| Plan Review Stops For Permit 00080866 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-10-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-10-04 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-19 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | 1]PROVIDE COPY OF SURVEY TO DETERMINE | | | PROPERTY LINES. | | | 2]SUBMIT ENERGY EFFICIENCY CALCULATIONS | | | 2 COPYS SIGNED AND SEALED. | | | 3]VERIFY REMOVAL OF INTERIOR BLOCK WALL | | | IS NON BEARING. | | | 4]PROVIDE DETAIL FOR INTERIOR WALL[STOP | | | ABOVE THE CEILING OR TO BOTTOM OF ROOF | | | DECK]. | | | 5]SUBMIT PRODUCT TEST REPORTS FOR ALL | | | EXTERIOR GLAZING AND DOORS[ALL NEW | | | EXTERIOR GLAZING SHALL BE PROTECTED | | | FROM IMPACT]. | | | | | | | | | | | | REVIEWED BY: | | | LUIS MARTIEZ | | | 561-659-8096 | | | EXT.8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-19 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-19 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-09-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-13 |
Time |
20:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-13 |
Time |
20:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | | FROM FIRST REVIEW WERE ADDRESSED. | | | PLEASE SEE NOTES FOR LOAD CALCULATIONS. | | | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS FOR LOADS OF CONTINUOUS | | | LOADS OR LARGEST MOTOR LOADS ECT. | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 | | | | | | PLEASE SHOW HOW WORK STATIONS ARE BEING | | | FED? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-30 |
Time |
06:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-30 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH ALL | | | BRANCH CIRCUIT #`S SHOWN ON LAYOUT. | | | PLEASE SUBMIT A PANEL SCHEDULE TO | | | CORRELATE WITH LAYOUT AND BRANCH CIRCUIT | | | #`S. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCUALTION | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING)/(SIGNAGE) ECT. | | | THE LOAD IS SHOWN AT 200 AMPS? PLEASE | | | SHOW LOAD CALCS PER 220. MAIN DISC IS | | | RATED FOR 200A. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-18 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-18 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO BUILDING ADDRESS SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS | | | TO COMPLY WITH CITY CODE REQUIREMENTS. | | | 2) INTERIOR FINISHES IN OFFICE AREAS | | | TO BE CLASS A,B,OR C. INTERIOR FINISHES | | | IN EXITS SHALL BE CLASS A OR B. | | | 3) WORKSTATIONS WHEN INSTALLED TO | | | PROVIDE AT LEAST 44" AISLES. | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-14 |
Time |
11:07 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-09-14 |
Time |
11:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-30 |
Time |
15:19 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-30 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | | | | REQUIRES ENGINEERED DESIGN DRAWINGS W/ | | | SIGNED RAISED SEAL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-11-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-13 |
Time |
07:56 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-13 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO; | | | SUBJECT TO FLOW TEST AT FINAL INSPECTION | | | BY PLUMBING INSPECTOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-09-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-09-23 |
Time |
11:16 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-19 |
Time |
10:02 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2000-09-19 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ENTERED IN ERROR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-09-16 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-16 |
Time |
10:35 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2000-09-16 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC | | | SECS.4.1.3.(10)(A),4.15.PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 2)ACCESSIBLE TOILET STALLS WITHIN THE | | | RESTROOM SHALL COMPLY W/FACBC SEC.4.17.3 | | | FOR SIZE. | | | | | | 3)SINK IN LOUNGE SHALL COMPLY W/FACBC | | | SEC.4.24.1-4.24.7. | | | | | | 4)SUBMIT A SANITARY RISER DIAGRAM THAT | | | COMPLIES W/SPC IN ALL RESPECTS.SEE | | | BELOW: | | | A)WATER CLOSETS NOT PERMITTED ON WET | | | VENTS.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 911.1.1. | | | | | | B)FLAT,DRY VENTS ARE NOT PERMITTED PER | | | SPC SEC.906.2.1. | | | | | | C)MOP SINK NOT PROPERLY VENTED.SPC SEC. | | | 906.2.1. | | | | | | D)FLOOR DRAINS SHALL BE EQUIPPED W/TRAPS | | | PER SPC 901.2. | | | | | | E)WATER CLOSETS ARE NOT PROPERLY VENTED. | | | SPC 901.2,COUNTYWIDE AMENDMENTS TO SPC | | | SEC.911.1.3. | | | | | | 5)MIN.SIZE OF DRAINAGE SYSTEM UNDER- | | | GROUND SHALL BE 2"PER SPC SEC.714.4. | | | | | | 6)OVER 2 FIXTURES ARE SUPPLIED BY 1/2" | | | C.W.(SEE MOP SINK AREA.)PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.607.7. | | | | | | 7)COMPILE SHEETS INTO 2 COMPLETE SETS OF | | | PLANS AND VOID OLD SHEETS.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-20 |
Time |
10:52 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-20 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)ALL PUBLIC AND COMMON AREA TOILET | | | ROOMS SHALL BE FULLY ACCESSIBLE PER | | | FACBC SEC.4.1.3.(11).(SEE TOILET ROOM AT | | | RECEPTION AREA.) | | | | | | 2)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC | | | SECS.4.1.3(10)(A),4.15.PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 3)FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC SEC.409.1.1. | | | | | | 4)WATER HEATER SHALL BE READILY ACCESS- | | | IBLE PER SPC SEC.501.7.SUPPLY PERMANENT | | | LADDER OR RELOCATE HEATER TO FLOOR. | | | | | | 5)ACCESSIBLE TOILET STALLS WITHIN THE | | | RESTROOM SHALL COMPLY W/FACBC SEC.4.17.3 | | | (MIN.SIZE TO BE 83" IF LAV.IS ADJACENT | | | TO WATER CLOSET.FACBC SEC.4.22.4. | | | | | | 6)SINK IN LOUNGE SHALL COMPLY W/FACBC | | | SECS.4.24.1-4.24.7. | | | | | | 7)REMOVE TRAP FROM PAN DRAIN AND PIPE | | | DRAIN TO APPROVED LOCATION PER SPC SEC. | | | 507.8.2. | | | | | | 8)RELIEF VALVE SHALL NOT DRAIN INTO PAN | | | PER COUNTYWIDE AMENDMENTS SEC.507.8.4. | | | | | | 9)SUBMIT A REVISED SANITARY RISER | | | DIAGRAM THAT COMPLIES W/SPC IN ALL | | | RESPECTS.THERE ARE TOO MANY CODE VIOLAT- | | | IONS ON THE DRAWING TO LIST.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|