Plan Review Details - Permit 00081084
Plan Review Stops For Permit 00081084
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-12-05 Cont ID  
Sent By jleahy Date 2000-12-05 Time 09:50 Rev Time 0.30
Received By jleahy Date 2000-12-05 Time 09:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-10-24 Cont ID  
Sent By dpalmer Date 2000-10-24 Time 23:23 Rev Time 0.00
Received By jleahy Date 2000-12-05 Time 09:35 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PER STATE STAT-
 -UES. CHANGES MADE TO PLANS MUST BE
 SIGNED AND DATED BY ARCH/ENGINEER OF
 RECORD. PLEASE ALSO NOTE THAT THE PLANS
 WERE RESUBMITTED WITHOUT BEING SIGNED,
 SEALED OR DATED BYT ENGINEER OF RECORD.
 THE IS REQ`D ALSO PER STATE STATUE
 61G15-23.002 AND 471.025.
  
 PLEASE HAVE THE ENGINEER OF RECORD MAKE
 THE ABOVE CHANGES FROM THE FIRST SET OF
 REVIEW NOTES. PLEASE SUBMIT ALL THE
 INFORMATION FROM BOTH REVIEWS FOR REVIEW
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 18:31 Rev Time 0.00
Received By jleahy Date 2000-12-05 Time 09:36 Sent To  
Notes
2001-01-08 00:00:00.************* UNSAT *******************
 0
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 EQUIPMENT MAINS AND PANEL. PER 110-9 AND
 215-5.
  
 2)NOTE: PLEASE SEE 210-52-E FOR GFI REC
 INFRONT OF DWELLING.
  
 3)NOTE:PLEASE SEE 210-52D AND 210-11-C-3
 FOR THE REQ`D BATH(S) CIRCUIT(S). PLEASE
 LIST ON PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATON FOR
 REVIEW. PLANS WOULD HAVE PASSED WITH A
 PROVISO BUT WERE COMING BACK FOR OTHER
 COMMENTS. PLEASE TAKE CARE OF THE NOTES
 BEFORE RE-SUBMITTING. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372
  
  
 021

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-26 Cont ID  
Sent By jleech Date 2000-08-26 Time 12:40 Rev Time 0.33
Received By jleech Date 2000-08-26 Time 12:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-12-05 Cont ID  
Sent By jleech Date 2000-12-05 Time 07:40 Rev Time 0.33
Received By jleech Date 2000-12-05 Time 07:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-20 Cont ID  
Sent By tlarge Date 2000-10-20 Time 19:13 Rev Time 0.50
Received By tlarge Date 2000-10-20 Time 19:13 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY RISER DIAGRAM THAT
 CORRELATES W/THE FLOOR AND COMPLIES W/
 THE SPC IN ALL RESPECTS.THERE ARE TOO
 MANY VIOLATIONS TO LIST.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-27 Cont ID  
Sent By pschmitz Date 2000-08-27 Time 11:57 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) DESIGN PLBG DWV ISOMETRIC TO SPC 94.
 QUESTIONS CONTACT PAUL SCHMITZ
 561-659-8096 X 8233

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-11-09 Cont ID  
Sent By drunnels Date 2000-11-09 Time 09:18 Rev Time 1.00
Received By drunnels Date 2000-11-09 Time 09:18 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-27 Cont ID  
Sent By lsmith Date 2000-09-27 Time 13:24 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TM SEE NOTES ON PLANS 9/27/00

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By gjoyce Date 2000-08-24 Time 17:13 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy