Plan Review Details - Permit 00081147
Plan Review Stops For Permit 00081147
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-09-20 Cont ID  
Sent By lmartine Date 2000-09-20 Time 14:44 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-11-06 Cont ID  
Sent By dpalmer Date 2000-11-06 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2000-11-06 Time 15:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 20:02 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 20:02 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:PLEASE SUBMIT PLANS SHOWING ALL
 BRANCH CIRCUIT #`S AND CORRELATE WITH
 PANEL SCHEDULES.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS!
 215-5
 ALSO PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% .
  
 3)NOTE: AIC RATINGS GIVEN FOR PANELS
 BUT ALSO NEED TO SUBMIT FOR MAIN DISC.
 PER 110-9 AND 215-5.
  
 4)NOTE:PLEASE SHOW GROUNDING ELECTRODE
 FOR TRANSFORMER.
  
 5)NOTE: PLANS SHOW MORE THAN WHAT PANEL
 SCHEDULES SHOW. PLEASE CLARIFY.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372
  
  
 ***6)NOTE: PLEASE SEE LOCAL CODE FOR
 COLOR CODING OF CONDUCTORS. 277/480V
 YOUR NOTES SHOW ORANGE AS "B" PHASE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-30 Cont ID  
Sent By mcarsill Date 2000-08-30 Time 09:46 Rev Time 0.30
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-11 Cont ID  
Sent By ndenmark Date 2000-09-11 Time 16:29 Rev Time 0.25
Received By ndenmark Date 2000-09-11 Time 16:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-10 Cont ID  
Sent By tlarge Date 2000-09-10 Time 09:44 Rev Time 0.33
Received By tlarge Date 2000-09-10 Time 09:44 Sent To  
Notes
2001-01-08 00:00:00PLUMBING SHOWN AS EXIST.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved