| Plan Review Stops For Permit 00081025 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-12 |
Time |
12:45 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-12 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ALL DEMIZING WALLS SHALL BE COMPLETE | | | PRIOR TO C.O. BEING ISSUED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-05 |
Time |
10:25 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-05 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.OWNER/AGENT MUST SIGN FLORIDA ENERGY | | | SHEETS. | | | 2.SUBMIT FIRE SPRINKLER PLANS AND | | | APPLICATION. | | | | | | NOTE: ALL FIRE RESISTANT DEMIZING WALLS | | | TO BE COMPLETED PRIOR TO C.O. BEING | | | ISSUED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-12 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-12 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** PROVISO **************** | | | | | | 1)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER 220. PLEASE SHOW ALL CONTINUOUS | | | LOADS AT 125%. | | | | | | PLEASE SUBMIT THE ABOVE FOR SHEET E-4.0 | | | BEFORE ROUGH ELECTRICAL INSPECTION IS | | | CALLED IN. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-31 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-31 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************ UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW LOAD CALCULATION/S/ | | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% | | | | | | 2)NOTE: PLEASE SEE 220-3-B-7/ 220-12-A | | | FOR SHOW WINDOW REQ`MENTS. | | | | | | 3)NOTE: PLEASE SEE 220-12-B FOR TRACK | | | LIGHTING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-12 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-12 |
Time |
11:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-31 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-31 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG TRAVEL DISTANCE NOTED ON PLANS. | | | SHOULD READ 150 FEET INSTEAD OF 250 | | | FEET BECAUSE THE SPACE IS FIRE SPRINKLER | | | PROTECTED. CODE NFPA 101, 1985 EDITION. | | | 2) AN ADDITIONAL EXIT SIGN IS NEEDED TO | | | DIRECT PERSONS TO CORRIDOR 006. | | | 3) PLEASE INDICATE EMERGENCY LIGHT | | | FIXTURES IN SALES AREA. | | | 4) ADDITIONAL FIRE ALARM DEVICES ARE | | | NEEDED WITHIN TENANT SPACE. | | | 5) EXITING THROUGH STOCKROOM PERMITTED | | | ONLY IF AN AISLE OF AT LEAST 44" WIDE | | | IS PRESENT, THIS 44" AISLE MUST BE | | | MAINTAINED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-31 |
Time |
13:50 |
Rev Time |
0.75 |
| Received By |
ndenmark |
Date |
2000-08-31 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. RETURN AIR PLENUM AREA ABOVE CEILING | | | SHALL HAVE NO COMBUSTABLE CONSTRUCTION | | | OR MATERIALS IN PLENUM SPACE PER 1997 | | | SMC 609.1.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-11-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-15 |
Time |
15:13 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-15 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-09-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-08 |
Time |
18:07 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-09-08 |
Time |
17:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-31 |
Time |
21:09 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-31 |
Time |
20:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SHOW CLEAR FLOOR SPACE FOR DRINKING | | | FOUNTAINS AND BREAKROOM SINK ON THE PLAN | | | FIXTURES CANNOT OBSTRUCT CLEAR ACCESS TO | | | OTHER FIXTURES.CLEAR FLOOR SPACES FOR | | | FIXTURES MAY OVERLAP.4.15.5,4.19.3. | | | | | | 2)MIN.SIZE OF HEATER PAN DRAIN SHALL BE | | | 1"PER SPC SEC.507.8.2. | | | | | | 3)BENCH IN H.C.FITTING ROOM SHALL COMPLY | | | W/FACBC SEC.4.35.4.MIRROR SHALL COMPLY | | | W/SEC.4.35.5. | | | | | | 4)BREAKROOM SINK SHALL COMPLY W/FACBC | | | SEC.4.24.1-4.24.7. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-29 |
Time |
18:56 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-29 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)BENCH IN H.C.FITTING ROOM SHALL BE | | | AFFIXED ALONG THE WALL WITH THE LONGER | | | DIMENSION PER FACBC SEC.4.35.4. | | | | | | 2)MIRROR IN H.C.FITTING ROOM SHALL | | | COMPLY W/FACBC 4.35.5. | | | | | | 3)BREAKROOM SINK SHALL COMPLY W/FACBC | | | SEC.4.24.1-4.24.7 | | | | | | 4)SUBMIT SANITARY AND WATER RISERS SHALL | | | BE SUBMITTED FOR REVIEW.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | NOTE:A DRINKING FOUNTAIN WILL NOT BE | | | REQUIRED PER SPC TABLE 407,FOOTNOTE 8. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|