Plan Review Details - Permit 00080757
Plan Review Stops For Permit 00080757
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-01 Cont ID  
Sent By dpalmer Date 2000-09-01 Time 10:38 Rev Time 0.00
Received By dpalmer Date 2000-09-01 Time 10:38 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW SMOKE DETECTORS
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 AND ON EACH LEVEL OF MULTI-LEVEL RES.
  
 2)NOTE: PLEASE PROVIDE MORE INFORMATION
 ON SERVICE AND LOAD CALCULATION PER
 220-3-C-1
  
 3)NOTE: PLEASE SHOW BATH(S) CIRCUITS PER
 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH\\
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-26 Cont ID  
Sent By jleech Date 2000-08-26 Time 09:58 Rev Time 0.50
Received By jleech Date 2000-08-26 Time 09:58 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.SHOW ALL DUCT WORK NEW AND EXISTING.
 2.SIZE RETURN AIR, SUPPLY AIR, AND
 DROP SIZES.
 3.LIST CFM'S FOR EACH DROP.
 4.LIST EQUIPMENT INFOMATION,MODEL # ETC
 5.SHOW CONDENSOR LOCATION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-19 Cont ID  
Sent By jleech Date 2000-08-19 Time 11:50 Rev Time 0.50
Received By jleech Date 2000-08-19 Time 11:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-25 Cont ID  
Sent By jgomez Date 2000-09-25 Time 15:51 Rev Time 3.00
Received By jgomez Date 2000-09-25 Time 15:51 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-TAKE DRAWINGS TO PALM BEACH COUNTY TO
 VERIFY IF IMPACT FEES ARE DUE OR NOT.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-ENTRY DOORS TO HAVE 32" MINIMUM CLEAR
 OPENING (ONE LEAF). TABLE 1004 SBC/97.
 3-SPECIFY SAFETY GLASS AS REQUIRED. SEE
 PLANS. SECTION 2405.2 SBC 1997.
 4-PROVIDE AREA TABULATION FOR EXISTING
 AND NEW AREA.
 5-PROVIDE ENERGY CALCULATIONS.
 6-PROVIDE UPLIFT CALCULATIONS AT ROOF
 FRAMING PLAN. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 7-THE STRUCTURAL ENGINEER FIRM'S LOGO IS
 NOT INCORPORATED ON ALL STRUCTURAL
 DRAWINGS. WHY?. NEED THIS INFORMATION
 ON ALL DRAWINGS SIGNED AND SEALED BY
 THE STRUCTURAL ENGINEER. FLORIDA
 STATUTES CHAPTER 471.
 8-PROVIDE A COMPLETE WINDOW SCHEDULE IN
 ORDER TO VERIFY EGRESS REQUIREMENTS.
 9-PROVIDE ATTIC ACCESS AT BEDROOM #4 AND
 MASTER BEDROOM ROOF.SEC 2309.6 SBC/97.
 10-EXISTING ROOF TRUSSES ARE GOING TO BE
 USED AS FLOOR TRUSSES. USUALLY ROOF
 TRUSSES ARE DESIGNED FOR A DIFFERENT
 LOADING THAN FLOOR TRUSSES. ENGINEER
 TO PROVIDE A COMPLETE ENGINEERING
 ANALYSIS TO DEMONSTRATE HOW THESE
 TRUSSES CAN SUPPORT THE NEW LOADING
 IMPOSSED. SEC 104.2.2 CITY AMENDMENTS.
 11-CLEARLY SPECIFY ATTIC VENTIALTION.
 SECTION 2309.7 SBC 1997.
 12-PROVIDE CURRENT PRODUCT APPROVAL FROM
 DADE COUNTY OR SBCCI FOR:
 -ROOF TILE (CLEARLY HIGHLIGHT SPECIFIC
 ATTACHMENT METHOD AND COMPONENTS TO
 BE USED IN THIS PROJECT)
 -ENTRY "INSWING" DOORS.
 -WINDOW MULLIONS APPROVED TO BE USED
 WITH MISSILE IMPACT RESISTANT WINDOWS.
 13-SEE PLANS FOR ADDITIONAL COMMENTS,
 INCLUDING THOSE BY THE OTHER TRADES.
  
  
  
 NOTES:
  
 -PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTION ARE DONE TO ORIGINAL DWGS,
 IN ORDER TO EXPEDITE THE REVIEW
 PROCESS.
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT
 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-17 Cont ID  
Sent By gjoyce Date 2000-08-17 Time 11:16 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***