Plan Review Details - Permit 00080930
Plan Review Stops For Permit 00080930
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-20 Cont ID  
Sent By drunnels Date 2000-09-20 Time 13:29 Rev Time 1.00
Received By drunnels Date 2000-09-20 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-14 Cont ID  
Sent By drunnels Date 2000-09-14 Time 08:04 Rev Time 1.00
Received By drunnels Date 2000-09-14 Time 08:04 Sent To  
Notes
2001-01-08 00:00:001.SHEET A5, DETAIL C, HAVE STRUCTURAL
 ENGINEER CERTIFY LOADING OF BOTTOM
 CORD OF ROOF TRUSSES WITH WOOD BEAM
 AND CEILING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-05 Cont ID  
Sent By bstaples Date 2000-09-05 Time 10:37 Rev Time 1.20
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00A. SHEET CS1
 1. CODE REFERENCES, CORRECT THE
 FOLLOWINF,
 MECHANICIAL CODE IS 1997 NOT 1994
 BUILDING CODE IS 1997 NOT 1999
 ELECTRICAL CODE IS 1999 NOT 1996
  
 B. SHEET CS2
 1. NOTE #7 REFERS TO WRONG ACCESSABILITY
 CODE PROPER REFERENCE IS TO FLORIDA
 ACCESSABILITY CODE 1997 EDITION
  
 C. SHEET A1
 1. SIGNS ARE NOT COVERED BY PRIME PERMIT
 SUBMIT SEPERATE APPLICATION FOR PERMIT.
  
 D. SHEET A3 NOTES INDICATE EXTERIOR STUD
 1. NOTES INDICATE EXTERIOR STUD WALLS
 THIS BUILDING IS IN THE FIRE DISTRICT
 USE OF WOOD IS A VIOLATION OF 1997 SBC
 SECTION F102.1, REVISE.
 2. NOTE ON STRUCTURAL, ALL STRUCTURAL
 VERIFICATION IS TO BE PERFORMED BY A
 FLORIDA LICENSED ENGINEER OR ARCHITECT.
  
 E. SHEET A5
 1. DETAIL C, HAVE STRUCTURAL ENGINEER
 CERTIFY LOADING OF BOTTOM CORD OF ROOF
 TRUSSES WITH WOOD BEAM AND CELING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-08-25 Cont ID  
Sent By dpalmer Date 2000-08-25 Time 10:46 Rev Time 0.00
Received By dpalmer Date 2000-08-25 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-20 Cont ID  
Sent By mcarsill Date 2000-09-20 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2000-09-20 Time 13:48 Sent To  
Notes
2001-01-08 00:00:001) PROVIDE PLANS AND PERMIT FOR FIRE
 SPRINKLER REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-18 Cont ID  
Sent By mcarsill Date 2000-08-18 Time 10:11 Rev Time 0.00
Received By mcarsill Date 2000-08-18 Time 10:11 Sent To  
Notes
2001-01-08 00:00:001) NO BUILDING ADDRESS SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 2) ENTRY DOORS MUST SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 3) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 4) ALL EXIT DOORS SUBJECT TO AN
 OCCUPANCY OF 100 OR MORE PERSONS ARE
 TO BE EQUIPPED WITH APPROVED PANIC
 HARDWARE. NO OTHER LOCKS WILL BE
 PERMITTED.
 5) INTERIOR FINISHES SHALL BE CLASS
 A OR B IN EXITS. INTERIOR FINISHES IN
 OTHER AREAS SHALL BE CLASS A,B,OR C.
 6) PROVIDE COMPLETE PLANS FOR THE
 INSTALLATION OF THE HOOD, DUCT, AND
 EXTINGUISHING SYSTEM. A SEPARATE PERMIT
 IS REQUIRED.
 7) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 8) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 9) NO FIRE SPRINKLER DRAWINGS SUBMITTED
 WITH PLANS. ACCORDING TO FIRE RESCUE
 RECORDS, THIS BUILDING HAS AN EXISTING
 FIRE SPRINKLER SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-06 Cont ID  
Sent By ndenmark Date 2000-10-06 Time 08:00 Rev Time 0.25
Received By ndenmark Date 2000-10-06 Time 08:00 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. PROVIDE CFM VALUES AND ALL DUCT SIZES
 2. PROVIDE INFORMATION ON EQUIPMENT SCHE
 DULE INCLUDING SEER AND OUTSIDE AIR
 3. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED WITH NOTIFICATION BY BLDG ALARM
 OR HORN AND STROBE PER NFPA 90A 4.4-4.
  
 INFORMATION TO BE SUBMITTED PRIOR TO
 FINAL INSPECTION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-28 Cont ID  
Sent By ndenmark Date 2000-08-28 Time 09:14 Rev Time 0.50
Received By ndenmark Date 2000-08-28 Time 09:14 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1.FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TESTED
 2.SEPARATE PERMITS REQUIRED FOR HOODS,
 COOLERS, SUPPRESSION SYSTEMS. SUBMIT
 PLANS AT TIME OF PERMIT APPLICATION FOR
 THESE SYSTEMS

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-20 Cont ID  
Sent By tlarge Date 2000-09-20 Time 10:50 Rev Time 0.75
Received By tlarge Date 2000-09-20 Time 10:50 Sent To  
Notes
2001-01-08 00:00:00SEPARATE PLANS AND PERMIT REQD.FOR GAS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-09-19 Cont ID  
Sent By tlarge Date 2000-09-19 Time 15:05 Rev Time 0.75
Received By tlarge Date 2000-09-19 Time 15:05 Sent To  
Notes
2001-01-08 00:00:001)PLANS SHALL BE APPROVED BY THE DEPT.OF
 BUSINESS REG.PRIOR TO REVIEW BY THIS
 DEPT.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
  
 2)INDICATE TYPE OF GAS PIPING USED IN
 THE GAS SYSTEM.COMPLY W/SGC SEC.305.4.
  
 3)VOID/DELETE ALL OLD SHEETS .
  
 4)COMPLY W/ALL PREVIOUS COMMENTS FOR GAS
 SYSTEM.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.
 561-659-8096,EXT.8377.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-13 Cont ID  
Sent By tlarge Date 2000-09-13 Time 15:09 Rev Time 2.50
Received By tlarge Date 2000-09-13 Time 15:09 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD BASED ON SQ.FT.OF
 HABITABLE FLOOR SPACE PER SPC TABLE 407.
 SEE SPC.SEC.407.1.3 FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 2)DESIGN OF GREASE TRAP SHALL COMPLY W/
 CITY OF WPB BUILDING DEPT.REQS.(SEE
 ATTACHED).CONTACT ROD COMPO AT
 (561)835-7423 FOR APPROVAL OF SIZE.
 SUBMIT APPROVAL FORM FROM UTILITIES DEPT
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
  
 3)SUBMIT A COMPLETE GAS RISER DIAGRAM
 FOR REVIEW.SHOW ALL EQUIPMENT ON THE GAS
 RISER DIAGRAM.COMPLY W/ATTACHED GAS REQS
  
 4)VACUUM RELIEF VALVE ON WATER HEATER
 IS NOT PROPERLY CONNECTED.INSTALLATION
 SUBJECT TO FIELD INSPECTOR'S APPROVAL.
 SPC SEC.507.1.2.
  
 5)PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL PRIOR TO APPROVAL BY THIS DEPT.
 CALL (954)958-5520.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7.
  
 6)SHT.K-2 LISTS CONNECTION OF GAS EQUIP.
 W/GAS HOSE.GAS HOSE IS PROHIBITED PER
 SGC SEC.403.2.COMPLY W/SGC SEC.403.1.1.
  
 7)RELIEF DRAIN FOR EWH SHALL DISCHARGE
 INTO A FLOOR SINK,NOT A FLOOR DRAIN PER
 SPC SEC.804.1.,807.1.3.
  
 8)IF YOUR OCCUPANT LOAD REMAINS AT 120
 PERSONS ADDITIONAL PLUMBING FIXTURES
 WILL BE REQD.PER SPC TABLE 407.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-26 Cont ID  
Sent By tlarge Date 2000-08-26 Time 10:04 Rev Time 0.75
Received By tlarge Date 2000-08-26 Time 09:34 Sent To  
Notes
2001-01-08 00:00:001)HANDICAP STALLS SHALL COMPLY W/FACBC
 SEC.4.17.3.(MIN.WIDTH SHALL BE 83"IF
 LAV.IS ADJACENT TO W.C.)SEE 4.1.6.(B)
  
 2)SUBMIT OCCUPANT LOAD BASED ON SQ.FT.OF
 HABITABLE FLOOR SPACE PER SPC TABLE 407.
 SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 3)DISHWASHER AND GARBAGE DISPOSAL SHALL
 BYPASS GREASY WASTE AND CONNECT TO
 SANITARY SYSTEM PERCITY ORDINANCE.
  
 4)DESIGN OF GREASE TRAP SHALL COMPLY W/
 BUILDING DEPT.REQS. (SEE ATTACHED)
 CONTACT ROD COMPO AT 561-835-7423 FOR
 APPROVAL OF SIZE.SUBMIT APPROVAL FORM
 FROM UTILITIES.
  
 5)SHOW ALL EQUIPMENT ON GAS DRAWING.SEE
 ATTACHED FOR REQS.
  
 6)SHUT-OFF VALVE,AUTOMATIC GAS VALVE(
 FIRE VALVE)AND UNION SHALL BE INSTALLED
 BELOW CEILING AND BE ACCESSIBLE.NFPA
 5.5.4.
  
 7)GREASY WASTE DESIGN SHALL COMPLY W/
 SPC SEC.921.
  
 8)SHT.P-1-BOTTOM FED WATER HEATER SHALL
 BE EQUIPPED W/VACUUM RELIEF VALVE PER
 SPC SEC.507.1.2.
  
 9)SHT.P-4-WATER CLOSETS AND FIXTURE
 BRANCHES NOT PERMITED ON WET VENTS PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 10)HUB DRAINS NOT PERMITTED.REVISE TO
 FLOOR DRAIN.
  
 11)SHT.P-4-FLAT DRY VENT NOT PERMITTED
 FOR CAN WASH.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.