| Plan Review Stops For Permit 00081182 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-03-22 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-22 00:00:00 | REVISION #4 DATED 2/5/01 | | | | | | A TEST REPORT OR FIRE DESIGN REFERENCE | | | IS REQUIRED FOR THE SPRINKLER METHOD | | | SHOWN ON SHEET A5.01 ON THE WINDOW FOR | | | A TWO HOUR RATING.SEE SBC 705.1.2 | | | | | | SHEET A6.01 AND OTHERS HAVE A NOTE | | | SAYING SPRAYED FIRE PROTECTION TO BE | | | APPLIED AT TENANT BUILD OUT.NO | | | OCCUPANCY OF ANY PORTION OF THE | | | BUILDING CAN BE ACCOMPLISHED UNLESS THE | | | SHELL MEETS THE REQUIREMENTS OF FIRE | | | RESISTANCE FOR TYPE II CONSTRUCTION. | | | ALSO THE SPRINKLER SYSTEM MUST BE | | | FUNCTIONAL REGARDLESS OF A TENANT | | | OCCUPYING THE SPACE OR NOT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-11-27 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-11-27 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2000-11-27 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-11-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-11-01 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 2ND CKLST LETTER W/APPLICATION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-04 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-10-04 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2000-09-29 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER W/ APP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2001-04-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-30 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-30 |
Time |
17:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-13 |
Time |
06:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-13 |
Time |
06:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-07 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-07 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2000-11-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-13 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-13 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST RE- | | | -VIEW. PLEASE NOTE THAT THE INLINE | | | DISC FOR GENERATOR IS NOT SHOWN. THIS | | | DISCONNECT WILL BE REQ`D AT ATS LOCATION | | | AND GROUPED WITH MAINS. 230-72. | | | FIRE DEPT. WILL NOT BE GOING TO THE ROOF | | | TO SHUT POWER OFF AT GENERATOR IF THERE | | | IS A FIRE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS FOR | | | THE ABOVE PLEASE CALL. ALSO PLEASE SEE | | | SHEET E3.4 AND E5.1 THEY APPEAR TO BE | | | COPIES OF THE SIGNATURE? PER 61G15-23- | | | -.002 MUST BE OF ORIGINAL SIGNATURE. | | | | | | | | | DEWEY PALMER | | | ELECTRICALPLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-11-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-09 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-09 |
Time |
17:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-09-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-15 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-15 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE 230-70 AND 230-72 | | | FOR REQ`MENTS OF AN INLINE DISC FROM | | | GENERATOR TO ATS. | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | AND INCLUDE 125% FOR ALL CONTINUOUS | | | LOADS. PER 215-3 | | | | | | 3)NOTE: PLEASE SHOW WIRE SIZES ON ONE | | | LINE DIAGRAM FOR GENERATOR CONDUCTORS. | | | PIPE SIZE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-26 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-26 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2001-04-26 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FUEL INSTALLATION. | | | 2) THE ENTIRE FIRE SPRINKLER SYSTEM AND | | | FIRE ALARM SYSTEM WITH REQUIRED | | | SUPERVISION ARE TO BE COMPLETE AND | | | APPROVED BY FIRE RESCUE PRIOR TO ANY | | | OCCUPANCY. | | | 3) EMERGENCY LIGHTING, EXIT SIGNAGE, | | | STAIRS AND RATED FIRE DOORS ARE ALSO | | | TO BE FUNCTIONAL PRIOR TO OCCUPANCY. | | | 4) A KNOX-BOX RAPID ENTRY KEY BOX WILL | | | BE REQUIRED FOR THE BUILDING. | | | 5) REQUIRED FIREPROOFING IS TO BE | | | INSPECTED BY CONSTRUCTION SERVICES AND | | | APPROVED PRIOR TO ANY OCCUPANCY. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-03-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-14 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-14 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2001-03-14 00:00:00 | 1) THE MECHANICAL CHASE TO BE PROPERLY | | | FIRE RATED. | | | 2) NEW FABRIC AWNING SHOWN ON WEST | | | ELEVATION DRAWING TO BE FIRE RETARDANT. | | | 3) PLEASE SHOW TYPE AND NUMBER OF PIPE | | | SUPPORTS FOR FUEL PIPING. PLEASE DISPLAY | | | ROOF SUPPORTS FOR PIPING. PLEASE PROVIDE | | | PRODUCT APPROVLS FOR DAY TANK AND | | | GENERATOR. PLEASE PROVIDE MORE DETAILS | | | ON AUTOMATIC REMOTE FILLING SYSTEM. | | | ADDITIONAL MECHANICAL PERMITS REQUIRED | | | FOR FUEL SYSTEM INSTALLATION. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-21 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-21 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLEASE PROVIDE MORE DETAILS ON FUEL | | | STORAGE TANK BELOW GENERATOR. PLEASE | | | PROVIDE CUT SHEETS ON GENERATOR AND | | | STORAGE TANK. PLEASE PROVIDE MORE | | | INFORMATION ON PHOENIX FILL PORT AND | | | ASSOCIATED PIPING AND WELDED OUTLETS. | | | PLEASE PROVIDE ANY AND ALL UL LISTINGS | | | OR FM APPROVALS FOR THESE DEVICES. | | | THE PLANS INDICATE TWO GENERATOR ROOMS. | | | HOW MANY GENERATORS AND HOW MUCH FUEL | | | IS ANTICIPATED. IS THE FILL PIPE | | | INSIDE OR OUTSIDE THE BUILDING. IF | | | OUTSIDE, IS IT PROTECTED AGAINST | | | CORROSION. IS THE PIPES LABELED. THIS | | | ARRANGEMENT IF APPROVED MUST MEET ALL | | | REQUIREMENTS OF NFPA 30, THE FLAMMABLE | | | AND COMBUSTIBLE LIQUID CODE. WHAT IS THE | | | RATING OF THE GENERATOR ROOM WALLS. | | | A SEPARATE PLANS AND PERMIT REQUIRED. | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-11-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-08 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-08 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS DOES NOT APPEAR | | | ON ELEVATION DRAWINGS. BUILDING ADDRESS | | | TO COMPLY WITH CITY CODE REQUIREMENTS. | | | 2) FIRE ALARM NOTES INDICATE CLASS B, | | | STYLE C CIRCUITS. ONLY CLASS A, STYLE | | | D CIRCUITS ARE PERMITTED. | | | 3) WHERE IS THE FIRE DEPARTMENT | | | SPRINKLER AND STANDPIPE CONNECTION | | | LOCATED. ENTIRE BUILDING IS TO BE | | | COMPLETELY FIRE SPRINKLER PROTECTED. | | | THIS INCLUDES ALL SERVICE ROOMS, | | | ELECTRICAL ROOMS, AND MECHANICAL ROOMS. | | | ALL VERTICAL SHAFTS ARE TO BE PROTECTED. | | | THE ONLY EXCEPTION IS THE FPL VAULT | | | ROOM. FURTHER CLARIFY THE PRE-ACTION | | | SYSTEM LOCATIONS. WHAT APPROVALS HAVE | | | BEEN RECEIVED TO INSTALL THESE SYSTEMS | | | IN THE BUILDING. | | | 4) ELEVATOR(S) TO COMPLY WITH ANSI A17.1 | | | AND 4A-47. | | | 5) COMPLETE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR THE FIRE ALARM SYSTEM | | | EQUIPMENT SHOWN ON PLANS. THE FIRE ALARM | | | SYSTEM IS TO BE ADDRESSABLE OR CLASS A. | | | CUT SHEETS, WIRING DIAGRAMS, FLOOR | | | PLANS ARE TO BE SUBMITTED. | | | 6) EMERGENCY GENERATOR ROOM IS TO BE | | | AT LEAST TWO HOUR FIRE SEPARATED. | | | OPENINGS ARE TO BE PROPERLY PROTECTED. | | | 7) NO FIRE STANDPIPE SYSTEM INFORMATION | | | INCLUDED WITH PLANS. | | | 8) TENANT SEPARATION REQUIREMENTS ARE TO | | | MEET BUILDING CODE REQUIREMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-24 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-24 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. | | | 2) NO INFORMATION ON FIRE ALARM | | | EQUIPMENT PRESENTLY IN OR PLANNED FOR | | | THE BUILDING. | | | 3) FUTURE CORRIDORS ARE TO BE AT LEAST | | | ONE HOUR FIRE RATED. | | | 4) NO INFORMATION ON STANDPIPE SYSTEM | | | PRESENTLY IN OR PLANNED FOR THE BUILDING | | | 5) PLEASE PROVIDE MORE DETAILS ON TWO | | | HOUR FIRE RATED FLOOD SPRINKLER SYSTEM | | | ON PAGE A5.01 | | | 6) EMERGENCY GENERATOR ROOM TO BE AT | | | LEAST TWO HOUR FIRE RATED AND MEET THE | | | REQUIREMENTS OF NFPA 30, SINCE THE | | | GENERATOR WILL HAVE SUB BASE TANK. | | | 7) EMERGENCY LIGHTS AND EXIT SIGNS OF | | | PROPER AMOUNT ARE TO PRESENT IN ALL | | | MEANS OF EGRESS. | | | 8) CODE ANALYSIS BOX INCORRECT. IF | | | SAFETY 1994 MEANS THE LIFE SAFETY CODE, | | | IT SHOULD READ SAFETY 1985. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2001-05-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-21 |
Time |
11:15 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-05-21 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2001-05-21 00:00:00 | NOTES ON MECH 01031029 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2001-05-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-11 |
Time |
15:14 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-05-11 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2001-05-11 00:00:00 | ******************PROVISO*************** | | | | | | DRAWING M7.2, C.U. STAND SHALL BE A | | | MINIMUM OF 18" FROM ROOF SURFACE TO | | | BOTTOM OF THE C.U. SUPPORT RAIL. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE | | | CONTACTPATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-20 |
Time |
10:21 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-03-19 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2001-03-20 00:00:00 | ******************PROVISO*************** | | | | | | MECHANICAL DRAWING M7.1, DETAIL 1-M2.1 | | | FOR THE HVAC EQUIPMENT ROOF CURB DETAIL | | | INDICATES 18" MINIMUM - IF THIS CURB IS | | | FOR A ROOF TOP PACKAGE UNIT IN WHICH | | | THE UNIT FITS OVER THE CURB IT IS NOT | | | REQUIRED TO BE 18".THE 18" MINIMUM | | | CLEARENCE IS FOR STANDS AS INDICATED ON | | | DRAWING M7.2, IN WHICH THE CONDENSERS | | | SIT ON TOP AND THE ROOF IS CONTINUOUS | | | UNDERNEATH, THEREFORE THE 18" CLEARENCE | | | IS REQUIRED. | | | REFERENCE - AMENDED 1997 SMC 304.2.5. | | | | | | AS PER 1997 SMC 609.1.1, THERE SHALL BE | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | | AIR PLENUM. | | | | | | DRAWING M6.1 AIR BALANCE SCHEDULE WAS | | | NOT ADJUSTED TO REFLECT THE ADDITION OF | | | AHU-4. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-30 |
Time |
12:44 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-11-30 |
Time |
12:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-11-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-14 |
Time |
08:10 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-11-14 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1.REVISION SHOWS ROOF STAND CLEARANCE TO | | | BE PER SFBCD. WE DO NOT USE THIS CODE IN | | | WEST PALM BEACH. THE LOCAL AMENDMENT | | | REQUIRES MINIMUM 18" CLEARANCE BETWEEN | | | ROOF SURFACE AND BOTTOM OF EQUIPMENT | | | SUPPORT BEAM FOR ROOF ACCESS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-06 |
Time |
11:12 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-09-06 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1.PROVIDE SHAFT DETAIL FOR DUCTS PENETR- | | | ATING FROM ROOF TO 1ST FL. SHOWING COMP- | | | LIANCE WITH 1997 SMC 610.4 | | | 2.FIRE DAMPERS LOCATION AND INSTALLATION | | | DETAILS TO BE SHOWN ON PLAN BY DESIGNER | | | PER 1997 SMC 610.6 | | | 3.FAN SHUT DOWN FOR UNITS WITH LESS THAN | | | 2000 CFM BUT SERVING AREAS USED FOR | | | EGRESS SHALL HAVE FAN SHUT DOWN BY DUCT | | | SMOKE DETECTOR PER 1997 SMC 406.2 | | | 4. FAN SHUT DOWN TO BE TIED TO BUILDING | | | FIRE ALARM SYSTEM PER NFPA 90A 4-4.4 | | | 5. MODEL COUNTYWIDE AMENDMENTS AS ADOPTE | | | D BY ORDINANCE REQUIRES EQUIPMENT MOUNT- | | | ED ON ROOF TO HAVE MIN. 18" CLEARANCE | | | FOR ACCESS TO ROOF MATERIALS UNDERNIETH | | | FROM ROOF SURFACE TO BOTTOM OF MAIN | | | SUPPORT STRUCTURE OF STAND |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-05-10 |
Time |
08:55 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-05-10 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-04-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-04-19 |
Time |
16:44 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2001-04-19 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-03-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-22 |
Time |
17:29 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-03-22 |
Time |
17:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-28 |
Time |
14:55 |
Rev Time |
2.50 |
| Received By |
jleech |
Date |
2000-11-28 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO; | | | 1.ADD TO NOTE 2 ON PAGE A9.1 [PAINT OR | | | TILE OVER MOISTURE RESISTANT GYPSUM | | | BOARD TO BE USED IN ALL RESTROOMS.] | | | | | | 2.DELETE WATER HEATER MOUNTING DETAIL. | | | | | | PLUMING PLAN REVIEW BY, | | | JOHN LEECH | | | 659-80960 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-10-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-28 |
Time |
06:38 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-10-28 |
Time |
05:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)FLOORS AND WALLS IN TOILET ROOMS SHALL | | | BE NONABSORBENT TO A HEIGHT OF 4'.IF | | | WALLS WILL BE PAINTED INDICATE TYPE OF | | | PAINT ON THE FINISH SCHEDULE.SBC 1204.2. | | | | | | 2)DRINKING FOUNTAINS SHALL COMPLY W/ | | | FACBC SEC.4.1.3.(10)(B).(IF MORE THAN | | | ONE ON A FLOOR,50% SHALL COMPLY W/SEC. | | | 4.15.) | | | | | | 3)CLEARLY SHOW INSIDE DIMENSIONS OF ALL | | | ACCESSIBLE TOILET STALLS.IF LAV.IS | | | INSTALLED ADJACENT TO THE W.C.THE MIN. | | | WIDTH SHALL BE 83"PER FACBC SEC.4.17.3. | | | | | | 4)SHT.A4.01-MIN.CLEAR FLOOR SPACE UNDER | | | H.C.LAV.SHALL BE 29",NOT 27"AS SHOWN. | | | FACBC SEC.4.19.2. | | | | | | 5)SHT.A4.01-PAPER TOWEL DISPENSER,SOAP | | | DISPENSER,TOILET PAPER HOLDER AND MIRROR | | | SHALL BE INSTALLED ACCORDING TO FACBC | | | REQS.FOR MIN.MOUNTING HEIGHTS. | | | | | | 6)DELETE MOUNTING DETAIL FOR EWH FROM | | | SHT.PO.1. | | | | | | 7)PLUMBING PLANS STILL REFER TO "EXPRESS | | | PREACTION"SYSTEM.SUBMIT DETAILS AND INFO | | | FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | 8)FLOOR DRAIN SHALL BE INSTALLED IN LIEU | | | OF HUB DRAIN.SPC 807.1.2.,807.1.3.. | | | | | | CALL IF YOU HAVE QUESTIONS.561-659-8096 | | | EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-27 |
Time |
11:53 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-08-27 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)ADDITIONAL PLUMBING FIXTURES ARE REQD. | | | BASED ON SQ.FEET OF HABITABLE FLOOR | | | SPACE AND OCCUPANT LOAD PER SPC TABLE | | | 407.SEE SPC SEC.407.1.3.FOR ALLOWED | | | DEDUCTIBLE AREAS.(RE:W.C.'S,LAVS,D.F.'S) | | | | | | 2)FLOORS AND WALLS SHALL BE NONABSORBENT | | | TO A HEIGHT OF 4'PER SBC SEC.1204.2. | | | | | | 3)DRINKING FOUNTAINS SHALL COMPLY W/ | | | FACBC SEC.4.1.3(10)(B). | | | | | | 4)CLEARLY SHOW DIMENSIONS (LXW)OF THE | | | H.C.TOILET STALLS.COMPLY W/FACBC SEC. | | | 4.17.3.(MIN.WIDTH SHALL BE 83") | | | | | | 5)SHOW MOUNTING HEIGHT/DIMENSIONS OF ALL | | | HANDICAP FIXTURES AND APPURTENANCES. | | | COMPLY W/FACBC 1997 ED. | | | | | | 6)SHOW LOCATION OF H.C.URINAL ON PLAN | | | AND DETAIL 30"X48"CLEAR FLOOR SPACE | | | PER FACBC SEC.4.18. | | | | | | 7)SHOW WHEELCHAIR TURNING SPACE IN | | | RESTROOMS PER FACBC SEC.4.2.3. | | | | | | 8)DIELECTRIC NIPPLES/COUPLINGS TO BE | | | USED ON DISSIMILAR METALS.UNIONS NOT | | | PERMITTED.309.3 | | | | | | 9)WATER HEATER SHALL BE READILY ACCESS- | | | IBLE PER SPC SEC.501.7.PROVIDE FIXED | | | LADDER & PLATFORM OR RELOCATE EWH TO | | | FLOOR. | | | | | | 10)SUBMIT INFO ON "EXPRESS PREACTION" | | | SYSTEM.CONDENSATE CANNOT DRAIN TO | | | SANITARY SYSTEM.SMC SEC.304.8.3. | | | | | | 11)SUBMIT PAN DRAIN AND P&T RISER FOR | | | REVIEW.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | *****NOTE:THIS PLAN REVIEW DOESN'T | | | INCLUDE THE FUEL OIL PIPING SYSTEM. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|