Plan Review Details - Permit 00081051
Plan Review Stops For Permit 00081051
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-27 Cont ID  
Sent By mcarsill Date 2000-09-27 Time 13:36 Rev Time 0.00
Received By mcarsill Date 2000-09-27 Time 13:36 Sent To  
Notes
2001-01-08 00:00:001) COPIES OF THE UNIFORM FIRE CODE
 FOR ELEVATORS HAVE BEEN INCLUDED WITH
 THE PLANS FOR REVIEW. PLEASE NOTE
 SECTIONS 4A-47.009 AND 4A-47.010
 REGARDING INSTALLATION OF SMOKE AND
 HEAT DETECTORS FOR ELEVATOR EQUIPMENT.
 2) SYSTEM TO BE CLASS A OR ADDRESSABLE.
 3) SYSTEM AFTER INSTALLATION IS SUBJECT
 TO INSPECTION BY FIRE RESCUE.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-23 Cont ID  
Sent By mcarsill Date 2000-08-23 Time 14:30 Rev Time 0.00
Received By mcarsill Date 2000-08-23 Time 14:30 Sent To  
Notes
2001-01-08 00:00:001) NO CUT SHEETS PROVIDED FOR SMOKE
 AND HEAT DETECTORS PLANNED FOR
 INSTALLATION.
 2) NO HORN STROBES SHOWN ON PLAN. PLEASE
 BE ADVISED THAT THE 1997 STANDARD
 BUILDING CODE SECTION 903.8.3 REQUIRES
 THAT WHEN THE FIRE SPRINKLER SYSTEM IS
 ACTIVATED, THE BUILDING FIRE ALARM
 SYSTEM IS TO SOUND. HOW IS THIS
 REQUIREMENT GOING TO BE ACCOMPLISHED.
 3) NO INDICATION OF THE FIRE ALARM
 SYSTEM BEING MONITORED. THE FIRE
 SPRINKLER SYSTEM IS TO BE SUPERVISED BY
 BUILDING AND FIRE CODES.