Plan Review Details - Permit 00081031
Plan Review Stops For Permit 00081031
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-18 Cont ID  
Sent By drunnels Date 2000-09-18 Time 09:33 Rev Time 1.00
Received By drunnels Date 2000-09-18 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-01 Cont ID  
Sent By bstaples Date 2000-09-01 Time 08:27 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS NOT SIGNED BY
 OWNER/AGENT.
 2. WIND LOAD PRODUCT APPROVAL FOR STORE
 FRONT NOT SUBMITTED. PROVIDE PRODUCT
 APPROVALS.
 3. HURRICANE SHUTTERS: PROVIDE THE
 FOLLOWING INFORMATION:
 A. PRODUCT APPROVAL, METRO DADE COUNTY
 OR SBCCI, SSTD 12-97.
 B. STORAGE LOCATION IN UNIT.
 C. LETTER FROM TENNANT GIVING TIME TO
 INSTALL AND TRAINING PROGRAM FOR STAFF.
 D. STORAGE LOCATION IN UNIT. NOTE: IF
 STORED IN A VERTICAL MANNER PROVIDE
 DESIGN FOR ENGINEERED STORAGE RACK.
 4. FIRE SPRINKLER PERMIT REQUIRED PRIOR
 TO ISSUANCE OF BUILDING PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-18 Cont ID  
Sent By dpalmer Date 2000-09-18 Time 09:14 Rev Time 0.00
Received By dpalmer Date 2000-09-18 Time 09:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-31 Cont ID  
Sent By dpalmer Date 2000-08-31 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2000-08-31 Time 11:20 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE 220-3-B-7/220-12-A
 FOR THE REQ`D LOAD CALCULATIONS FOR
 SHOW WINDOWS.
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.(LIGHTING)
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS
 215-5
  
 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 AND CONNECTION FOR GROUNDING. TRANSFORM-
 -ER. ETC.
  
 5)NOTE: PLEASE SEE LOADS FOR LIGHTING
 CIRCUITS #`S 3,5. LOAD SHOWN IS ABOVE
 80% FOR BREAKERS. PLEASE CORRECT.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-15 Cont ID  
Sent By mcarsill Date 2000-09-15 Time 16:05 Rev Time 0.00
Received By mcarsill Date 2000-09-15 Time 16:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-31 Cont ID  
Sent By mcarsill Date 2000-08-31 Time 08:01 Rev Time 0.00
Received By mcarsill Date 2000-08-31 Time 08:01 Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS.
 2) INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL BE CLASS A OR B. PLEASE NOTE
 THIS ON PLANS.
 3) EXITING THROUGH STOCKROOM PERMITTED
 IF THE FOLLOWING CONDITIONS ARE PRESENT,
 DOOR LEADING TO STOCKROOM CANNOT BE
 LOCKED, AN AISLE OF AT LEAST 44" WIDE
 SHALL BE PROVIDED, THIS 44" AISLE IS
 TO BE MAINTAINED, AND NO MORE THAN
 50 PERCENT OF EXIT ACESS CAN BE THROUGH
 STOCKROOM.
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 5) PLEASE PROVIDE FIRE ALARM PLANS FOR
 FIRE ALARM DEVICES SHOWN ON PLANS. PULL
 STATIONS ARE NOT NECESSARY IN TENANT
 SPACES.
 6) ADDITIONAL EXIT SIGN IS REQUIRED AT
 REAR EXIT DOOR.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-20 Cont ID  
Sent By ndenmark Date 2000-12-20 Time 09:39 Rev Time 0.25
Received By ndenmark Date 2000-12-20 Time 09:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-30 Cont ID  
Sent By ndenmark Date 2000-08-30 Time 14:20 Rev Time 0.50
Received By ndenmark Date 2000-08-30 Time 14:20 Sent To  
Notes
2001-01-08 00:00:00NOTE:::
 AT LEAST ONE SET HAS NO A-5 (MECH) PLAN
 COMPLETE ALL SETS TO HAVE TWO FULL SETS

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-30 Cont ID  
Sent By tlarge Date 2000-08-30 Time 17:52 Rev Time 0.65
Received By tlarge Date 2000-08-30 Time 17:43 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 SUBMIT WATER RISER DIAGRAM FOR REVIEW.
  
 2)LOCATION OF THE DRINKING FOUNTAIN
 SHALL BE INDELIBLY POSTED FOR THE
 INTENDED USE,BE ON AN ACCESSIBLE ROUTE
 AND BE AVAILABLE TO PATRONS WITHOUT
 RESTRICTION DURING NORMAL OPERATING
 HOURS.THE ACCESSIBLE ROUTE SHALL BE
 CLEARLY DEFINED ON THE PLANS.FACBC SECS.
 4.1,4.2,4.3,SPC 407.2.2.
  
 2)A FLOOR DRAIN W/TRAP PRIMER IS REQD.IN
 THE TOILET ROOM PER SPC SEC.409.4.1.1.
  
 3)BENCH IN H.C.FITTING ROOM SHALL BE
 AFFIXED TO THE WALL WITH THE LONGER
 DIMENSION PER FACBC SEC.4.35.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.
  
 THIS PLAN IS APPROVED W/THE ABOVE
 PROVISOS.SUBMIT REVISED PLANS PRIOR TO
 PLUMBING INSPECTION.