| Plan Review Stops For Permit 00081051 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-27 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-27 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) COPIES OF THE UNIFORM FIRE CODE | | | FOR ELEVATORS HAVE BEEN INCLUDED WITH | | | THE PLANS FOR REVIEW. PLEASE NOTE | | | SECTIONS 4A-47.009 AND 4A-47.010 | | | REGARDING INSTALLATION OF SMOKE AND | | | HEAT DETECTORS FOR ELEVATOR EQUIPMENT. | | | 2) SYSTEM TO BE CLASS A OR ADDRESSABLE. | | | 3) SYSTEM AFTER INSTALLATION IS SUBJECT | | | TO INSPECTION BY FIRE RESCUE. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-23 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-23 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO CUT SHEETS PROVIDED FOR SMOKE | | | AND HEAT DETECTORS PLANNED FOR | | | INSTALLATION. | | | 2) NO HORN STROBES SHOWN ON PLAN. PLEASE | | | BE ADVISED THAT THE 1997 STANDARD | | | BUILDING CODE SECTION 903.8.3 REQUIRES | | | THAT WHEN THE FIRE SPRINKLER SYSTEM IS | | | ACTIVATED, THE BUILDING FIRE ALARM | | | SYSTEM IS TO SOUND. HOW IS THIS | | | REQUIREMENT GOING TO BE ACCOMPLISHED. | | | 3) NO INDICATION OF THE FIRE ALARM | | | SYSTEM BEING MONITORED. THE FIRE | | | SPRINKLER SYSTEM IS TO BE SUPERVISED BY | | | BUILDING AND FIRE CODES. |
|
|
|