Plan Review Details - Permit 00081158
Plan Review Stops For Permit 00081158
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-09-14 Cont ID  
Sent By dpalmer Date 2000-09-14 Time 17:50 Rev Time 0.00
Received By dpalmer Date 2000-09-14 Time 17:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-06 Cont ID  
Sent By jleech Date 2000-09-06 Time 18:06 Rev Time 0.50
Received By jleech Date 2000-09-06 Time 18:06 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 REVISED DRAWINGS REQUIRED BEFORE ROUGH
 A/C INSPECTION
 CORRECT;
 1.MASTER BATH DROP 10X6 CFM'S NOT CORECT
 2.6 INCH.DUCT TO MASTER CLOSET SIZE
 DROP AND LIST CFM'S.
 3.4 INCH DUCT TO BATHROOM BY KITCHEN
 SIZE DROP AND LIST CFM'S.
 4.MASTER TOILET ROOM EX-FAN CFM'S.
 5.NEED RETURN AIR FROM MASTER BEDROOM
 IF OVER 300 CFM'S
 6.LIST SEER SEE A/C NOTES 5 E .

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 07:08 Rev Time 0.30
Received By tlarge Date 2000-08-29 Time 07:04 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 LAUNDRY TRAY NOT ON RISER.SUBMIT SIGNED
 AND SEALED RISER PRIOR TO INSPECTION.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-10-18 Cont ID  
Sent By lhatten Date 2000-10-18 Time 21:09 Rev Time 4.00
Received By lhatten Date   Time   Sent To  
Notes
2001-01-08 00:00:00OKED PER LOU HATTEN
 `

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By gjoyce Date 2000-08-24 Time 17:17 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***