Plan Review Details - Permit 00080578
Plan Review Stops For Permit 00080578
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-10-25 Cont ID  
Sent By dpalmer Date 2000-10-25 Time 00:10 Rev Time 0.00
Received By dpalmer Date 2000-10-25 Time 00:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-10-18 Cont ID  
Sent By dpalmer Date 2000-10-18 Time 06:58 Rev Time 0.00
Received By dpalmer Date 2000-10-18 Time 06:58 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT THE PLANS ARE
 NOT SIGNED OR SEALED??? PLEASE SEE FL.
 STATE STATUES. 471.025 AND 61G15-23.002
  
 2)NOTE: PLEASE SEE FIRST TWO REVIEW
 NOTES. THEY BOTH NOTE NEC ARTS;210-52D
 AND 210-11-C-3 FOR DEDICATED BATH(S)
 MUST BE #12 AND 20AMP. YOU SHOW 15A AND
 #14 AWG. PLEASE CORRECT.
  
 3)NOTE: PLEASE NOTE THAT THE DRYER LOAD
 SHOWN EXCEEDS THE 80% OF BRKR RATING OF
 30A.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. THE PLANS ARE BEING DENIED FOR
 NOT BEING SIGNED AND SEALED.PLEASE MAKE
 THE CORRECTIONS FOR THE OTHER TWO NOTES.
 NOTE #2 HAS BEEN GIVEN TWICE BEFORE.
 ONCE AGAIN IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-10-04 Cont ID  
Sent By dpalmer Date 2000-10-04 Time 15:31 Rev Time 0.00
Received By dpalmer Date 2000-10-04 Time 15:28 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE ORIG NOTES. NOT ALL
 NOTES WERE ADDRESSED.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT. MAIN DISCONNECTS/PANELS
 ETC. 110-9 215-5
  
 3)NOTE: LIST REQ`D BATH(S) CIRCUIT(S)
 PER 210-52D/210-11-C-3
  
  
 PLEASE SUBMIT THE ABOVE ON NEW REDRAWN
 ELECTRICAL SHEET PER COUNTY/CITY WIDE
 ADMINISTRATIVE CODE. 104.2.7
  
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE "B"
 AHU#3 SHOWN AT 7KW AND LOAD SHOWN AT
 10KW. PLEASE CORRELATE.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-25 Cont ID  
Sent By dpalmer Date 2000-08-25 Time 12:35 Rev Time 0.00
Received By dpalmer Date 2000-08-25 Time 12:35 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT*******************
  
 1)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL
 EQUIPMENT BEING INSTALLED INCULDING
 MAIN DISCONNECTS AND PANEL. 110-9/215-5
  
 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE
 FOR "C". NOT SHOWN. 215-5
  
 3)NOTE; PLEASE SEE LOAD CALCULATIONS!!!
 SQ FT CALCS DO NOT CORRELATE WITH PLANS
 OR HOUSE BEING BUILT.215-5
  
 4)NOTE: PLEASE SHOW COLD WATER PIPE PER
 250-50
  
 5)NOTE: PLEASE SEE 210-8 FOR LAUNDRY
 ROOM REC.
  
 6)NOTE: PLEASE SEE 210-52 FOR OUTLET
 SPACING.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-17 Cont ID  
Sent By cthirben Date 2000-08-17 Time 08:01 Rev Time 1.00
Received By cthirben Date 2000-08-17 Time 08:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-16 Cont ID  
Sent By tlarge Date 2000-08-16 Time 06:18 Rev Time 0.33
Received By tlarge Date 2000-08-16 Time 06:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-09-30 Cont ID  
Sent By rmcdouga Date 2000-09-30 Time 10:51 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR ARCH
 WINDOWS PRIOR TO INSTALLATION.
  
 2)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN FOR STORM PANELS PRIOR TO INSTALL-
 ATION.
  
 3)PROVIDE SOIL COMPACTION TEST AT FIRST
 INSPECTION.
  
 5)GLAZING IN BATH ROOMS AND WITHIN TWO
 FEET OF SWINGING DOORS SHALL COMPLY WITH
 97 SBC 2405.2 AS APPLICABLE FOR SAFETY
 GLASS.
  
 6)PROVIDE PRODUCT APPROVALS FOR 9 FT.
 DOUBLE FRONT ENTRY DOORS PRIOR TO
 INSTALLATION.
  
 7)PROVIDE REVISED ROOF FRAMING DRAWINGS
 SPECIFYING GIRDER TRUSS TO BOND BEAM
 CONNECTORS AT EXTERIOR WALL NEAR BEDROOM
 #3 AND BREAKFAST ROOM, TRUSS TO BEAM
 CONNECTORS AT LIBRARY, MASTER BEDROOM
 AND BATH ROOM AREA & TRUSS TO WOOD
 GIRDERS AT FRONT ENTRY AND REAR PORCH
 PRIOR TO INSTALLATION OF TRUSSES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-18 Cont ID  
Sent By rmcdouga Date 2000-09-18 Time 10:08 Rev Time 5.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)DESIGN COMPLIANCE FORM MUST HAVE WET
 SIGNATURE OF ARCHITECT.
  
 2)MEAN ROOF HEIGHT ON DESIGN COMPLIANCE
 FORM DIFFERS FROM 32'-6" SHOWN ON SHEET
 A-5 OF PLANS. PLEASE CORRECT.
  
 3)PROVIDE INFORMATION FOR FOOTING AND
 COLUMN AT RIGHT SIDE OF GARAGE,SHEET A-2
  
 4)CLARIFY SIZE AND # OF REINFORCING
 STEEL IN THICKENED EDGE #1,SHEET A-2.
  
 5)PROVIDE SOIL COMPACTION TEST AT FIRST
 INSPECTION.
  
 6)CLARIFY TRUSS ANCHOR TYPES AND
 LOCATIONS AT LIBRARY AND MASTER BED ROOM
 AREA.SOME OF THESE ARE UNDISCERNIBLE.SEE
 SHEET A-8.
  
 7)PLEASE CORRECT WALL SECTION 2 ON SHEET
 A-9 THE 12" DIMENSION AT THE FOOTING IS
 UNCLEAR.
  
 8)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR ARCH
 WINDOWS.
  
 9)PROVIDE CONSTRUCTION DETAIL FOR ARCH
 OPENINGS.
  
 10)ALL NON-IMPACT RESISTANT GLAZING IS
 REQUIRED TO HAVE IMPACT PROTECTION.
 PROVIDE PRODUCT APPROVALS,KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS
 OR APPLY UNDER A SEPARATE PERMIT.
  
 11)PLEASE SPECIFY ON PLANS THE LOCATIONS
 OF GLAZINGS THAT ARE NOT IMPACT
 RESISTANT.
  
 12)97 FL ACCESSIBILITY CODE SEC.4.22.2
 REQUIRES A MINIMUM OF ONE ACCESSIBLE
 BATHROOM WITH A DOOR THAT HAS A 29"
 CLEAR OPENING.PLEASE INDICATE THE BATH-
 ROOM THAT MEETS THIS REQUIREMENT.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-15 Cont ID  
Sent By gjoyce Date 2000-08-15 Time 12:41 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***