2000-09-27 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2000-09-27 Time 19:53 Sent To  
Notes
2001-01-08 00:00:00*****************UNSAT ****************
  
  
 1)NOTE: PLEASE SEE FIRST REVIEW NOTES.
 NOT ALL NOTES WERE ADDRESSED.
 110-9/215-5
  
  
 PLEASE SUBMIT FOR REVIEW.ONCE AGAIN IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-29 Cont ID  
Sent By dpalmer Date 2000-08-29 Time 21:30 Rev Time 0.00
Received By dpalmer Date 2000-08-29 Time 21:30 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING
 ALL BRANCH CIRCUIT #`S ON PLANS.
 PLEASE CORRELATE #`S WITH PANEL SCHEDULE
 TO BE SUBMITTED WITH PLANS. 215-5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL MAINS AND PANELS. EQUIPMENT MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9
  
 3)NOTE : PLEASE SHOW GROUNDING ELECTRODE
 ATTACHMENTS PER 250 OF THE NEC.
  
 4)NOTE :PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-25 Cont ID  
Sent By mcarsill Date 2000-08-25 Time 09:25 Rev Time 0.00
Received By mcarsill Date 2000-08-25 Time 09:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-03 Cont ID  
Sent By ndenmark Date 2000-10-03 Time 13:38 Rev Time 0.25
Received By ndenmark Date 2000-10-03 Time 13:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-09-01 Cont ID  
Sent By ndenmark Date 2000-08-30 Time 14:54 Rev Time 0.33
Received By ndenmark Date 2000-09-01 Time 10:09 Sent To  
Notes
2001-01-08 00:00:00INSUFFICIENT MECHANICAL INFORMATION FOR
 REVIEW. PROVIDE INFORMATION ON DIFFUSERS
 OUTSIDE AIR PER ASHRAE 62-89, AIR
 BALANCE SHOWING COMPLIANCE W/ SMC 501.2,
 VENTILATION AND BATH EXHAUST REQUIRED TO
 COMPLY WITH ASHRAE 62-89 AND STANDARD
 CODES
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR W/
 NOTIFICATION BY BLDG FIRE ALARM OR HORN
 AND STROBE REQUIRED PER NFPA 90A 4-4.4

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-11-30 Cont ID  
Sent By jleech Date 2000-11-30 Time 09:09 Rev Time 0.25
Received By jleech Date 2000-11-30 Time 09:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-26 Cont ID  
Sent By tlarge Date 2000-09-26 Time 15:04 Rev Time 0.50
Received By tlarge Date 2000-09-26 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).
 CALL 561 -659-8096 EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-27 Cont ID  
Sent By tlarge Date 2000-08-27 Time 08:42 Rev Time 0.50
Received By tlarge Date 2000-08-27 Time 08:36 Sent To  
Notes
2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD. PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 2)SUBMIT A WATER ISOMETRIC FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 3)CLEANOUTS ARE REQD.AND SHALL COMPLY W/
 SPC SEC.710.2.
  
 4)A MAIN VENT IS REQD.PER SPC SEC.904.3.
  
 5)CLARIFY FLOOR DRAIN.IF IT'S FOR THE
 TOILET ROOM,INSTALL ONE IN EACH TOILET
 ROOM.SPC 409.4.1.1.
  
 6)SHOW WHEELCHAIR TURNING SPACE IN
 TOILET ROOMS.FACBC SEC.4.2.3.
  
 7)SHOW LOCATION OF FUTURE SINK ON PLANS.
 IF LOCATED IN A BREAK/LOUNGE AREA THE
 SINK SHALL COMPLY W/FACBC SEC.4.24.1-
 4.24.7.
  
 8)WALLS IN TOILET ROOMS SHALL BE
 NONABSORBENT TO A HEIGHT OF 4' PER SBC
 SEC.1204.2(PLANS NOTE PAINT-WHAT TYPE?)
  
 9)WATER CLOSETS NOT PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.