Plan Review Details - Permit 00080832
Plan Review Stops For Permit 00080832
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-21 Cont ID  
Sent By drunnels Date 2000-09-21 Time 11:10 Rev Time 1.00
Received By drunnels Date 2000-09-18 Time 09:49 Sent To  
Notes
2001-01-08 00:00:00PROVISO
 STOREFRONTS UNDER SEPERATE PERMIT
 SIGNS AND AWNING UNDER SEPERATE PERMITS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-24 Cont ID  
Sent By drunnels Date 2000-08-24 Time 06:58 Rev Time 1.00
Received By drunnels Date 2000-08-24 Time 06:58 Sent To  
Notes
2001-01-08 00:00:00 
 1. SHEET A4.0-TOTAL SQUARE FOOTAGE IS
 2065, AREA CALCULATIONS INDICATE 1426 ?
 2. OCCUPANCY COUNT ON SHEET A1.0 MUST BE
 CORECTED TO REFLECT CORECT OCCUPANCY
 LOAD.
 EXAMPLE: SEATING IS SHOWN ON A1.0 FOR
 11 PEOPLE, ACTUAL SEATING COUNT IS 32
 PEOPLE.
 3.SHEET A1.0- 1997 SBC SECTION 1004.1.2
 TWO MEANS OF EGRESS REQUIRED, CORRECTED
 OCCUPANCY COUNT-SEATING 32+21+2=55 TOTAL
 4.EXIT COURIDOR TO BE A MIMIMIN 44"
 1997 SBC TABLE 1004
 5.REAR EXIT DOOR TO COMPLY WITH 1997 SBC
 SECTION 1003.2 AND ASSOCIATED SUBSECTION
 6.PLANS INDICATE LOCATION IN BROWERD CO
 CORRECT PLANS TI REFLECT PALM BEACH CO.
 7.PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT WINDOWS AND DOORS FOR STORE-
 FRONT/METRO DADE COUNTY OR SBCCI
 8.FLORIDA ENERGY SHEETS MUST BE COMPLETE
 AND BE SIGNED BY OWNER/AGENT.
 9.SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION.
 10.DEMIZING WALL MUST BE COMPLETED ON
 BOTH SIDES PRIOR TO C.O. BEING ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-18 Cont ID  
Sent By dpalmer Date 2000-09-18 Time 15:58 Rev Time 0.00
Received By dpalmer Date 2000-09-18 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-28 Cont ID  
Sent By dpalmer Date 2000-08-28 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2000-08-28 Time 16:50 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING
 DETAIL FOR TRANSFORMER BEING INSTALLED.
 PLEASE SEE 450-21-B FOR INSTALLATION
 DETAILS AND REQ`MENTS.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER ART;220 OF NEC. CLARIFY LOAD CALCS
 FOR TRACK LIGHTING PER 220-12-B. PLEASE
 SHOW SQ FT ON LOAD CALCS AND ALL CONTIN-
 -UOUS LOADS AT 125%.
 PLEASE SHOW LOAD ON LINE SIDE OF MAIN
 TRANSFORMER FEEDING STARBUCKS.
 PROVIDE CONDUCTOR SIZES. 215-5
  
 3)NOTE:PANEL "A" IS REQ`D TO BE MCB ON
 LOAD SIZE OF TRANSFORMER AS IT IS A
 SEPARATELY DERIVED SYSTEM.
  
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-09-21 Cont ID  
Sent By mcarsill Date 2000-09-21 Time 10:16 Rev Time 0.00
Received By mcarsill Date 2000-09-21 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-09-18 Cont ID  
Sent By mcarsill Date 2000-09-18 Time 09:55 Rev Time 0.00
Received By mcarsill Date 2000-09-18 Time 09:54 Sent To  
Notes
2001-01-08 00:00:001) PREVIOUS COMMENTS FROM ORIGINAL PLAN
 REVIEW NOT ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-18 Cont ID  
Sent By mcarsill Date 2000-08-18 Time 15:50 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) AWNING TO BE FIRE RETARDANT ON
 EXTERIOR OF BUILDING.
 2) DEFINE OUTDOOR SEATING AREA.THIS
 PROPOSED SEATING SHALL NOT INTERFERE
 WITH FIRE RESCUE ACCESS TO PLAZA FIRE
 LANE.
 3) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 4) PLEASE EXPLAIN EXITING ARRANGEMENT
 TO THIS OFFICE.
 5) PROVIDE FIRE EXTINGUISHERS.
 6) NO FIRE SPRINKLER DRAWINGS CONTAINED
 WITH PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-15 Cont ID  
Sent By ndenmark Date 2000-09-14 Time 13:16 Rev Time 0.50
Received By ndenmark Date 2000-09-14 Time 13:16 Sent To  
Notes
2001-01-08 00:00:00INCOMPLETE PLANS MISSING M-1.0
 M-2.0 REVISIONS OK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-22 Cont ID  
Sent By ndenmark Date 2000-08-22 Time 12:26 Rev Time 0.50
Received By ndenmark Date 2000-08-22 Time 12:26 Sent To  
Notes
2001-01-08 00:00:00***********DENIED**********************
  
 1.OUTSIDE AIR SUPPLIED DOES NOT MEET
 ASHRAE 62-89 (34PERSON X 20CFM EA =680CF
 M)PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE EXHAUST FAN CAPACITY IN CFM
 NOTE:
 NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM AREA
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TIED TO HORN AND STROBE FOR NOTI-
 FICATION PER NFPA 90A 4-4.4

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-14 Cont ID  
Sent By tlarge Date 2000-09-14 Time 20:58 Rev Time 0.65
Received By tlarge Date 2000-09-14 Time 20:58 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
 THIS CHAOTIC MESS OF BLUEPRINTS SHALL
 BE ASSEMBLED INTO COMPLETE SETS OF PLANS
 FOR SUBMITTAL AND PROPER PLAN REVIEW.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-18 Cont ID  
Sent By tlarge Date 2000-08-18 Time 07:21 Rev Time 1.50
Received By tlarge Date 2000-08-18 Time 07:21 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT 2 COMPLETE SETS OF PLUMBING
 DRAWINGS FOR REVIEW.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 2)SIZE ALL THE VENTS ON THE ISOMETRIC.
 COMPLY W/SPC TABLE 920.2.
  
 3)SUBMIT SQUARE FEET OF HABITABLE FLOOR
 SPACE.SEE SPC 407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 4)NOTE TOTAL NUMBER OF SEATS PROVIDED TO
 ENSURE COMPLIANCE W/SPC TABLE 407 FOR
 MINIMUM PLUMBING FIXTURES.
  
 5)WAINSCOTING TO 4' REQD.IN TOILET ROOMS
 PER SBC SEC.1204.2.
  
 6)SHT.A6.3-T.P.DISPENSER SHALL BE
 MOUNTED 19"TO CENTER,NOT BOTTOM PER
 FACBC FIG.29.
  
 7)ONLY 2 FIXTURES PERMITTED TO BE
 SUPPLIED BY 1/2"CW LINE.COUNTYWIDE AMEND
 MENTS TO SPC SEC.607.7
  
 8)RELIEF LINE CANNOT DRAIN INTO PAN PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.4
  
 9)SUBMIT WAIVER FROM CITY OF WPB
 UTILITIES FOR DELETION OF CONNECTION TO
 GREASE INTERCEPTOR.CONTACT R.COMPO AT
 561-835-7423.
  
 10)SIZE ALL PLBG.VENTS ON THE DRAWING.
  
 11)BACK TO BACK WATER COSETS SHALL BE
 VENTED PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.