Plan Review Details - Permit 00081159
Plan Review Stops For Permit 00081159
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-11 Cont ID  
Sent By dpalmer Date 2001-01-11 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2001-01-11 Time 15:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-09-01 Cont ID  
Sent By dpalmer Date 2000-09-01 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2000-09-01 Time 08:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-07 Cont ID  
Sent By jleech Date 2000-10-07 Time 12:05 Rev Time 0.33
Received By jleech Date 2000-10-07 Time 12:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-26 Cont ID  
Sent By jleech Date 2000-08-26 Time 11:18 Rev Time 0.33
Received By jleech Date 2000-08-26 Time 11:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-26 Cont ID  
Sent By jleech Date 2000-08-26 Time 11:18 Rev Time 0.33
Received By jleech Date 2000-08-26 Time 11:18 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-11-14 Cont ID  
Sent By lhatten Date 2000-11-14 Time 22:18 Rev Time 4.00
Received By lhatten Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER LOU HATTEN

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-13 Cont ID  
Sent By rmcdouga Date 2000-09-13 Time 15:45 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED PER TONY MARCELLO 9-13-00
  
 1)TRUSS LAYOUT SHOWS GRC TRUSS TO THE
 WALL WITH A CONNECTOR AND S2(A)INDICATES
 THIS TRUSS TO BE ON TOP OF THE WALL.
 PLEASE RECHECK THIS AREA FOR CONNECTORS,
 UPLIFT LOADS AND FASTENERS.
  
 2)DETAIL ON CONNECTION OF THE WINDOW AND
 DOOR BUCKS TO MASONRY AS PER SEC.1606.2.
 6.2
  
 3)GRD TRUSS AS SHOWN ON CHAMBERS LAYOUT
 AS LAYING ON THE BEARING WALL.SHEET S29A
 SHOWS THIS TRUSS TO WALL. PLEASE CLARIFY
 AND SHOW THE REQUIRED CONNECTORS.
  
 4)TRUSS GRA ENGINEERING SHOWS UPLIFT OF
 1377# AND 1083# THE CONNECTOR A3 AS
 SHOWN HAS AN UPLIFT OF 1080#. PLEASE
 RECHECK.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By gjoyce Date 2000-08-24 Time 09:35 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***