Plan Review Details - Permit 00081025
Plan Review Stops For Permit 00081025
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By drunnels Date 2000-09-12 Time 12:45 Rev Time 1.00
Received By drunnels Date 2000-09-12 Time 12:45 Sent To  
Notes
2001-01-08 00:00:00ALL DEMIZING WALLS SHALL BE COMPLETE
 PRIOR TO C.O. BEING ISSUED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-05 Cont ID  
Sent By drunnels Date 2000-09-05 Time 10:25 Rev Time 1.00
Received By drunnels Date 2000-09-05 Time 10:25 Sent To  
Notes
2001-01-08 00:00:001.OWNER/AGENT MUST SIGN FLORIDA ENERGY
 SHEETS.
 2.SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION.
  
 NOTE: ALL FIRE RESISTANT DEMIZING WALLS
 TO BE COMPLETED PRIOR TO C.O. BEING
 ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 11:06 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 11:05 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 220. PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%.
  
 PLEASE SUBMIT THE ABOVE FOR SHEET E-4.0
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-31 Cont ID  
Sent By dpalmer Date 2000-08-31 Time 12:17 Rev Time 0.00
Received By dpalmer Date 2000-08-31 Time 12:17 Sent To  
Notes
2001-01-08 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SHOW LOAD CALCULATION/S/
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%
  
 2)NOTE: PLEASE SEE 220-3-B-7/ 220-12-A
 FOR SHOW WINDOW REQ`MENTS.
  
 3)NOTE: PLEASE SEE 220-12-B FOR TRACK
 LIGHTING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By mcarsill Date 2000-09-12 Time 11:32 Rev Time 0.00
Received By mcarsill Date 2000-09-12 Time 11:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-31 Cont ID  
Sent By mcarsill Date 2000-08-31 Time 08:23 Rev Time 0.00
Received By mcarsill Date 2000-08-31 Time 08:23 Sent To  
Notes
2001-01-08 00:00:001) WRONG TRAVEL DISTANCE NOTED ON PLANS.
 SHOULD READ 150 FEET INSTEAD OF 250
 FEET BECAUSE THE SPACE IS FIRE SPRINKLER
 PROTECTED. CODE NFPA 101, 1985 EDITION.
 2) AN ADDITIONAL EXIT SIGN IS NEEDED TO
 DIRECT PERSONS TO CORRIDOR 006.
 3) PLEASE INDICATE EMERGENCY LIGHT
 FIXTURES IN SALES AREA.
 4) ADDITIONAL FIRE ALARM DEVICES ARE
 NEEDED WITHIN TENANT SPACE.
 5) EXITING THROUGH STOCKROOM PERMITTED
 ONLY IF AN AISLE OF AT LEAST 44" WIDE
 IS PRESENT, THIS 44" AISLE MUST BE
 MAINTAINED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-31 Cont ID  
Sent By ndenmark Date 2000-08-31 Time 13:50 Rev Time 0.75
Received By ndenmark Date 2000-08-31 Time 13:50 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. RETURN AIR PLENUM AREA ABOVE CEILING
 SHALL HAVE NO COMBUSTABLE CONSTRUCTION
 OR MATERIALS IN PLENUM SPACE PER 1997
 SMC 609.1.1

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-11-15 Cont ID  
Sent By jleech Date 2000-11-15 Time 15:13 Rev Time 0.33
Received By jleech Date 2000-11-15 Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-09-08 Cont ID  
Sent By tlarge Date 2000-09-08 Time 18:07 Rev Time 0.65
Received By tlarge Date 2000-09-08 Time 17:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-31 Cont ID  
Sent By tlarge Date 2000-08-31 Time 21:09 Rev Time 0.65
Received By tlarge Date 2000-08-31 Time 20:38 Sent To  
Notes
2001-01-08 00:00:001)SHOW CLEAR FLOOR SPACE FOR DRINKING
 FOUNTAINS AND BREAKROOM SINK ON THE PLAN
 FIXTURES CANNOT OBSTRUCT CLEAR ACCESS TO
 OTHER FIXTURES.CLEAR FLOOR SPACES FOR
 FIXTURES MAY OVERLAP.4.15.5,4.19.3.
  
 2)MIN.SIZE OF HEATER PAN DRAIN SHALL BE
 1"PER SPC SEC.507.8.2.
  
 3)BENCH IN H.C.FITTING ROOM SHALL COMPLY
 W/FACBC SEC.4.35.4.MIRROR SHALL COMPLY
 W/SEC.4.35.5.
  
 4)BREAKROOM SINK SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 18:56 Rev Time 0.65
Received By tlarge Date 2000-08-29 Time 18:33 Sent To  
Notes
2001-01-08 00:00:001)BENCH IN H.C.FITTING ROOM SHALL BE
 AFFIXED ALONG THE WALL WITH THE LONGER
 DIMENSION PER FACBC SEC.4.35.4.
  
 2)MIRROR IN H.C.FITTING ROOM SHALL
 COMPLY W/FACBC 4.35.5.
  
 3)BREAKROOM SINK SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7
  
 4)SUBMIT SANITARY AND WATER RISERS SHALL
 BE SUBMITTED FOR REVIEW.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 NOTE:A DRINKING FOUNTAIN WILL NOT BE
 REQUIRED PER SPC TABLE 407,FOOTNOTE 8.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.