Plan Review Details - Permit 00080686
Plan Review Stops For Permit 00080686
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-08-25 Cont ID  
Sent By dpalmer Date 2000-08-25 Time 06:56 Rev Time 0.00
Received By dpalmer Date 2000-08-25 Time 06:56 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: PLEASE SUBMIT WIRE SIZES FOR
 ALL SERVICE CONDUCTORS.METER CAN TO
 PANEL INSIDE, SIZES OF PIPE,SIZE OF
 PANEL INSIDE.
 ALSO PLEASE SUBMIT PANEL SCHEDULE AND
 IF THERE ARE ANY NEW CIRCUIT(S) PLEASE
 SHOW. SUBMIT LOAD CALCULATION.
 ALL PER 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE SERVICE CHANGE FINAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372