Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-03-22 Cont ID  
Sent By hpiskura Date 2001-03-22 Time 14:41 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-03-22 00:00:00REVISION #4 DATED 2/5/01
  
 A TEST REPORT OR FIRE DESIGN REFERENCE
 IS REQUIRED FOR THE SPRINKLER METHOD
 SHOWN ON SHEET A5.01 ON THE WINDOW FOR
 A TWO HOUR RATING.SEE SBC 705.1.2
  
 SHEET A6.01 AND OTHERS HAVE A NOTE
 SAYING SPRAYED FIRE PROTECTION TO BE
 APPLIED AT TENANT BUILD OUT.NO
 OCCUPANCY OF ANY PORTION OF THE
 BUILDING CAN BE ACCOMPLISHED UNLESS THE
 SHELL MEETS THE REQUIREMENTS OF FIRE
 RESISTANCE FOR TYPE II CONSTRUCTION.
 ALSO THE SPRINKLER SYSTEM MUST BE
 FUNCTIONAL REGARDLESS OF A TENANT
 OCCUPYING THE SPACE OR NOT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-11-27 Cont ID  
Sent By hpiskura Date 2000-11-27 Time 10:06 Rev Time 0.00
Received By hpiskura Date 2000-11-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-11-01 Cont ID  
Sent By hpiskura Date 2000-11-01 Time 15:16 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:002ND CKLST LETTER W/APPLICATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-04 Cont ID  
Sent By hpiskura Date 2000-10-04 Time 09:03 Rev Time 0.00
Received By hpiskura Date 2000-09-29 Time 09:45 Sent To  
Notes
2001-01-08 00:00:00LETTER W/ APP

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-04-30 Cont ID  
Sent By dpalmer Date 2001-04-30 Time 17:04 Rev Time 0.00
Received By dpalmer Date 2001-04-30 Time 17:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-03-13 Cont ID  
Sent By dpalmer Date 2001-03-13 Time 06:22 Rev Time 0.00
Received By dpalmer Date 2001-03-13 Time 06:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 10:46 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 10:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-11-13 Cont ID  
Sent By dpalmer Date 2000-11-13 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2000-11-13 Time 08:12 Sent To  
Notes
2001-01-08 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST RE-
 -VIEW. PLEASE NOTE THAT THE INLINE
 DISC FOR GENERATOR IS NOT SHOWN. THIS
 DISCONNECT WILL BE REQ`D AT ATS LOCATION
 AND GROUPED WITH MAINS. 230-72.
 FIRE DEPT. WILL NOT BE GOING TO THE ROOF
 TO SHUT POWER OFF AT GENERATOR IF THERE
 IS A FIRE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS FOR
 THE ABOVE PLEASE CALL. ALSO PLEASE SEE
 SHEET E3.4 AND E5.1 THEY APPEAR TO BE
 COPIES OF THE SIGNATURE? PER 61G15-23-
 -.002 MUST BE OF ORIGINAL SIGNATURE.
  
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-11-09 Cont ID  
Sent By dpalmer Date 2000-11-09 Time 17:03 Rev Time 0.00
Received By dpalmer Date 2000-11-09 Time 17:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-15 Cont ID  
Sent By dpalmer Date 2000-09-15 Time 06:46 Rev Time 0.00
Received By dpalmer Date 2000-09-15 Time 06:46 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE 230-70 AND 230-72
 FOR REQ`MENTS OF AN INLINE DISC FROM
 GENERATOR TO ATS.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 AND INCLUDE 125% FOR ALL CONTINUOUS
 LOADS. PER 215-3
  
 3)NOTE: PLEASE SHOW WIRE SIZES ON ONE
 LINE DIAGRAM FOR GENERATOR CONDUCTORS.
 PIPE SIZE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-04-26 Cont ID  
Sent By mcarsill Date 2001-04-26 Time 10:59 Rev Time 0.00
Received By mcarsill Date 2001-04-26 Time 10:58 Sent To  
Notes
2001-04-26 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FUEL INSTALLATION.
 2) THE ENTIRE FIRE SPRINKLER SYSTEM AND
 FIRE ALARM SYSTEM WITH REQUIRED
 SUPERVISION ARE TO BE COMPLETE AND
 APPROVED BY FIRE RESCUE PRIOR TO ANY
 OCCUPANCY.
 3) EMERGENCY LIGHTING, EXIT SIGNAGE,
 STAIRS AND RATED FIRE DOORS ARE ALSO
 TO BE FUNCTIONAL PRIOR TO OCCUPANCY.
 4) A KNOX-BOX RAPID ENTRY KEY BOX WILL
 BE REQUIRED FOR THE BUILDING.
 5) REQUIRED FIREPROOFING IS TO BE
 INSPECTED BY CONSTRUCTION SERVICES AND
 APPROVED PRIOR TO ANY OCCUPANCY.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-03-14 Cont ID  
Sent By mcarsill Date 2001-03-14 Time 09:41 Rev Time 0.00
Received By mcarsill Date 2001-03-14 Time 09:41 Sent To  
Notes
2001-03-14 00:00:001) THE MECHANICAL CHASE TO BE PROPERLY
 FIRE RATED.
 2) NEW FABRIC AWNING SHOWN ON WEST
 ELEVATION DRAWING TO BE FIRE RETARDANT.
 3) PLEASE SHOW TYPE AND NUMBER OF PIPE
 SUPPORTS FOR FUEL PIPING. PLEASE DISPLAY
 ROOF SUPPORTS FOR PIPING. PLEASE PROVIDE
 PRODUCT APPROVLS FOR DAY TANK AND
 GENERATOR. PLEASE PROVIDE MORE DETAILS
 ON AUTOMATIC REMOTE FILLING SYSTEM.
 ADDITIONAL MECHANICAL PERMITS REQUIRED
 FOR FUEL SYSTEM INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-11-21 Cont ID  
Sent By mcarsill Date 2000-11-21 Time 15:42 Rev Time 0.00
Received By mcarsill Date 2000-11-21 Time 15:42 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE MORE DETAILS ON FUEL
 STORAGE TANK BELOW GENERATOR. PLEASE
 PROVIDE CUT SHEETS ON GENERATOR AND
 STORAGE TANK. PLEASE PROVIDE MORE
 INFORMATION ON PHOENIX FILL PORT AND
 ASSOCIATED PIPING AND WELDED OUTLETS.
 PLEASE PROVIDE ANY AND ALL UL LISTINGS
 OR FM APPROVALS FOR THESE DEVICES.
 THE PLANS INDICATE TWO GENERATOR ROOMS.
 HOW MANY GENERATORS AND HOW MUCH FUEL
 IS ANTICIPATED. IS THE FILL PIPE
 INSIDE OR OUTSIDE THE BUILDING. IF
 OUTSIDE, IS IT PROTECTED AGAINST
 CORROSION. IS THE PIPES LABELED. THIS
 ARRANGEMENT IF APPROVED MUST MEET ALL
 REQUIREMENTS OF NFPA 30, THE FLAMMABLE
 AND COMBUSTIBLE LIQUID CODE. WHAT IS THE
 RATING OF THE GENERATOR ROOM WALLS.
 A SEPARATE PLANS AND PERMIT REQUIRED.
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-11-09 Cont ID  
Sent By mcarsill Date 2000-11-08 Time 16:20 Rev Time 0.00
Received By mcarsill Date 2000-11-08 Time 16:19 Sent To  
Notes
2001-01-08 00:00:001) BUILDING ADDRESS DOES NOT APPEAR
 ON ELEVATION DRAWINGS. BUILDING ADDRESS
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 2) FIRE ALARM NOTES INDICATE CLASS B,
 STYLE C CIRCUITS. ONLY CLASS A, STYLE
 D CIRCUITS ARE PERMITTED.
 3) WHERE IS THE FIRE DEPARTMENT
 SPRINKLER AND STANDPIPE CONNECTION
 LOCATED. ENTIRE BUILDING IS TO BE
 COMPLETELY FIRE SPRINKLER PROTECTED.
 THIS INCLUDES ALL SERVICE ROOMS,
 ELECTRICAL ROOMS, AND MECHANICAL ROOMS.
 ALL VERTICAL SHAFTS ARE TO BE PROTECTED.
 THE ONLY EXCEPTION IS THE FPL VAULT
 ROOM. FURTHER CLARIFY THE PRE-ACTION
 SYSTEM LOCATIONS. WHAT APPROVALS HAVE
 BEEN RECEIVED TO INSTALL THESE SYSTEMS
 IN THE BUILDING.
 4) ELEVATOR(S) TO COMPLY WITH ANSI A17.1
 AND 4A-47.
 5) COMPLETE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR THE FIRE ALARM SYSTEM
 EQUIPMENT SHOWN ON PLANS. THE FIRE ALARM
 SYSTEM IS TO BE ADDRESSABLE OR CLASS A.
 CUT SHEETS, WIRING DIAGRAMS, FLOOR
 PLANS ARE TO BE SUBMITTED.
 6) EMERGENCY GENERATOR ROOM IS TO BE
 AT LEAST TWO HOUR FIRE SEPARATED.
 OPENINGS ARE TO BE PROPERLY PROTECTED.
 7) NO FIRE STANDPIPE SYSTEM INFORMATION
 INCLUDED WITH PLANS.
 8) TENANT SEPARATION REQUIREMENTS ARE TO
 MEET BUILDING CODE REQUIREMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-24 Cont ID  
Sent By mcarsill Date 2000-08-24 Time 11:36 Rev Time 0.00
Received By mcarsill Date 2000-08-24 Time 11:36 Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS.
 2) NO INFORMATION ON FIRE ALARM
 EQUIPMENT PRESENTLY IN OR PLANNED FOR
 THE BUILDING.
 3) FUTURE CORRIDORS ARE TO BE AT LEAST
 ONE HOUR FIRE RATED.
 4) NO INFORMATION ON STANDPIPE SYSTEM
 PRESENTLY IN OR PLANNED FOR THE BUILDING
 5) PLEASE PROVIDE MORE DETAILS ON TWO
 HOUR FIRE RATED FLOOD SPRINKLER SYSTEM
 ON PAGE A5.01
 6) EMERGENCY GENERATOR ROOM TO BE AT
 LEAST TWO HOUR FIRE RATED AND MEET THE
 REQUIREMENTS OF NFPA 30, SINCE THE
 GENERATOR WILL HAVE SUB BASE TANK.
 7) EMERGENCY LIGHTS AND EXIT SIGNS OF
 PROPER AMOUNT ARE TO PRESENT IN ALL
 MEANS OF EGRESS.
 8) CODE ANALYSIS BOX INCORRECT. IF
 SAFETY 1994 MEANS THE LIFE SAFETY CODE,
 IT SHOULD READ SAFETY 1985.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2001-05-21 Cont ID  
Sent By pkrauss Date 2001-05-21 Time 11:15 Rev Time 0.25
Received By pkrauss Date 2001-05-21 Time 11:15 Sent To  
Notes
2001-05-21 00:00:00NOTES ON MECH 01031029

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-05-11 Cont ID  
Sent By pkrauss Date 2001-05-11 Time 15:14 Rev Time 0.30
Received By pkrauss Date 2001-05-11 Time 15:14 Sent To  
Notes
2001-05-11 00:00:00******************PROVISO***************
  
 DRAWING M7.2, C.U. STAND SHALL BE A
 MINIMUM OF 18" FROM ROOF SURFACE TO
 BOTTOM OF THE C.U. SUPPORT RAIL.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE
 CONTACTPATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-03-20 Cont ID  
Sent By pkrauss Date 2001-03-20 Time 10:21 Rev Time 0.40
Received By pkrauss Date 2001-03-19 Time 16:22 Sent To  
Notes
2001-03-20 00:00:00******************PROVISO***************
  
 MECHANICAL DRAWING M7.1, DETAIL 1-M2.1
 FOR THE HVAC EQUIPMENT ROOF CURB DETAIL
 INDICATES 18" MINIMUM - IF THIS CURB IS
 FOR A ROOF TOP PACKAGE UNIT IN WHICH
 THE UNIT FITS OVER THE CURB IT IS NOT
 REQUIRED TO BE 18".THE 18" MINIMUM
 CLEARENCE IS FOR STANDS AS INDICATED ON
 DRAWING M7.2, IN WHICH THE CONDENSERS
 SIT ON TOP AND THE ROOF IS CONTINUOUS
 UNDERNEATH, THEREFORE THE 18" CLEARENCE
 IS REQUIRED.
 REFERENCE - AMENDED 1997 SMC 304.2.5.
  
 AS PER 1997 SMC 609.1.1, THERE SHALL BE
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM.
  
 DRAWING M6.1 AIR BALANCE SCHEDULE WAS
 NOT ADJUSTED TO REFLECT THE ADDITION OF
 AHU-4.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-11-30 Cont ID  
Sent By ndenmark Date 2000-11-30 Time 12:44 Rev Time 0.50
Received By ndenmark Date 2000-11-30 Time 12:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-11-14 Cont ID  
Sent By ndenmark Date 2000-11-14 Time 08:10 Rev Time 0.50
Received By ndenmark Date 2000-11-14 Time 08:10 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1.REVISION SHOWS ROOF STAND CLEARANCE TO
 BE PER SFBCD. WE DO NOT USE THIS CODE IN
 WEST PALM BEACH. THE LOCAL AMENDMENT
 REQUIRES MINIMUM 18" CLEARANCE BETWEEN
 ROOF SURFACE AND BOTTOM OF EQUIPMENT
 SUPPORT BEAM FOR ROOF ACCESS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-09-06 Cont ID  
Sent By ndenmark Date 2000-09-06 Time 11:12 Rev Time 1.00
Received By ndenmark Date 2000-09-06 Time 11:12 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1.PROVIDE SHAFT DETAIL FOR DUCTS PENETR-
 ATING FROM ROOF TO 1ST FL. SHOWING COMP-
 LIANCE WITH 1997 SMC 610.4
 2.FIRE DAMPERS LOCATION AND INSTALLATION
 DETAILS TO BE SHOWN ON PLAN BY DESIGNER
 PER 1997 SMC 610.6
 3.FAN SHUT DOWN FOR UNITS WITH LESS THAN
 2000 CFM BUT SERVING AREAS USED FOR
 EGRESS SHALL HAVE FAN SHUT DOWN BY DUCT
 SMOKE DETECTOR PER 1997 SMC 406.2
 4. FAN SHUT DOWN TO BE TIED TO BUILDING
 FIRE ALARM SYSTEM PER NFPA 90A 4-4.4
 5. MODEL COUNTYWIDE AMENDMENTS AS ADOPTE
 D BY ORDINANCE REQUIRES EQUIPMENT MOUNT-
 ED ON ROOF TO HAVE MIN. 18" CLEARANCE
 FOR ACCESS TO ROOF MATERIALS UNDERNIETH
 FROM ROOF SURFACE TO BOTTOM OF MAIN
 SUPPORT STRUCTURE OF STAND

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-05-10 Cont ID  
Sent By jleech Date 2001-05-10 Time 08:55 Rev Time 1.50
Received By jleech Date 2001-05-10 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-04-19 Cont ID  
Sent By kstevens Date 2001-04-19 Time 16:44 Rev Time 0.75
Received By kstevens Date 2001-04-19 Time 16:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-03-22 Cont ID  
Sent By jleech Date 2001-03-22 Time 17:29 Rev Time 1.50
Received By jleech Date 2001-03-22 Time 17:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-11-28 Cont ID  
Sent By jleech Date 2000-11-28 Time 14:55 Rev Time 2.50
Received By jleech Date 2000-11-28 Time 14:55 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 1.ADD TO NOTE 2 ON PAGE A9.1 [PAINT OR
 TILE OVER MOISTURE RESISTANT GYPSUM
 BOARD TO BE USED IN ALL RESTROOMS.]
  
 2.DELETE WATER HEATER MOUNTING DETAIL.
  
 PLUMING PLAN REVIEW BY,
 JOHN LEECH
 659-80960 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-28 Cont ID  
Sent By tlarge Date 2000-10-28 Time 06:38 Rev Time 1.50
Received By tlarge Date 2000-10-28 Time 05:43 Sent To  
Notes
2001-01-08 00:00:001)FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO A HEIGHT OF 4'.IF
 WALLS WILL BE PAINTED INDICATE TYPE OF
 PAINT ON THE FINISH SCHEDULE.SBC 1204.2.
  
 2)DRINKING FOUNTAINS SHALL COMPLY W/
 FACBC SEC.4.1.3.(10)(B).(IF MORE THAN
 ONE ON A FLOOR,50% SHALL COMPLY W/SEC.
 4.15.)
  
 3)CLEARLY SHOW INSIDE DIMENSIONS OF ALL
 ACCESSIBLE TOILET STALLS.IF LAV.IS
 INSTALLED ADJACENT TO THE W.C.THE MIN.
 WIDTH SHALL BE 83"PER FACBC SEC.4.17.3.
  
 4)SHT.A4.01-MIN.CLEAR FLOOR SPACE UNDER
 H.C.LAV.SHALL BE 29",NOT 27"AS SHOWN.
 FACBC SEC.4.19.2.
  
 5)SHT.A4.01-PAPER TOWEL DISPENSER,SOAP
 DISPENSER,TOILET PAPER HOLDER AND MIRROR
 SHALL BE INSTALLED ACCORDING TO FACBC
 REQS.FOR MIN.MOUNTING HEIGHTS.
  
 6)DELETE MOUNTING DETAIL FOR EWH FROM
 SHT.PO.1.
  
 7)PLUMBING PLANS STILL REFER TO "EXPRESS
 PREACTION"SYSTEM.SUBMIT DETAILS AND INFO
 FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 8)FLOOR DRAIN SHALL BE INSTALLED IN LIEU
 OF HUB DRAIN.SPC 807.1.2.,807.1.3..
  
 CALL IF YOU HAVE QUESTIONS.561-659-8096
 EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-27 Cont ID  
Sent By tlarge Date 2000-08-27 Time 11:53 Rev Time 2.00
Received By tlarge Date 2000-08-27 Time 10:29 Sent To  
Notes
2001-01-08 00:00:001)ADDITIONAL PLUMBING FIXTURES ARE REQD.
 BASED ON SQ.FEET OF HABITABLE FLOOR
 SPACE AND OCCUPANT LOAD PER SPC TABLE
 407.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.(RE:W.C.'S,LAVS,D.F.'S)
  
 2)FLOORS AND WALLS SHALL BE NONABSORBENT
 TO A HEIGHT OF 4'PER SBC SEC.1204.2.
  
 3)DRINKING FOUNTAINS SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(B).
  
 4)CLEARLY SHOW DIMENSIONS (LXW)OF THE
 H.C.TOILET STALLS.COMPLY W/FACBC SEC.
 4.17.3.(MIN.WIDTH SHALL BE 83")
  
 5)SHOW MOUNTING HEIGHT/DIMENSIONS OF ALL
 HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/FACBC 1997 ED.
  
 6)SHOW LOCATION OF H.C.URINAL ON PLAN
 AND DETAIL 30"X48"CLEAR FLOOR SPACE
 PER FACBC SEC.4.18.
  
 7)SHOW WHEELCHAIR TURNING SPACE IN
 RESTROOMS PER FACBC SEC.4.2.3.
  
 8)DIELECTRIC NIPPLES/COUPLINGS TO BE
 USED ON DISSIMILAR METALS.UNIONS NOT
 PERMITTED.309.3
  
 9)WATER HEATER SHALL BE READILY ACCESS-
 IBLE PER SPC SEC.501.7.PROVIDE FIXED
 LADDER & PLATFORM OR RELOCATE EWH TO
 FLOOR.
  
 10)SUBMIT INFO ON "EXPRESS PREACTION"
 SYSTEM.CONDENSATE CANNOT DRAIN TO
 SANITARY SYSTEM.SMC SEC.304.8.3.
  
 11)SUBMIT PAN DRAIN AND P&T RISER FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 *****NOTE:THIS PLAN REVIEW DOESN'T
 INCLUDE THE FUEL OIL PIPING SYSTEM.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.