Plan Review Details - Permit 00080956
Plan Review Stops For Permit 00080956
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By mcarsill Date 2000-08-24 Time 08:24 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) FIRE ALARM SYSTEM ADDITIONS SHALL BE
 CLASS A, STYLE D WIRED OR BE ADDRESSABLE
 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS
 TO BE AUDIBLE THROUGHOUT SPACE.
 3) SMOKE DETECTORS TO BE INSTALLED A
 MINIMUM OF THREE FEET FROM ANY AIR
 CONDITIONER DIFFUSERS.
 4) SYSTEM AFTER INSTALLATION TO BE
 TESTED WITH FIRE RESCUE REPRESENTATIVES.
 5) FIRE ALARM EQUIPMENT INSTALLED ON THE
 NINTH FLOOR IS TO BE CONNECTED TO THE
 BASE BUILDING FIRE ALARM SYSTEM.