Plan Review Details - Permit 00080584
Plan Review Stops For Permit 00080584
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-08-24 Cont ID  
Sent By jwitmer Date 2001-08-24 Time 08:48 Rev Time 1.00
Received By jwitmer Date 2001-08-24 Time 08:47 Sent To  
Notes
2001-08-24 00:00:00REVISION #2/3 8/24/01JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-06-04 Cont ID  
Sent By jwitmer Date 2001-06-04 Time 14:12 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-04 00:00:00REVISION # 1 MAY 30/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-08 Cont ID  
Sent By jwitmer Date 2001-02-08 Time 13:35 Rev Time 3.00
Received By jwitmer Date 2001-02-08 Time 10:55 Sent To  
Notes
2001-02-08 00:00:00PROVISO:
 1)- THE 2ND FLOOR WILL BE USED FOR
 "STORAGE" TAKING EXCEPTION TO #2 FOR
 STORAGE UNDER FL SS 553.509, CHANGE OF
 OCCUPANCY WILL REQUIRE VERTICAL ACCESS-
 IBILTY.
 2)- SBC 709.5.2.2 STRUCTURAL STEEL
 BEAMS & GIRDERS REQUIRE FIRE RESISTANT
 MATERIALS, PROVIDE PRODUCT INFORMATION.
 3)- PAY COUNTY IMPACT FEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-19 Cont ID  
Sent By jwitmer Date 2001-01-19 Time 15:13 Rev Time 3.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-19 00:00:00BUILDING PLAN REVIEW:
 1)- SBC 104.2.2- ADDITIONAL INFO
 SHEET A-1 SHOWS A STAIRWAY AT THE BACK
 OF THE EXISTING BUILDING ON THE SECOND
 FLOOR PLAN, IS THIS STAIR BEING DELETED?
 IF NOT IT BLOCKS THE EGRESS ON THE
 EGRESS ON THE FIRST FLOOR CORRIDOR. THE
 SAME STAIRWAY SHOWS UP ON VARIOUS PLANS.
 2)- SHEET A-3 SECTION "CC" SHOWS AN
 ADJACACEENT 2 STORY EXISTING WALL. THE
 DETAIL CALLS OUT FOR FOR UL DES U473 TO
 BE INSTALLED ATOP OF A STEEL BEAM. HOW
 WILL THE CEMENTITIOUS BACKER BOARD BE AT
 TACHED? THE SECOND QUESTION IS HOW WILL
 THE BOTTOM OF THE CEMENTITIOUS BOARD BE
 SEALED FOR FIRE PROOFING? THE THIRD ITEM
 IN THIS DETAIL IS A NOTE ON INSTALLING
 FIRE MASTER BOARD UL 723 IN THE UL LIST-
 ING BOOK X723 LIST A SPRAY TYPE OF INSUL
 ATION, WE NEED MORE INFORMATION FOR THIS
 2 HR RATING?
 3)- SHEET RA-6 SHOWS A DETAIL ON THE
 1-HR RATED ACOUSTIC TILE CEILING, PLEASE
 PROVIDE INFORMATION ON THE TILE, FRAME
 AND TILE LOCKING OR HOLD DOWN.
 4)- NOTE: THE PLANS INDICATE THAT THE
 SECOND FLOOR WILL BE USED FOR STORAGE
 PURPOSES ONLY, TAKING THE EXCEPTION OF
 NO ELEVATOR REQUIRED BY THE FL. ACCESS-
 IBILITY CODE. IF THE TENANT OCCUPANCY
 USAGE CHANGES TO A HABITABLE SPACE A
 ELEVATOR WOULD BE REQUIRED.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-07 Cont ID  
Sent By drunnels Date 2000-11-07 Time 08:43 Rev Time 3.00
Received By drunnels Date 2000-11-06 Time 14:18 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT DETAILS SHOWING ELECTRICAL
 ROOM COMPLYING TO SECTION 1006&1007
 SBC 1997 EDITION
 2.SUBMIT DETAILS SHOWING STAIR TO WORK/
 LOFT COMPLYING TO SECTION 1007 1997 SBC
 3.SUBMIT DRAWING SHOWING BUILDING
 COMPLYING TO THE 1997 FLORIDA
 ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION.
 4.SUBMIT UL LISTING OF 1-HR RATED
 DEMISING PARITION.
 5.SUBMIT DRAWING SHOWING ARRANGEMENT AND
 NUMBER OF EXITS TO COMPLY WITH SECTION
 1004 1997 SBC
 6.SUBMIT PRODUCT APPROVALS FOR WINDOWS,
 DOORS AND ROOF COVERINGS/METRO DADE CO./
 OR SBCCI.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2001-02-12 Cont ID  
Sent By dpalmer Date 2001-02-12 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2001-02-12 Time 10:06 Sent To  
Notes
2001-02-12 00:00:0002/12/01 ARCH LETTER ELEC TO BE REVIEWED
 UNDER A SEPERATE PLANS, PERMIT & FEES.
 J. WITMER
 LETTER FROM ARCH. ELEC PERMIT TO BE
 ISSUED UNDER A SEPERATE PLANS, PERMIT
 & FEES. J. WITMER
 ELETRICAL PULLED FROM PLANS BY ARCH OF
 RECORD.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-02-12 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 19:11 Sent To  
Notes
2001-01-22 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
 THIS INFORMATION WAS GIVEN ON SHEET E-4
 ON LAST SUBMITTAL BUT IS NOT SHOWN ON
 SHEET RE-4A ON THIS SUBMITTAL. PLEASE DO
 SO.
  
 2)NOTE: PLEASE NOTE THAT UNDER F.A.C,
 SEC 481-.221 ALL HAND WRITTEN CHANGES ON
 PLANS ARE TO BE SIGNED AND DATED BY
 THEARCH/OF RECORD. PLEASE SEE E- SHEETS
 WITH BRANCH CIRCUIT #`S HAND WRITTEN
 IN. PLEASE REDRAW PLANS BEFORE
 RE-SUBMITTAL
 PER COUNTY-WIDE ADMINISTRATIVE CODE SEC
 104.2.1 AND 104.2.7
  
 3)NOTE: PLEASE TRANSFER ATTACHED SHEETS
 CONTAINING LOAD CALCULATIONS AND PANEL
 SCHEDULES OF PANELS "A" AND "B". PLEASE
 HAVE THESE DRAWN ON PLANS AS ATTACHED
 SHEETS SEEM TO GET TORN OFF DURING
 CONSTRUCTION. IF THOSE ATTACHED SHEETS
 ARE PREPARED BY SOMEONE ELSE THEN UNDER
 C.A.C THEY ARE TO BE SIGNED ALSO. SEC
 104.2.1.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-80096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2001-02-12 Cont ID  
Sent By dpalmer Date 2000-11-02 Time 16:05 Rev Time 0.00
Received By dpalmer Date 2000-11-02 Time 17:15 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE PROVIDE BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE WITH PANEL
 SCHEDULES.
  
 2)NOTE:PLEASE SEE RISER THIS SHOWS PANEL
 "A" FEEDING PANEL "B" YET PANEL SCHEDULE
 -S SHOW MDP FEEDING PANELS A&B ???
 PLEASE CLARIFY.
 PLEASE SEE THAT YOU SHOW A 100A MAIN ON
 RISER FUSED AT 100AMPS? YET YOU SHOW A
 PANEL SCHEDULE?? PLEASE CLARIFY.
  
 3)NOTE; PLEASE SEE PLAN PANEL"A"
 DOESN'T SHOW FEEDING PANEL "B".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mcarsill Date 2001-08-22 Time 16:57 Sent To  
Notes
2001-08-22 00:00:001) PLEASE BE ADVISED THAT THIS LOCATION
 IS LOCATED WITHIN THE CITY FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY.
 2) BALCONY GUARDS AND HANDRAIL TO
 COMPLY WITH THE REQUIREMENTS OF NFPA
 101, THE LIFE SAFETY CODE, 1985 EDITION.
 A) GUARDS MUST BE AT LEAST 42" HIGH
 B) MUST RESIST A 4" SPHERE SINCE THE
 STANDARD BUILDING CODE, 1997 EDITION IS
 MORE RESTRICTIVE THAN THE 1985 EDITION
 OF THE LIFE SAFETY CODE.
 C) MUST BE CONSTRUCTED FOR PRESCRIPTIVE
 REQUIREMENTS OF HORIZONTAL LOADS.
 3) HANDRAILS REQUIRED ON BOTH SIDES OF
 STAIR.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-02-08 Cont ID  
Sent By mcarsill Date 2001-02-08 Time 15:21 Rev Time 0.00
Received By mcarsill Date 2001-02-08 Time 15:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-01-30 Cont ID  
Sent By mcarsill Date 2001-01-30 Time 13:40 Rev Time 0.00
Received By mcarsill Date 2001-01-30 Time 13:40 Sent To  
Notes
2001-01-30 00:00:001) BUILDING ADDRESS REQUIRED ON BUILDING
 IN ACCORDANCE WITH CITY CODE
 REQUIREMENTS.
 2) PLEASE INDICATE MAXIMUM TRAVEL
 DISTANCES TO REACH EXITS. IT IS PRESUMED
 THAT THE BUILDING DOES NOT CONTAIN FIRE
 SPRINKLER PROTECTION.
 3) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION ON WALLS AND CEILINGS.
 4) NO DOOR SCHEDULE COULD BE LOCATED
 IN PLANS.
 5) ALL STAIRS TO COMPLY WITH NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION.
 6) SEVERAL VOIDED SHEETS CONTAINED IN
 PLANS. ALSO NOTES MADE TO PLANS THAT ARE
 NOT DATED OR SIGNED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-11-07 Cont ID  
Sent By mcarsill Date 2000-11-07 Time 09:11 Rev Time 0.00
Received By mcarsill Date 2000-11-07 Time 09:10 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE MORE DETAILS FOR THE
 WORK/LOFT AREA.
 2) PLEASE PROVIDE A LIFE SAFETY PLAN TO
 EXPLAIN THE EXITING ARRANGEMENT.
 OCCUPANT LOAD CALCULATIONS ARE TO BE
 PROVIDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-25 Cont ID  
Sent By rturnque Date 2000-10-25 Time 15:42 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001. THE TRAVEL DISTANCE FROM THE MOST
 REMOTE LOCATION OF THE 2ND FLOOR EXCEED
 THE TRAVEL DISTANCE REQUIREMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-02-06 Cont ID  
Sent By ndenmark Date 2001-02-06 Time 12:02 Rev Time 0.50
Received By ndenmark Date 2001-02-06 Time 12:02 Sent To  
Notes
2001-02-06 00:00:00ARCHITECT J. SAUNDERS SAID VOID
 MECHANICAL PERMIT. OWNERS MECH
 CONTRACTOR WILL SUBMIT PLANS AT TIME OF
 NEW MECHANICAL PERMIT APPLICATION AND
 OWNER IS AWARE THAT ADDITIONAL FEES
 WILL BE DUE AT THAT TIME. GENERAL
 CONTRACTOR NOTIFIED THAT MECHANICAL WAS
 BEING PULLED FROM THIS PERMIT AT THIS
 TIME.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-01-29 Cont ID  
Sent By ndenmark Date 2001-01-29 Time 14:34 Rev Time 0.50
Received By ndenmark Date 2001-01-29 Time 14:33 Sent To  
Notes
2001-01-29 00:00:00*************DENIED*********************
 1. SUBMIT DRAWINGS WHERE THE MECHANICAL
 ELECTRICAL AND ARCHITECTURAL MATCH IN
 USE AND LAYOUT. UNABLE TO REVIEW UNTIL
 DRAWINGS MATCH.
 2. PROVIDE INFORMATION ON EQUIPMENT
 INDICATING LOCATION AND TYPE. PROVIDE
 CURB INFO IF RTU OR PROVIDE PENETRATION
 INFO IF PACKAGE EQUIPMENT.
 PROVIDE INFO ON LOCATION OF
 CONDENSING UNITS FOR SPLIT SYSTEMS.
 MECHANICAL EQUIPMENT ON ROOF REQUIRES
 MINIMUM 18" OF CLEARANCE BETWEEN ROOF
 SURFACE AND BOTTOM OF EQUIPMENT STAND
 SUPPORT.
 3. PROVIDE INFO ON INSTALLATION OF AHU
 EQUIPMENT, CONDENSATE DRAIN, OVERFLOW
 PROTECTION, RETURN DUCT OR PLENUM, ETC.
 4. DOES DUCT RUN BETWEEN OLD TRUSSES OR
 NEW FLOOR ASSEMBLY.
 5. NEED INFORMATION ON FIRE PROTECTION
 OF ALL DUCTS PENETRATING RATED FLOORS,
 CEILING , OR WALLS.
 6. PROVIDE INFORMATION ON EXHAUST FANS
 REQUIRED FOR ALL BATHROOMS TO BE
 INSTALLED.
 7. PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 8. PROVIDE AIR BALANCE SCHEDULE PER
 1997SMC 501.2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-06 Cont ID  
Sent By ndenmark Date 2000-11-06 Time 14:01 Rev Time 1.00
Received By ndenmark Date 2000-11-06 Time 14:01 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
 1. INSUFFICIENT INFORMATION PROVIDED
 FOR REVIEW. PROVIDE INFORMATION ON
 MECHANICAL SYSTEM FOR BOTH FLOORS INCL.
 ANY REQUIRED FIRE PROTECTION OF RATED
 PENETRATIONS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-02-11 Cont ID  
Sent By pschmitz Date 2001-02-11 Time 11:17 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-26 Cont ID  
Sent By jleech Date 2001-01-26 Time 13:10 Rev Time 1.50
Received By pschmitz Date 2001-01-26 Time 13:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-22 Cont ID  
Sent By tlarge Date 2000-10-22 Time 07:43 Rev Time 3.75
Received By pschmitz Date 2000-10-22 Time 07:43 Sent To  
Notes
2001-01-08 00:00:001)SHT.SP-1-WATER CLOSETS AND FIXTURE
 BRANCHES ARE NNOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 2)RELIEF LINE AND PAN DRAIN FOR WATER
 HEATER SHALL DISCHARGE TO EXTERIOR PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.6.1
 507.8.3.
  
 3)PAN DRAIN AND PAN SHALL COMPLY W/SPC
 SEC.507.8.2.
  
 4)SHT.SP-1- SANITARY RISER SHOWS 2 LAVS
 ON 2ND FLOOR AND SHT.A-2 SHOWS FULL BATH
 SHOW ALL NEW PLUMBING ON THE SANITARY
 RISER.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 5)SHT.A-5-PLANS SHOW 8"STORM DRAIN
 DISCHARGING INTO 6"LINE.SPC SEC.307.5.
  
 6)INDICATE SLOPE OF STORM DRAIN PIPING
 ON PLANS.COMPLY W/SPC TABLE 1108.1,
 1108.2.
  
 7)SHOW SQ.FT.AREA OF ROOF DRAINED BY EA.
 ROOF DRAIN.COMPLY W/SPC TABLE 1108.1,
 1108.2.INCLUDE 1/2 AREA OF PARAPET WALLS
 PER SPC SEC.1108.3.
  
 8)SUBMIT CALCULATIONS FOR SECONDARY
 DRAINAGE.COMPLY W/SPC SEC.1109.2,1109.3,
 APPENDIX "A"& TABLE A101.2.
  
 9)CLEARLY SHOW DIMENSIONS OF OVERFLOW
 SCUPPER AND LOCATION OF SCUPPERS ON ROOF
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 10)SUBMIT A WATER RISER DIAGRAM FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 11)DRINKING FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 12)2ND.FLOOR BATH SHALL BE FULLY ACCESS-
 IBLE PER FACBC 4.1.3(11).
  
 13)VERTICAL ACCESSIBILITY SHALL BE
 PROVIDED TO THE 2ND FLR.PER FACBC SEC.
 4.1.3.,FLA.STATUTE 553.509.
  
 14)A DRINKING FOUNTAIN IS REQD.ON THE
 2ND.FLOOR PER SPC TABLE 407.DRINKING
 FOUNTAIN SHALL COMPLY W/FACBC SEC.4.1.3
 (10)(A).
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop Z ZONING
Rev No 2 Status N Date 2000-10-23 Cont ID  
Sent By lmartine Date 2000-10-23 Time 15:33 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-10-19 Cont ID  
Sent By gjoyce Date 2000-08-17 Time 10:52 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00DID NOT MEET DMP REQUIREMENTS