Plan Review Details - Permit 00080709
Plan Review Stops For Permit 00080709
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-22 Cont ID  
Sent By pschmitz Date 2000-08-22 Time 16:06 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO FOR CONDITION OF APPR.PES
 APPLICABLE TAB FOR PE FROM MFG.
 END OF COMMENTS PES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 06:24 Rev Time 0.33
Received By pschmitz Date 2000-08-17 Time 06:24 Sent To  
Notes
2001-01-08 00:00:00SUBMIT COPY OF APPLICABLE GAS SIZING
 TABLE FOR THE P.E.& GALV.PIPE.SGC 305.4.
  
 PLANS SHOW 3/4"PIPE FROM METER SUPPLYING
 SYSTEM.COMPLY W/SGC TABLE 305.4(A)FOR
 APPLICABLE SIZE.(1 1/4" IS INADEQUATE).
  
 PLANS NOTE INTERIOR PIPING AS 102'.
 LENGTHS ON RISER DON'T CORRELATE.CLARIFY
  
 NOTE:A COPY OF THE APPLICABLE SIZING
 TABLE FOR EACH TYPE OF PIPE SHALL BE
 SUBMITTED W/PLANS.SEE ATTACHED.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.