Plan Review Details - Permit 00081156
Plan Review Stops For Permit 00081156
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-11 Cont ID  
Sent By dpalmer Date 2001-01-11 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2001-01-11 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 19:56 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 19:56 Sent To  
Notes
2001-01-08 00:00:00**********PROVISO ******************
  
 1)NOTE: PLEASE FEEDER SIZE FOR SERVICE.
  
  
 PLEASE SUBMIT A REVISED RISER DIAGRAM
 BEFORE ROUGH SHOWING SERVICE FEEDER
 WIRE SIZE..IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-30 Cont ID  
Sent By jleech Date 2000-08-30 Time 18:36 Rev Time 0.33
Received By jleech Date 2000-08-30 Time 18:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-25 Cont ID  
Sent By rmcdouga Date 2000-09-25 Time 12:39 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER PAUL E. SCHMITZ 8-27-00

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-11-14 Cont ID  
Sent By lhatten Date 2000-11-14 Time 22:31 Rev Time 4.00
Received By lhatten Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER LOU HATTEN

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-25 Cont ID  
Sent By rmcdouga Date 2000-09-25 Time 12:16 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED PER TONY MARCELLO 9-25-00
  
 1)ENERGY SHEET IS SHOWING 2300 SQFT OF
 A/C AREA,THE PLAN SHOWS 2010 SQFT.PLEASE
 RECHECK.
  
 2)WINDOWS W16 & W7 MUST COMPLY WITH SEC.
 2405.2.
  
 3)PLEASE PROVIDE A DESIGN CERTIFICATION
 SHEET SIGNED AND SEALED SHOWING THE CODE
 USED.
  
 4)PLEASE RECHECK THE UPLIFT CALLED FOR
 ON THE TRUSS ENGINEERING AND THE DESIGN-
 ATED CONNECTORS CALLED FOR S-2(A) FOR
 THE FOLLOWING TRUSSES C,D,DHI,GRA,GRE,O,
 P,R,S,T AND W.
  
 5)TRUSS GRFI AS SHOWN DOES NOT CONFORM
 WITH THE FRAMING PLAN FOR CONNECTORS,
 UPLIFT VALUE AND LENGTH.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By gjoyce Date 2000-08-24 Time 17:23 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***