Plan Review Details - Permit 00080866
Plan Review Stops For Permit 00080866
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-10-04 Cont ID  
Sent By lmartine Date 2000-10-04 Time 10:20 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-19 Cont ID  
Sent By lmartine Date 2000-09-19 Time 10:03 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1]PROVIDE COPY OF SURVEY TO DETERMINE
 PROPERTY LINES.
 2]SUBMIT ENERGY EFFICIENCY CALCULATIONS
 2 COPYS SIGNED AND SEALED.
 3]VERIFY REMOVAL OF INTERIOR BLOCK WALL
 IS NON BEARING.
 4]PROVIDE DETAIL FOR INTERIOR WALL[STOP
 ABOVE THE CEILING OR TO BOTTOM OF ROOF
 DECK].
 5]SUBMIT PRODUCT TEST REPORTS FOR ALL
 EXTERIOR GLAZING AND DOORS[ALL NEW
 EXTERIOR GLAZING SHALL BE PROTECTED
 FROM IMPACT].
  
  
  
 REVIEWED BY:
 LUIS MARTIEZ
 561-659-8096
 EXT.8456

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-19 Cont ID  
Sent By dpalmer Date 2000-09-19 Time 11:00 Rev Time 0.00
Received By dpalmer Date 2000-09-19 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 20:18 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 20:18 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
 PLEASE SEE NOTES FOR LOAD CALCULATIONS.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS FOR LOADS OF CONTINUOUS
 LOADS OR LARGEST MOTOR LOADS ECT.
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372
  
 PLEASE SHOW HOW WORK STATIONS ARE BEING
 FED?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-30 Cont ID  
Sent By dpalmer Date 2000-08-30 Time 06:21 Rev Time 0.00
Received By dpalmer Date 2000-08-30 Time 06:21 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH ALL
 BRANCH CIRCUIT #`S SHOWN ON LAYOUT.
 PLEASE SUBMIT A PANEL SCHEDULE TO
 CORRELATE WITH LAYOUT AND BRANCH CIRCUIT
 #`S.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCUALTION
 SHOWING ALL CONTINUOUS LOADS AT 125%
 (LIGHTING)/(SIGNAGE) ECT.
 THE LOAD IS SHOWN AT 200 AMPS? PLEASE
 SHOW LOAD CALCS PER 220. MAIN DISC IS
 RATED FOR 200A.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-18 Cont ID  
Sent By mcarsill Date 2000-08-18 Time 15:14 Rev Time 0.00
Received By mcarsill Date 2000-08-18 Time 14:38 Sent To  
Notes
2001-01-08 00:00:001) NO BUILDING ADDRESS SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 2) INTERIOR FINISHES IN OFFICE AREAS
 TO BE CLASS A,B,OR C. INTERIOR FINISHES
 IN EXITS SHALL BE CLASS A OR B.
 3) WORKSTATIONS WHEN INSTALLED TO
 PROVIDE AT LEAST 44" AISLES.
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-14 Cont ID  
Sent By ndenmark Date 2000-09-14 Time 11:07 Rev Time 0.25
Received By ndenmark Date 2000-09-14 Time 11:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-30 Cont ID  
Sent By ndenmark Date 2000-08-30 Time 15:19 Rev Time 0.33
Received By ndenmark Date 2000-08-30 Time 15:19 Sent To  
Notes
2001-01-08 00:00:00***********DENIED***********************
  
 REQUIRES ENGINEERED DESIGN DRAWINGS W/
 SIGNED RAISED SEAL.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-11-13 Cont ID  
Sent By jleech Date 2000-11-13 Time 07:56 Rev Time 0.33
Received By jleech Date 2000-11-13 Time 07:56 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 SUBJECT TO FLOW TEST AT FINAL INSPECTION
 BY PLUMBING INSPECTOR.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-23 Cont ID  
Sent By pschmitz Date 2000-09-23 Time 11:16 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2000-09-19 Cont ID  
Sent By tlarge Date 2000-09-19 Time 10:02 Rev Time 1.00
Received By pschmitz Date 2000-09-19 Time 10:01 Sent To  
Notes
2001-01-08 00:00:00ENTERED IN ERROR.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-16 Cont ID  
Sent By tlarge Date 2000-09-16 Time 10:35 Rev Time 1.00
Received By pschmitz Date 2000-09-16 Time 10:18 Sent To  
Notes
2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SECS.4.1.3.(10)(A),4.15.PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 2)ACCESSIBLE TOILET STALLS WITHIN THE
 RESTROOM SHALL COMPLY W/FACBC SEC.4.17.3
 FOR SIZE.
  
 3)SINK IN LOUNGE SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 4)SUBMIT A SANITARY RISER DIAGRAM THAT
 COMPLIES W/SPC IN ALL RESPECTS.SEE
 BELOW:
 A)WATER CLOSETS NOT PERMITTED ON WET
 VENTS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 B)FLAT,DRY VENTS ARE NOT PERMITTED PER
 SPC SEC.906.2.1.
  
 C)MOP SINK NOT PROPERLY VENTED.SPC SEC.
 906.2.1.
  
 D)FLOOR DRAINS SHALL BE EQUIPPED W/TRAPS
 PER SPC 901.2.
  
 E)WATER CLOSETS ARE NOT PROPERLY VENTED.
 SPC 901.2,COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.3.
  
 5)MIN.SIZE OF DRAINAGE SYSTEM UNDER-
 GROUND SHALL BE 2"PER SPC SEC.714.4.
  
 6)OVER 2 FIXTURES ARE SUPPLIED BY 1/2"
 C.W.(SEE MOP SINK AREA.)PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.607.7.
  
 7)COMPILE SHEETS INTO 2 COMPLETE SETS OF
 PLANS AND VOID OLD SHEETS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-20 Cont ID  
Sent By tlarge Date 2000-08-20 Time 10:52 Rev Time 0.50
Received By tlarge Date 2000-08-20 Time 10:46 Sent To  
Notes
2001-01-08 00:00:001)ALL PUBLIC AND COMMON AREA TOILET
 ROOMS SHALL BE FULLY ACCESSIBLE PER
 FACBC SEC.4.1.3.(11).(SEE TOILET ROOM AT
 RECEPTION AREA.)
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SECS.4.1.3(10)(A),4.15.PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 3)FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.1.1.
  
 4)WATER HEATER SHALL BE READILY ACCESS-
 IBLE PER SPC SEC.501.7.SUPPLY PERMANENT
 LADDER OR RELOCATE HEATER TO FLOOR.
  
 5)ACCESSIBLE TOILET STALLS WITHIN THE
 RESTROOM SHALL COMPLY W/FACBC SEC.4.17.3
 (MIN.SIZE TO BE 83" IF LAV.IS ADJACENT
 TO WATER CLOSET.FACBC SEC.4.22.4.
  
 6)SINK IN LOUNGE SHALL COMPLY W/FACBC
 SECS.4.24.1-4.24.7.
  
 7)REMOVE TRAP FROM PAN DRAIN AND PIPE
 DRAIN TO APPROVED LOCATION PER SPC SEC.
 507.8.2.
  
 8)RELIEF VALVE SHALL NOT DRAIN INTO PAN
 PER COUNTYWIDE AMENDMENTS SEC.507.8.4.
  
 9)SUBMIT A REVISED SANITARY RISER
 DIAGRAM THAT COMPLIES W/SPC IN ALL
 RESPECTS.THERE ARE TOO MANY CODE VIOLAT-
 IONS ON THE DRAWING TO LIST.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.