Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-04-20 Cont ID  
Sent By dpalmer Date 2001-04-20 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2001-04-20 Time 12:54 Sent To  
Notes
2001-04-20 00:00:00PLANS ARE TO BE RE-DRAWN BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 18:53 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 18:52 Sent To  
Notes
2001-04-05 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE ORIGINAL
 PLAN WAS SUBMITTED AGAIN WITH
 HANDWRITTEN CHANGES W/OUT ENGINEER OF
 RECORD SIGING EACH CHANGE. ALSO, THE
 COPY OF PLAN IS VERY UNCLEAR. PLEASE
 NOTE UNDER F.S.
 F.A.C, COUNTY AND CITYWIDE
 ADMINISTRATIVE CODE. 104.2, 104.2.1,
 471.025 PLANS ARE TO BE CLEAR AND
 LEGIABLE.PLEASE HAVE ELECTRICAL PART
 OF PLAN RE-DRAWN .
  
  
 2)NOTE: PLEASE NOTE THERE ARE NOT ENOUGH
 CONDUCTORS SHOWN COMING FROM MAIN PANEL
 AT HOUSE. PLANS SHOW 2-6`S AND 1-#8.
 WHERE IS NEUTRAL? OR IS #8 NEUTRAL? IF
 SO THEN WHERE IS EQUIPMENT GROUNDING
 CONDUCTOR?
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 BATH. 210-52D ,#12, 20A.
  
 4)NOTE: PLEASE NOTE THAT PLANS SHOW THAT
 THERE IS NO ADDED LOAD ? HOW IS THIS
 POSSIBLE?
  
 AS ON PREVIOUS NOTES, PLEASE CALL IF THE
 RE ARE ANY QUESTIONS, OR CLARIFICATION
 NEEDED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-03-20 Cont ID  
Sent By dpalmer Date 2001-03-20 Time 13:48 Rev Time 0.00
Received By dpalmer Date 2001-03-20 Time 13:48 Sent To  
Notes
2001-03-20 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASENOTE THAT PER F.A.C.
 ALL PLANS THAT ARE SIGNED AND SEALED BY
 AN ARCH/ENGINEER NEED TO HAVE ALL
 CHANGES DONE BY THAT PERSONOF RECORD.
  
 2)NOTE: PLEASE NOTE PLANS ARE TO BE RE-
 DONE TO MEET ALL ORIGINAL NOTES.
  
 3)NOTE: PLEASE NOTE THAT TWO COPIES ARE
 TO BE SUBMITTED FOR REVIEW. ONE COMES
 BACK FOR YOUR RECORD ON THE JOB AND THE
 OTHER IS FOR OUR RECORD.
  
 4)NOTE: PLEASE CLARIFY PLANS SHOWING
 3-2/0`S GOING TO A 60A MAIN. PLEASE
 CLARIFY HOW 2/0 WIRE IS GOING TO FIT
 INTO A 60A MAIN.??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-11-16 Cont ID  
Sent By dpalmer Date 2000-11-16 Time 11:40 Rev Time 0.00
Received By dpalmer Date 2000-11-16 Time 11:40 Sent To  
Notes
2001-01-08 00:00:00************* REVISION REQUESTED *******
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION ON
 PANEL FOR GARAGE. MAIN BRKR? A MAIN
 MEANS OF DISCONNECT IS REQ`D.
  
 2)NOTE: PLEASE SHOW GROUNDING PER NEC
 FOR DETACHED GARAGE. COLD WATER,GRND ROD
  
 3)NOTE: PLEASE SEE REQ`MENTS FOR SD`S
 INSIDE SLEEPING ROOMS! NFPA-72 2-2.1.1.1
  
 4)NOTE: PLEASE PROVIDE A GFI REC OUTSIDE
 PER 210-52E
  
 THE FOLLOWING ARE NOTES TO QUESTION
 ANY OTHER ISSUES THAT MAY ARISE.
 IS THERE GOING TO BE CATV OR TELEPHONE
 OUTLETS INSTALLED??
 WHERE IS THE HOT WATER COMING FROM?
 PLEASE CLARIFY!
 IS THERE GOING TO BE CENTRAL A/C OR IS
 THERE GOING TO BE A WINDOW UNIT?
 PLEASE PROVIDE CLARIFICATION ON THE
 ABOVE INFORMATION.
  
 ALSO PLEASE NOTE THAT PROVISIONS FOR
 KITCHEN COOKING EQUIPMENT WILL NOT BE
 PERMITTED TO BE INSTALLED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
  
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-23 Cont ID  
Sent By dpalmer Date 2000-08-23 Time 15:00 Rev Time 0.00
Received By dpalmer Date 2000-08-23 Time 15:00 Sent To  
Notes
2001-01-08 00:00:00********* UNSAT **********************
  
 NO ELECTRICAL PLANS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-08-26 Cont ID  
Sent By jleech Date 2000-08-26 Time 08:53 Rev Time 0.25
Received By jleech Date 2000-08-26 Time 08:53 Sent To  
Notes
2001-01-08 00:00:00NO A/C

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-16 Cont ID  
Sent By jleech Date 2000-11-16 Time 18:56 Rev Time 0.25
Received By jleech Date 2000-11-16 Time 18:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-26 Cont ID  
Sent By tlarge Date 2000-08-26 Time 05:30 Rev Time 0.50
Received By tlarge Date 2000-08-26 Time 05:26 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT SANITARY AND WATER ISOMETRICS
 FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.COMPLY W/SPC.
  
 2)SHOWER SHALL BE A MIN.OF 30"WIDE AND
 MIN.1024 SQ.IN.TOTAL AREA.COUNTYWIDE
 AMENDMENTS TO SPC SEC.409.8.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-12-04 Cont ID  
Sent By fknapp Date 2000-12-04 Time 10:36 Rev Time 2.00
Received By fknapp Date 2000-12-04 Time 10:36 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-18 Cont ID  
Sent By fknapp Date 2000-09-18 Time 14:09 Rev Time 2.00
Received By fknapp Date 2000-09-18 Time 14:09 Sent To  
Notes
2001-01-08 00:00:00 
  
 *************BUILDING UNSAT*************
  
 SBC 104.2.2
  
 1)PROVIDE 2 COPIES OF PRODUCT APPROVALS
 THAT ARE SUPPLIED.
  
 2)PROVIDE STORM PANEL INFORMATION
 COMPLETE WITH INSTALLATION SCHEDULE AND
 KEY PLAN WITH SPECIFIC ANCHORS TO BE USE
  
 3)PROVIDE WALL SECTION DETAILS, DETAILS
 TO BE COMPLETE WITH ALL CONNECTORS AND
 MATERIALS TO BE USED.
  
 4)PROVIDE DETAILS OF SLAB REPAIR AND
 JOIST REPAIR.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-22 Cont ID  
Sent By gjoyce Date 2000-08-22 Time 10:07 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***