| Plan Review Stops For Permit 00080910 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-11-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-27 |
Time |
19:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-27 |
Time |
19:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-11-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-16 |
Time |
19:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-16 |
Time |
19:50 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE F.A.C ONLY THE ARCH/ | | | ENGINEER OF RECORD CAN MAKE CHANGES TO | | | SIGNED AND SEALED PLANS. THIS IS STATE | | | LAW AND VIOLATES 61G16 AND 481 OF | | | F.A.C | | | | | | ALSO PLEASE NOTE THAT THE COPIES OF THE | | | NATIONAL ELECTRIC CODE THAT WERE SUB- | | | -MITTED FOR MY REVIEW WERE OUT OF THE | | | "96" NEC. WE ARE IN THE "99" NEC AND | | | HAVE BEEN SINCE MARCH 1ST OF 2000. | | | PLEASE SEE ALL THE CODE ARTS IN THE"99" | | | FOR MY REFERENCES. | | | | | | PLEASE SUBMIT PLANS WITH ALL THE ABOVE | | | INFORMATION CORRECTED AND DONE BY THE | | | ARCH. OF RECORD. SIGNED, SEALED AND | | | DATED PER F.A.C. 481.221. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 | | | | | | | | | ALSO PLEASE NOTE THAT PLANS ARE STAMPED | | | BY ARCH. THIS IS UNACCEPTABLE PER FS. | | | WET SIGNATURE,RAISED SEALED AND DATED!! | | | 481.221 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-09-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-13 |
Time |
19:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-13 |
Time |
19:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE 210-8-A-6 FOR OUTLETS | | | SERVING KITCHEN COUNTERSPACE. | | | | | | 2)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1. | | | FOR SMOKE DETECTORS INSIDE AND OUTSIDE | | | BEDROOMS AND IN BEDROOM #3 NOW THAT | | | WORK IS BEING DONE IN THERE. | | | | | | 3)NOTE: PLEASE SEE 215-5 FOR ALL THE | | | INFORMATION REQ`D ON LOAD CALCULATIONS/ | | | RISER DIAGRAM ETC. | | | | | | 4)NOTE: PLEASE SEE 230-72 FOR GROUPING | | | OF MAINS. MAINS TO BE GROUPED. | | | | | | 5)NOTE: PLEASE SEE THAT YOU SHOW ON | | | RISER DIAGRAM PANEL BEING EXISTING AND | | | NEW.???? PLEASE CLARIFY. | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. PER | | | 110-9 AND 215-5. | | | | | | 7)NOTE:PLEASE SEE 210-11-C-3 FOR THE | | | REQ`D BATH(S) CIRCUIT(S) TO BE LISTED ON | | | PANEL SCHEULE. | | | | | | 8)NOTE: PLEASE SEE PIPE FILL FOR 1 1/4 | | | SCHED 80 PVC. SEE ALL THE WIRE BEING | | | SHOWN. | | | | | | 9)NOTE: PLEASE SEE 250-50 FOR GROUNDING | | | ELECTRODE SYSTEM. PLEASE SHOW AND INCL- | | | -UDE BLDG.STEEL AND COLD WATER PIPE. | | | | | | 10)NOTE: PLEASE SHOW LOCATION OF NEW | | | PANEL BEING INSTALLED FOR THE ADDITION. | | | | | | 11)NOTE: PLEASE SEE 110-26 FOR CLEARENCE | | | REQ`MENTS IN CLOSET IN MASTER/ALCOVE | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. PLEASE NOTE THAT IF THERE | | | ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-28 |
Time |
16:29 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2000-11-28 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-11-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-15 |
Time |
17:28 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-15 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED; | | | 1.SIZE ALL DUCT ROUND AND DUCTBOARD. | | | 2.SHOW CFM'S FOR EACH DROP. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-08-30 |
Time |
16:41 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-08-30 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED | | | 1.SIZE ALL DUCTS ROUND AND DUCTBOARD. | | | 2.SHOW CFM'S FOR EACH DROP. | | | 3.EXHAUST FAN REQUIRED IN TUB AREA ALSO | | | BOTH FANS TO VENT TO OUTSIDE. | | | 4.SHOW C/U LOCATION. | | | 5.FREON LINES UNDER SLAB OR OVERHEAD? |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-28 |
Time |
16:29 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2000-11-28 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-05 |
Time |
06:54 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-09-05 |
Time |
06:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2000-11-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-11-29 |
Time |
12:26 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE | | | OR SBCCI PRODUCT APPROVALS FOR EXTERIOR | | | WINDOWS AND DOORS PRIOR TO INSTALLATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2000-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-11-17 |
Time |
12:04 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED | | | RESUB | | | | | | 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE | | | OR SBCCI PRODUCT APPROVALS FOR ROOF | | | COVERING MATERIAL, EXTERIOR DOORS AND | | | WINDOWS THAT WILL BE INSTALLED ON NEW | | | ADDITION. | | | | | | 2)PROVIDE PRODUCT APPROVALS, KEY PLAN | | | AND INSTALLATION SCHEDULE WITH TYPE OF | | | ANCHORS BEING USED OR APPLY UNDER A | | | SEPARATE PERMIT. | | | | | | 3)HAVE OWNER OR THEIR AGENT (CONTRACTOR) | | | SIGN THE ENERGY FORMS. | | | | | | 4)HAVE THE ARCHITECT HAND SIGN EACH PAGE | | | OF THE PLANS. | | | | | | 5)PROVIDE SAFETY GLASS IN BATHROOM | | | WINDOWS.97SBC 2405.2 | | | | | | 6)HAVE ARCHITECT CORRECT CHECK HELTA 20 | | | ON SHEET S-1. | | | | | | 7)HAVE DESIGNER OF RECORD PROVIDE | | | ADDITIONAL INFORMATION DETAILING THE | | | CONNECTION OF THE NEW ADDITION TO THE | | | EXISTING STRUCTURE AT FOOTINGS, WALL | | | AND TIE BEAM. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-09-27 |
Time |
07:50 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE | | | OR SBCCI PRODUCT APPROVALS FOR EXTERIOR | | | WINDOWS THAT WILL BE INSTALLED. | | | | | | 2)PROVIDE PRODUCT APPROVALS FOR ROOFING | | | MATERIALS. | | | | | | 3)PROVIDE NEGATIVE AND POSITIVE DESIGN | | | PRESSURES FOR ADDITION WINDOWS. | | | | | | 4)PROVIDE PRODUCT APPROVALS,KEY PLAN AND | | | INSTALLATION SCHEDULE FOR STORM PANELS | | | OR PRODUCT APPROVALS FOR IMPACT | | | RESISTANT WINDOWS. IMPACT PROTECTION IS | | | REQUIRED FOR ALL EXTERIOR GLAZED | | | OPENINGS.CITY AMENDMENTS SEC.1606.4 | | | | | | 5)PROVIDE ENERGY CODE CALCULATIONS | | | INCLUDING MANUAL "J" PER 97 FL ENERGY | | | EFFICIENCY CODE. | | | | | | 6)WET SIGNATURE OF ARCHITECT IS REQUIRED | | | ON DRAWINGS. SIGNATURE STAMP IS NOT | | | ACCEPTABLE. | | | | | | 7)SAFETY GLASS IS REQUIRED IN BATHROOM | | | PER 97SBC SEC 2405.2. | | | | | | 8)PLEASE INDICATE THE LENGTH OF 5/8" | | | ANCHOR BOLTS @ 24"O.C. ON SHEET S-1. | | | | | | 9)SHEET S-1 SHOWS HELTA 20 TRUSS ANCHORS | | | SHOULD THESE BE HETAL 20? PLEASE RECHECK | | | | | | 10)PLEASE PROVIDE CONNECTION DETAILS OF | | | ADDITION TO EXISTING STRUCTURE FOR WALLS | | | FOOTINGS,AND TIE BEAMS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-08-22 |
Time |
10:01 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|