Plan Review Details - Permit 00080656
Plan Review Stops For Permit 00080656
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-16 Cont ID  
Sent By mcarsill Date 2000-08-16 Time 09:59 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) ALL DEEP FAT FRYERS ARE TO HAVE
 HIGH-LIMIT CONTROLS AS PER NFPA 96,
 SECTION 9-2.
 2) PROVIDE SEPARATE PLANS AND PERMIT
 FOR WET CHEMICAL EXTINGUISHING SYSTEM.
 NO DRY-CHEMICAL EXTINGUISHING SYSTEMS
 WILL BE ALLOWED.
 3) PLEASE DEFINE TYPE OF COMBUSTIBLE
 MATERIAL DESCRIBED ON PLAN.
 4) TEST AND BALANCE REPORT REQUIRED AT
 TIME OF FINAL.
 5) HOOD, DUCT AND EXTINGUISHING SYSTEM
 SUBJECT TO FINAL INSPECTION BY
 MECHANICAL AND FIRE RESCUE DIVISIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-17 Cont ID  
Sent By ndenmark Date 2000-08-17 Time 14:39 Rev Time 0.33
Received By ndenmark Date 2000-08-17 Time 14:39 Sent To  
Notes
2001-01-08 00:00:00FIRE DEPT COMMENTS APPLY TO THIS REVIEW