| Plan Review Stops For Permit 00080709 |
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-08-22 |
Time |
16:06 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO FOR CONDITION OF APPR.PES | | | APPLICABLE TAB FOR PE FROM MFG. | | | END OF COMMENTS PES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-17 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-17 |
Time |
06:24 |
Rev Time |
0.33 |
| Received By |
pschmitz |
Date |
2000-08-17 |
Time |
06:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT COPY OF APPLICABLE GAS SIZING | | | TABLE FOR THE P.E.& GALV.PIPE.SGC 305.4. | | | | | | PLANS SHOW 3/4"PIPE FROM METER SUPPLYING | | | SYSTEM.COMPLY W/SGC TABLE 305.4(A)FOR | | | APPLICABLE SIZE.(1 1/4" IS INADEQUATE). | | | | | | PLANS NOTE INTERIOR PIPING AS 102'. | | | LENGTHS ON RISER DON'T CORRELATE.CLARIFY | | | | | | NOTE:A COPY OF THE APPLICABLE SIZING | | | TABLE FOR EACH TYPE OF PIPE SHALL BE | | | SUBMITTED W/PLANS.SEE ATTACHED. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
|