| Plan Review Stops For Permit 00080984 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-18 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-18 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PROVIDE COMPLETE PLANS FOR THE | | | INSTALLATION OF THE WET CHEMICAL | | | EXTINGUISHING SYSTEMS PLANNED FOR THE | | | HOODS. THESE SYSTEMS ARE TO COMPLY WITH | | | NFPA 17A. | | | 2) PROVIDE DIAGRAM ON COOKING APPLIANCES | | | THAT WILL BE LOCATED UNDERNEATH THE | | | HOODS. | | | 3) HOOD AND DUCT INSTALLATIONS TO | | | COMPLY WITH NFPA 96. INSTALLATION OF | | | THESE DEVICES ARE SUBJECT TO FIRE | | | AND MECHANICAL DIVISION APPROVALS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-28 |
Time |
09:23 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-08-28 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. ALL HOOD AND DUCT TO BE PER 1997 SMC | | | AND 1996 NFPA 96 |
|
|
|